Contrec 202A Analogue Input Rate Totaliser
SAFETY NOTICES
Only competent persons with the applicable training and authorisation should
work in potentially explosive atmospheres.
When this instrument is used in hazardous area, all wiring must be energy
limited according to the documentation provided and the marking label
attached to the instrument.
The safety of any system that incorporates Contrec 200 series instruments is
the sole responsibility of the system assembler/installer.
This manual must have been fully read and understood before the installation
and commissioning of any system using this instrument.
The instrument should only be operated if installed and maintained correctly
To ensure correct and safe operation of this instrument after installation and
maintenance the instrument should be fully sealed via the front screws and
gland entries.
SPECIAL CONDITIONS FOR SAFE USE
To comply with this product ATEX/IECEx/CSA certification the special conditions
for safe use must be followed.
The Instrument type 202Ai shall be mounted in an area where electrostatic
charge/discharge will be avoided.
INTRODUCTION
The Model 202Ai Rate-Totaliser is a microprocessor-based instrument designed
to measure a 4-20mA signal from flowmeters and pressure transducers. The
instrument can be programmed to display directly in engineering units and
includes features such as linear or square law calculation, integration and
digital filtering.
Rate, Total and Accumulated Total can be displayed in engineering units on the
large LCD display. A front panel switch selects the function for display and a
Reset button allows the Total to be reset to zero.
The instrument is fully programmable, with all calculation constants set via
the front panel switches and stored in a non-volatile memory which will retain
data indefinitely. The user can program span, filtering levels, display
resolution and cutoff point.
The instrument is powered from a 4-20mA input signal and therefore, requires
no external power.
The Model 202Ai Rate Totaliser conforms to the EMC-Directive of the Council of
European Communites 2014/30/EU, the LVD directive 2014/35/EU and the following
standards:
EN61326:2013
Electrical equipment for measurement, control and laboratory use – EMC
requirements: Residential, Commercial & Light Industry Environment &
Industrial Environment.
EN61010:2010
Safety requirements for electrical equipment for measurement, control, and
laboratory use.
In order to comply with these standards, the wiring instructions in Section 7.5 must be followed.
MODEL NUMBER VERSIONS
The Model Number describes the options available for the 202Ai as follows:
Model 202Ai.X0X.X
The first X denotes the mounting options and will be replaced by one of the following numbers:
- 0 No holes drilled for cable entry
- 1 Panel mount
- 2 Wall mount (standard)
- 6 for Pipe mounting
The Wall mount instrument is supplied with cable glands that are watertight and have integral strain relief.
The second X denotes approval Versions:
- C CSA USA / Canada Approval
- M ATEX/IECEx Approval
*The third X denotes enclosure Type:**
- A Aluminium
- S Stainless Steel
Example part number 202Ai.20M.A
NOTE – As standard the enclosure type is plastic, unless specified with
‘A’ or ‘S’ as above.
INTRINSIC SAFETY APPROVALS
The Model 202Ai is certified for use in hazardous areas and has IECEx, ATEX
and CSA U S/C approvals.
The Model 202Ai certification details are:
Ambient Temperature: Maximum ambient temperature of -20° to+60°C.
When installing in hazardous areas, the instrument must be installed according to the guidelines in Section 2 and in accordance with the local relevant standards for wiring and installation in hazardous areas. Failure to do so may result in the protection provided by the equipment becoming impaired.
When bearing the CSA mark, the instrument must be powered supply unit with a limited energy cisrcuoit in accordance with CAN/CSA C22.2 No. 61010-1-12 and ANSI/UL 61010-1, or Class 2 as defined in teh Canadian Electrical Code C22.1, Section 16-200 and/or National Electrical Code (NFPA 70), article 725.121.
MAXIMUM INPUT VALUES
4-20mA Input
The input can be connected to IS circuits with the following maximum values:
- Ui = 28V
- Ii = 93mA
- Pi = 653mW
Relay Outputs
The outputs can be connected to IS circuits with the following maximum values:
- Ui = 28V
- Ii = 93mA
- Pi = 653mW
SPECIFICATION
General
-
Display: LCD, which is continuously powered.
-
Resettable Total: 7 digits with 10mm (0.4″) high digits.
Resettable from front panel. -
Accumulated Total: Displayed when the Accumulated Total button is pressed.
-
Rate/Display: 4 digits with 8.5mm (0.33″) high digits.
-
Span: The units of measure per timebase (eg. gallons/sec) is programmable in the range 0.000001 to 999,999.
-
Decimal Points: Decimal Point positions are fully programmable for both rate and total.
-
Timebase: Span can be programmed in units per second,minute, hour or day.
-
Signal Type: 4-20mA.
4-20mA Input
Resolution and
-
Linearity: 0.05% of span.
-
Accuracy: 0.05% of span @ 25°C.
0.1% (typ) of span, full temperature range. -
Update Time: 0.5 seconds.
-
Connection: Two wire.
-
Voltage Drop: 2.5 volts maximum.
Outputs
-
Type: Two open collector outputs suitable for driving DC solenoids or external relays. The outputs provide high and low flow alarms or pulse
output and low flow alarm. -
Switching Power: 200mA. 30VDC maximum.
-
Saturation Voltage: 0.8VDC typical across the output in the “on” state.
-
Isolation: Both outputs are separately optoisolated.
-
Pulse Duration: If CAL00 = 1 (scaled pulse output): (for pulse output)
- a. 1ms if output frequency > 50Hz,
- b. 10ms if output frequency is 5 … 50Hz,
- c. 100ms if output frequency is < 5Hz.
Physical
-
Temperature: Operating Temperature: -20°C to 60°C.
-
Dimensions: 98mm (3.9″) high x 151mm (5.9″) wide x 43mm (1.7″) deep (cable glands not included).
-
Protection: Sealed to Nema 4x or IP67 standards.
-
Cable Entry: By cable glands.
-
Wall Mounting: Universal Mounting Bracket supplied as standard.
-
Pipe Mounting: A galvanised metal bracket is available which enables the Model 202A to be attached to a 2″ vertical or horizontal pipe.
-
Panel Mounting: Supplied with mounting brackets.
Terminals accessible from rear. (Note that the panel mount version is not watertight.)
Cutout: 141mm (5.6″) wide x 87mm (3.4″) high. -
Max Weight: Stainless Steel – 22200g, Aluminium 900g,Polycarbonate – 400g
Additional
- Pollution Degree: 2
- Over Voltage Catergory : II
- Maximum Altitude: 2000m above sea level
PROGRAMMING
The Model 202A is fully programmable, with all parameters being stored in
nonvolatile memory.
The Program Mode can be entered in one of two ways:
- Plastic Enclosure – By removing the lower plastic cover strip (ie. the dark grey strip along the bottom of the enclosure) and replacing it the wrong side up. This brings a small magnet on the inside of the cover strip in contact with a reed switch inside the instrument.
- Metallic Enclosure – By removing the metallic cover strip below the buttons. Unscrew the strip and replace the wrong side up. This brings a small magnet on the inside of the cover strip in contact with a reed switch inside the instrument.
The PROGRAM switch is used to step through the program (CAL sequences) and The
and keys on the front panel are used to change and increment the flashing
digits.
The CAL number is displayed on the lower display and the parameter is
displayed on the upper display.
Parameters in Program Mode that consist of the two parts, whole numbers and digits after the decimal point, are restricted to having a maximum of 6 significant digits. Therefore the number of significant digits entered in the whole numbers determines the number of digits that are able to be entered in the digits after the decimal point.
For Example
- 000001 in the whole numbers makes 00000 available after the decimal place.
- 000100 in the whole numbers makes 000 available after the decimal place.
- 010000 in the whole numbers makes 0 available after the decimal place.
OPERATION
The Model 202A Rate Totaliser will display:
- Rate
- Resettable Total
- Accumulated Total
Both the Rate and Resettable Total are continuously displayed while the
Accumulated Total is only displayed when the ACCUM TOTAL key is
pressed.
The Resettable Total can be reset at any time by pressing the RESET key.
The instrument also has a test mode which can be entered by simultaneously pressing all three front panel keys. The tests are as follows:
- Lo Test By pressing the ACCUM TOTAL key, the low alarm output will go low.
- Hi-Test By pressing the RESET key, the high alarm output:
- a. will go low if CAL00 = 0 (high alarm output),
- b. will output 100ms pulses every 0.5sec if CAL00 = 1 (scaled pulse output).
- Display Test By pressing the PROGRAM key, all segments of the display will show.
To exit the test mode, simultaneously press all three front panel keys.
Note that when the input signal drops below 3.75mA (4-20mA input), a signal error will occur. The display will alternate between the current total and the word “SIGNAL”. When the input signal drops below ≈3.5mA the Model 202A shuts down saving totals in the non-volatile memory.
PROGRAM STEPS
CALCULATION OF RATE AND TOTAL
Analog Input
The flowrate, R, is calculated as follows:
At the minimum input (i.e. 4mA), A = 0, and at the maximum input (ie.20mA), A
= 1.
The Span, S, can be set during calibration anywhere in the range of 0.000001
to 999,999.
The Span, S, is programmed in units of volume per timebase (ie. litres/minute
or kilograms/hour). This also means that the Total will be displayed with the
same unit of volume, ie. litres or kilograms.
The Cutoff Point
Because many transducers do not always exactly transmit 4mA when they are at
zero rate, it is often necessary to define a rate below which no integration
takes place. This is termed the cutoff point and is programmed as a percent
age of the Span, S.
For example, if S = 2200 kg/min in a square law system, and the cutoff point is set at 20.0%, the actual cutoff rate Rc can be determined as follows:
The cutoff rate is defined as:
At 20% cutoff,
Rc = 2200 x 0.2
= 440 kg/min
The value of A which would produce this cutoff is:
A = 0.04
and the input signal would be:
I = 16mA x 0.04 + 4mA
= 4.64mA
TOTAL CONVERSION
The Total Conversion feature enables the rate to be displayed in one engineering unit (e.g. gallons/minute) and the totals to be displayed in another engineering unit (e.g. barrels).
The Span is always programmed in the unit relating to Rate, and the Total Conversion constant is a division factor which can be used to convert the totals to the different unit. The Total Conversion factor affects the resettable and accumulated totals.
For Example.
If the Rate is required in gallons per minute:
-
The Span would be programmed as gallons per minute.
-
The timebase would be programmed as minutes.
If the Totals are required in barrels: -
The Total Conversion factor is programmed as 42 (there are 42 gallons in a barrel). All totals will now totalise in barrels.
Some common units are given below together with the Total Conversion constant which should be programmed.
Units per second, minute, hour or day. The timebase is programmed separately during Programming.
FILTERING
Frequency fluctuations caused by pulsating flow through a flowmeter, often
makes the Rate impossible to read with any precision.
The Model 202A has a digital filter which will average out these fluctuations
and enable the Rate to be read to four digit accuracy. The ability to select a
suitable filtering level means that highly accurate and stable readings can be
obtained without excessive lag.
The diagram below shows a pulsating signal input together with the effect of filtering.
As a guideline to the degree of filtering to be used, the following table shows the response to a step change in input. The value, CAL 06, is the filter constant which is programmed during the Programming routine. The times for the display value to reach 90% and 99% of full swing are given in seconds,for different values of CAL 06.
Table 1 – Response to a step Input (in seconds).
A | 90% | 99% |
---|---|---|
1 | 0 | 0 |
2 | 1 | 2 |
4 | 2 | 4 |
6 | 3 | 6 |
10 | 5 | 11 |
15 | 8 | 17 |
20 | 11 | 22 |
25 | 14 | 28 |
35 | 20 | 40 |
45 | 25 | 51 |
60 | 34 | 69 |
75 | 43 | 86 |
90 | 52 | 103 |
99 | 57 | 113 |
Note that if CAL 06 is set to 01 there is no filtering of the input signal.
EXAMPLE
A vortex flowmeter has a maximum output of 20.538 litres/min at 20mA. It is
required to display the flowrate in litres/min with 1 decimal point and the
total in litres with no decimals. High and low alarms are required at 18 l/m
and 2 l/m respectively. The instrument is then programmed as follows:
CAL00 | 0 | No Pulse Output |
---|---|---|
CAL01 | 00020 | Span (Whole Numbers) |
CAL02 | 5380 | Span (Decimals) |
CAL03 | 0.05 | Cutoff Point as a fraction of Span |
CAL04 | 1 | Rate decimal posi�on |
CAL05 | 1 | Timebase |
CAL06 | 01 | Filter disabled |
CAL07 | 0 | Total decimal posi�on |
CAL08 | 0001 | Total Conversion (set to 1.0000) |
CAL09 | 0000 | Total Conversion (decimals) |
CAL10 | 00002 | Low Alarm |
CAL11 | 0000 | Low Alarm |
CAL12 | 00018 | High Alarm |
CAL13 | 0000 | High Alarm |
CAL14 | 0 | Linear Input |
CAL15 | xxxx Accumulated Totals | |
SOFT | 202A1.11 | Software Version |
SIGNAL INPUT
The signal input is on terminals 3 and 4 and can be connected as follows:
ALARM & PULSE OUTPUTS
Open collector outputs are provided for high and low flowrate alarms. The
output can sink up to 200mA and can be used to power external relays, lights
or audible alarms. The outputs are internally protected against voltage spikes
caused by relays and coils.
Both outputs are separately isolated via opto isolators.
As an alternative to a high flowrate alarm, the output on terminals 7 and 8
can be programmed to output a scaled pulse output.
The switching points can be programmed during the setup mode and the low flow
alarm will switch on whenever the flowrate drops below the programmed
flowrate. Similarly, the high alarm switches on whenever the flow exceeds the
high setpoint.
If a Scaled Pulse Output is programmed, a pulse will be output every preset value of the total. For example, if the total is in litres, then programming 5 will output one pulse every 5 litres. The duration of pulses is adjusted automatically to the output frequency.
Specification for Alarm Outputs
- Maximum Current (sink): 200mA.
- Maximum Voltage: 30VDC.
- Saturation Voltage: 0.8VDC across Outputs when in the “on” state.
- Isolation: Both outputs are separately isolated.
- Pulse Frequency: 500Hz maximum.
- Pulse Duration: 1ms if output frequency > 50Hz.
10ms if output frequency = 5 … 50Hz.
100ms if output frequency < 5Hz.
Connection
INTRINSIC SAFETY CONNECTIONS
When installing the Model 202Ai in hazardous areas, the wiring and
installation must comply with appropriate installation standards.
The approval uses entity parameters and an associated apparatus type approval
on the input/output connections to the 4-20mA current loop and alarms. The
4-20mA input and alarm outputs must, therefore, only be connected as shown on
the following page, to barriers with the specified parameters.
The Model 202A will connect directly to a 4-20mA current loop and alarms, provided they do not exceed the following input parameters:
- Ui = 28V
- Ii = 93mA
- Pi = 653mW
The internal capacitance seen on the input (terminals 3 & 4) is 0.02uF while
the internal capacitance seen on the output (terminals 5-8) is 0.1uF maximum.
Inductance is negligibly small on both the input and output.
Outputs
The two open collector outputs must only be connected to certified IS
equipment via barriers as shown on the following page. Only certified
intrinsically safe solenoids may be used for IS applications.
INSTALLATION
WIRING
All wiring must be undergone by a competent person with the necessary training
and comply to all national and local standards and legislation
Use wire with a minimum temperature rating of ≥ 65 Degrees Celsius
When connecting the 202A it is good practice to use shielded cable. The shield
should be connected to earth at one end of the cable. The other end of the
shield should not be connected.
This wiring practice is mandatory in order to comply with the requirements for
Electromagnetic Compatibility as per EMC-Directive 2004/108/EC of the
Council of the European Community.
MAINTENANCE
All printed circuit boards must be repaired by Contrec. In the case of a
fault,no attempt should be made to repair the instrument as the intrinsically
safe certification may be impaired.
For further details contact Contrec Ltd or Contrec representatives listed at
the end of this manual.
All batteries for use in hazardous areas must be supplied by Contrec.
No substitute batteries are permitted as the battery packs contain certified
energy-limiting devices and insulation protection.
The inside of the instrument should remain clean and free of contaminants.
Ater routne maintenance the instrument must be re-sealed to ensure no ingress
occures
Cleaning
Clean with mild detergent or maximum 35% isopropyl solution
GENERAL
Ensure that all gland entries not used are blanked with IP rated gland
plugs/blanking caps.
The instrument should be installed so that it is protected from impact and extreme weather conditions
Install in a way the minimises vibration
THE MAIN ELECTRONICS
The front section of the housing contains the microprocessor and display.
It is also possible to adjust the display contrast via a small potentiometer
on the board. The DISPLAY CONTRAST control is shown below and this can be
adjusted for optimum contrast.
Adjacent to this control is a RESET switch which can be used to reset the microprocessor. Note that pressing this button will Set all totals to zero and calibration parameters to default values.
GROUNDING THE ENCLOSURE
NOTE. This only applies to the aluminium enclosure.
On one side of the enclosure a ground point is available to attach the 202A to the nearest protective earth (PE).
WALL MOUNTING
A wall mounting bracket is supplied with each instrument. The bracket should
be attached to the wall using round head screws (do not use counter-sunk
screws).
The bracket is mounted with the “tray” section at the bottom. The instrument
is then attached to the bracket at the bottom with two screws (see diagram
below).
FRONT PANEL
Removing the front panel – Plastic enclosure
Only open the instrument in a clean, dry environment
The front of the instrument is removed as follows:
- Remove both the top and bottom cover strips (i.e. the dark plastic strips on the front) by levering a screwdriver under one end.
- Undo the seven screws retaining the front. Note that the screws should not be removed from the front panel as they are retained by O-rings.
- Pull the front panel free from the housing.
Replacing the front panel of the instrument is the reverse procedure.
However, ensure that the front panel is aligned at both connector points
before tightening the screws.
Removing the front panel – Metallic enclosure
The front panel should be removed as follows:
- Unscrew the 4 x pozi drive head screws from each corner of the front panel.
- These are retaining screws, held onto the front panel with o-rings
- Once fully loosened the front panel will pull away from the housing.
To replace the front cover, follow the above procedure in reverse. Ensure that the front panel is aligned at connector points before tightening the screws.
If slightly stiff, the enclosure has a small gap on the right side of the front panel. This can be used to open the instrument with a tool.
PANEL MOUNT VERSION
The panel mount version of the Model 202Ai is supplied with two panel mount
brackets and plug-in terminals which are accessible from the rear of
the instrument.
A diagram of the rear panel is shown below.
REAR VIEW OF 202A
PANEL MOUNT CASE
The cutout for the panel mount version is 141mm (5.55″) wide x 87mm (3.43″) high.
NOTE – The aluminium enclosure can not be supplied as a panel mounting instrument
INSTRUMENT DIMENSIONS
- Aluminium / Stainless Enclosure
- Plastic Enclosure
TERMINAL DESIGNATIONS
4-20mA Input
- 4-20mA (-)
- 4-20mA (+)
Outputs
- Low Alarm (-)
- Low Alarm (+)
- High Alarm (-) or Pulse Output (-)
- High Alarm (+) or Pulse Output (+)
INSTRUMENT DISPOSAL
Contrec instrumentation should not be thrown into the general waste system.
If within EU member states, this instrument should be disposed of according to
the guidelines set by the WEEE (Waste Electrical and Electronic Equipment)
directive 2012/19/EU. If outside of the EU, this equipment should be
responsibly disposed of according to local and national regulations for EEE
(Electrical and Electronic Equipment).
By not discarding of this product along with other house hold waste you are preserving natural resources and reducing waste sent to landfill and incinerators.