Haier AV12IMAURA MRV-5-RC Heat Recovery Outdoor, 33kW User Guide
- June 9, 2024
- Haier
Table of Contents
MRV-5-RC Heat Recovery
Outdoor, 33kW
White
QUICK REFERENCE GUIDE > AV12IMAURA
AV12IMAURA MRV-5-RC Heat Recovery Outdoor, 33kW
Haier’s heat recovery outdoor unit and new valve box offer simultaneous cooling and heating in one system, with multiple indoor unit choices.
- Three-pipe full DC inverter heat recovery system
- Heating and cooling, with an operational range from -23°C to 50°C
- Outdoor units can work in parallel to power a range of indoor units
- Total connected pipe length up to 1000m with 110m lift height
DIMENSIONS
Height | 1690 mm |
---|---|
Width | 980 mm |
Depth | 750 mm |
FEATURES & BENEFITS
Commercial scale solutions
Outdoor units can work in parallel, providing combined cooling or heating
capacity up to 224kW and connecting to up to 64 indoor units of varying
capacity and style.
Heat recovery
The MRV-5-RC outdoor unit and three-pipe valve box can heat and cool
simultaneously using heat recovery. In a three-pipe system, heat absorbed from
a cooling indoor unit can be recovered and used by another indoor unit for
heating, and vice versa.
Efficiency
With full DC-inverter technology and a new four-way heat exchanger, MRV-5-RC
is designed to heat and cool large spaces efficiently.
Choose your indoor unit
Choose from our wall mount, slim duct, high static duct, compact cassette and
large cassette indoor air conditioner units to suit your environment.
Simple maintenance
The electrical control box is designed with a hinge to easily lift and swing
open for faster servicing and diagnostics.
Optional central controller
For personalised control of the whole system, a wall-mounted controller lets
you manage individual indoor units, groups or zones from a single point.
SPECIFICATIONS
Capacity
Cooling capacity (kW)| 33.5kW
Heating capacity (kW)| 35kW
Consumption
COP| 3.78
EER| 3.65
Features
Compressor type| DC INV. SCROLL
Inverter controlled compressor| •
Installation
Connectible indoor unit ratio| 50-130%
Liquid line| 12.7mm
Maximum number indoor units| 20
Suction line| 25.4mm
Performance
R410a refrigerant| •
Sound power SWL (outdoor)| 85dBA
Working temperature cooling| -5°C ~ +50°C
Working temperature heating| -23°C ~ +21°C
Power Requirements
Power phase| 3
Power supply| 50Hz
Supply voltage| 400V
Product dimensions
Depth| 750 mm
Height| 1690 mm
Net weight| 267kg mm
Width| 980 mm
SKU| 51528
The product dimensions and specifications in this page apply to the specific
product and model. Under our policy of continuous improvement, these
dimensions and specifications may change at any time. You should therefore
check with Fisher & Paykel’s Customer Care Centre to ensure this page
correctly describes the model currently available. ? 2020 Haier Inc. All
rights reserved.
Other product downloads available athaier.com
User Guide – Outdoor Unit
User Guide – Valve Box 1×1
User Guide – Valve Box 1×4
User Guide – Wired Controller YR-
E17A
User Guide – Wired Controller YR-
E16B
Installation Guide – Outdoor
Unit
Installation Guide – Valve Box
1×1
Installation Guide – Valve Box
1×4
Installation Guide – Wired Controller YR-
E17A
Installation Guide – Wired Controller YR-
E16B
Install Drawing
A PEACE OF MIND SALE
24 Hours 7 Days a Week Customer Support
T 1300 729 948 Wwww.haier.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>