SIEMENS RDG160TU Room Thermostat Instruction Manual
- June 9, 2024
- SIEMENS
Table of Contents
SIEMENS RDG160TU Room Thermostat Instruction Manual
RDG160TU Commercial Thermostat
After your RDG160TU thermostat has been installed, this document will guide you through the basic operations, such as changing the setpoint, switching between heating and cooling modes, and adjusting the fan speed. For the advanced user, see RDG160TU Commercial Thermostat Installation Instructions (129-588).
**Front Panel
**
Buttons
- A Heat/Cool Mode
- B Programming
- C Fan Mode/OK
- D Rotary knob
Main Display
Room temperature
Temperature in degrees Celsius
Temperature in degrees Fahrenheit
Buttons are locked
Alert/Fault indicator
Condensation indicator
System active by temporary timer
Day of Week
Setting time and weekday
Setting the timers
Current time of day
Escape (Cancel)
Confirmation (OK)
Operating Mode
Heating
Electric heater on
Cooling
Comfort mode
Economy mode
System active by programmed timer
Protection mode (Freeze Protection)
Indicates active icon
Fan Mode/Speed
Automatic
Manual
- Low Medium High
Changing Room Temperature
- The room temperature setpoint can be adjusted with the rotary knob when the system is in Comfort mode ( ) or is active by programmed timer ( )
- Turn the rotary knob clockwise (+) to increase, or counterclockwise (-) to decrease the current room temperature setpoint.
NOTE: The default setting range is from 41°F to 104°F (5°C to 40°C). To
change the limits, see RDG160TU Commercial Thermostat Installation
Instructions (129-588). – Parameters P09 and P10.
Adjusting the Fan Speed
- Press the FAN/OK button until the desired fan mode is reached.
- In Automatic mode ( ), fan speed is automatically controlled by the thermostat. When the setpoint is reached, the fan stops or keeps running at low speed.
- In Manual mode, the fan operates independently and always runs at the same speed: Low/Medium/High
NOTE: To customize available fan modes, adjust Parameter P03. See RDG160TU Commercial Thermostat Installation Instructions (129-588). Change Parameter P15 to set fan to OFF or LOW if the setpoint is reached.
Changing Between Heating and Cooling
- Depending on the heating/cooling system, the changeover between heating and cooling is either automatic by a changeover sensor, or manual by pressing the HEAT/COOL button.
- If the system is set up for manual changeover, press the HEAT/COOL button until the desired mode is selected.
- With automatic changeover or continuous heating/cooling, icons / indicate that the system is in heating or cooling mode.
- With manual changeover, the ( ) icon highlights the heating or cooling icons.
Changing the System Mode
Press the HEAT/COOL button until the ( ) icon appears. Continue until your choice of Protection, Comfort, Auto (Programmed) Timer, or Economy mode is selected.
-
Protection mode (Freeze protection)
The system is turned off, unless the room temperature falls below 46°F(8°C). At that point, heating is turned on to prevent freezing. -
Comfort mode
The thermostat maintains the setpoint, which are adjusted with the rotary knob. -
Auto (Programmed) Timer mode
The thermostat automatically switches between Comfort and Economy mode settings according to timers, if they are programmed (maximum eight). -
Economy mode
The room temperature is maintained between a lower heating setpoint and a higher cooling setpoint, to save energy and money.
NOTE: To change available options, and to adjust the default Comfort mode and Economy mode setpoints, change Parameter P02. See RDG160TUCommercial Thermostat Installation Instructions (129-588).
CAUTION:
The setpoint for Economy can be set to OFF. This means that the thermostat is
completely turned off, and there is no protective heating or cooling provided.
Setting the Time of Day
-
Press the PROG button.
-
Press the FAN/OK button to edit the time of day. The time digits start blinking.
-
Turn the rotary knob clockwise or counterclockwise to set. To change from 24-hour format to 12-hour format, turn the knob clockwise past 23:59 or counterclockwise past 00:00. Reverse those steps to return back to the 24-hour format.
Setting the Day of Week -
Press the FAN/OK button to confirm the time of day. The weekday indicator starts blinking.
-
Turn the rotary knob clockwise or counterclockwise to set the day of week.
-
Press the FAN/OK button to confirm the current weekday.
-
Press the HEAT/COOL button until (Esc) displays to exit the program mode.
NOTE: After a power failure, the time of day blinks. However, the auto (programmed) timers continue to run. Select the setting mode to readjust the time if needed.
![Setting the Day of
Week](https://manuals.plus/wp-content/uploads/2023/02/Screenshot_33-104.png)
Programming the Programmable Timers
The RDG160TU provides eight programmable timers A1 to A8. Any one of the timers can be assigned to one or multiple days. To set a timer, do the following:
-
Press the PROG button ( ).
-
Turn the rotary knob to the highlight the desired timer A1 to A8 to set and press the FAN/OK button .
-
Turn the rotary knob to set the Comfort mode start time ( ). Press the FAN/OK button to confirm.
-
Turn the rotary knob to set the Comfort mode end time ( ). Press the FAN/OK button to confirm.
-
Select which days of week to apply this timer to:
a. The icon for the first day of the week blinks. Press the FAN/OK button to select or the HEAT/COOL button (Esc) to deselect. The next day of week blinks.
b. Repeat select or deselect and advance to the next day.
c. Repeat until the 7th day is set. All selected days of week will blink. Press the FAN/OK button to confirm the setting and to advance to the next timer. -
To set the next timer, repeat Steps 3 through 5, or press the HEAT/COOL button (Esc) to exit the Timer Programming mode.
NOTES
- Press the FAN/OK button in Step 6 before pressing Esc (to exit the programming mode) to save your settings.
- To disable the timer function, set Parameter P02 = 3 or P02 = 4. See RDG160TU Commercial Thermostat Installation Instructions (129-588).
Reviewing the Settings
- Press the PROG button twice. .
- Turn the rotary knob to review the eight auto timers.
- Press HEAT/COOL button until (Esc) displays to return to normal operation.
Temporary Timer for Extended Presence or Absence
The Comfort and Economy modes can be temporarily extended from 0.5 to 9.5 hours.
To set the temporary timer, press and hold the HEAT/COOL button for a maximum of 3 seconds. While holding the button, do one of the following:
- Turn the rotary knob clockwise to extend the Comfort mode. Display: 0 to +9:30.
- Turn the rotary knob counterclockwise to extend the Economy mode. Display: 0 to -9:30. After the temporary timer has elapsed, the thermostat will resume operation in Auto Timer mode.
Reloading the Factory Default Timer (Schedule) Settings
- Press the PROG button twice ( ).
- Press the FAN/OK button to enter the Temporary Timer Setting mode.
- Press the PROG button for at least 3 seconds; rES displays.
- Press the FAN/OK button to confirm reloading the default settings, or (Esc) to exit without changing.
Table 1. Default Settings.
Day of Week | Time of Day When Thermostat is in Comfort Mode |
---|---|
Mon (1) through Fri (5) | 06:30 to 08:30 (A1) |
Sat (6) | 08:00 to 23:00 (A3 |
Sun (7) | 08:00 to 22:30 (A4) |
For the remaining time, the thermostat is in Economy mode. Timers A5 through |
A8 are blank, without settings.
Locking the Front Buttons
- To lock or unlock the buttons manually, press and hold the FAN/OK button for 3 seconds. The buttons are locked or unlocked in this manner if Parameter P14 is set to 2.
- If Parameter P14 is set to 1, buttons are locked 10 seconds after the last user adjustment.
NOTE: To enable the button locking from front panel, set Parameter P14 to 2. To enable the automatic button locking after 10 seconds, set Parameter P14 to 1. See RDG160TU Commercial Thermostat Installation Instructions (129-588).
Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as design improvements are introduced. Products or company names mentioned herein may be the trademarks of their respective owners. © 2016 Siemens Industry, Inc.
Siemens Building Industry, Inc.
Building Technologies Division 1000 Deerfield Parkway Buffalo Grove, IL
60089-4513 USA
Tel. +1 847-215-1000
Your feedback is important to us. If you have comments about this document, please send them to SBT_technical.editor.us.sbt@siemens.com
Document No. A6V10986942 Printed in the USA
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>