SIEMENS 194-2042 Pnuematic Room Thermostat User Guide
- June 9, 2024
- SIEMENS
Table of Contents
- SIEMENS 194-2042 Pnuematic Room Thermostat
- 192 S Single Setpoint Pneumatic Room Thermostats
- 192 DN/ DNV Day/ Night/ Vent Pneumatic Room Thermostats
- 192 HC Heating/ Cooling Pneumatic Room Thermostat
- 193 HC Free Energy Band Heating/ Cooling Pneumatic Room Thermostats
- 193 HC Hesitation Free Energy Band Heating/ Cooling Room Thermostats
- Thermostat Covers Thermostat Accessories
- 832 D “All-M etal” Pneumatic Room Thermostat
- Retroline™ Powerstar Pneumatic Room Retrostats
- 356 Limitem™ Rigid Bulb Thermostats
- 188 Unit M ounted Thermostats
- 357 D Limitem™ Remote Bulb Thermostats
- 134 Pneumatic High and Low Temperature Detection Thermostats
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
SIEMENS 194-2042 Pnuematic Room Thermostat
192 S Single Setpoint Pneumatic Room Thermostats
Features
- Single setpoint dial available in Fa.hrenheit or Celsius scales.
- Direct or reverse acting models
- Sensitive bimetallic element responds to temperature changes
- Integral, adjustable limit stops.
- Wall mounting plate included for easy connection to rough-in boxes.
Applications
Designed for heating and cooling applications for control of pneumatic valves
and damper actuators, the 192 S Single Setpoint Pneumatic Room Thermostat is
excellent for commercial and institutional facilities.
These are available with both 1-pipe and 2-pipe configurations.
- pipe: Use when limited output air capacity is required to operate a single valve and/ or actuator; requires external restrictor, 20 scim (5.4 ml/ s) air supply.
- pipe: Use for high output capacity for control of multiple valves and actuators, used with or without high/low limiting controls.
Click on this link for 192 S Technical Instructions
192 DN/ DNV Day/ Night/ Vent Pneumatic Room Thermostats
Features
- Dual setpoint dials available in Fahrenheit or Celsius scales.
- Direct or reverse acting models.
- Sensitive bimetallic element responds to temperature changes
- Manual override selector for off- hour occupant comfort.
- Adjustable changeover pressure.
Applications
The 192 DN/ DNV Pneumatic Room
Thermostat controls valves and damper actuators in cooling equipment,
automatically performing setback changes from day to night. The 192 DNV also
performs a purge sequence at night to bring in “ vent” outside air to cool the
building. A manual override selector switch allows individual room or zone “
day” control locally during the night cycle. During the night control cycle,
the 192 DNV models provide a separate output signal (full air supply) allowing
ventilation control. Periodic resetting to the “ night” control mode during
evening or weekend periods using time clocks ensures optimal energy
management.
Click on this link for 192 DN/ DNV Technical Instructions
192 HC Heating/ Cooling Pneumatic Room Thermostat
Features
- Dual setpoint dials available in Fahrenheit or Celsius scales.
- Direct or reverse acting models.
- Sensitive bimetallic element responds to temperature changes
- Integral, adjustable limit stops.
- Adjustable changeover pressure.
- Large volume air capacity relay
Applications
Designed for temperature control of heating and cooling applications, the 192
HC Heating/ Cooling Pneumatic Room Thermostat controls valves and damper
actuators in cooling equipment. Providing energy management and occupant
comfort, the thermostat automatically adjusts to seasonal changes from heating
setpoint to cooling setpoint in commercial and institutional facilities. It is
available in a 2-pipe configuration.
Click on this link for 192 HC Technical Instructions
193 HC Free Energy Band Heating/ Cooling Pneumatic Room Thermostats
Features
- Dual setpoint dials available in Fahrenheit or Celsius scales.
- Integral, adjustable limit stops.
- Sensitive bimetallic element responds to temperature changes
- Adjustable Free Energy Band.
- Wall mounting plate included for easy connection to rough-in boxes.
Applications
Designed for buildings with early morning heat requirements and mid-morning to
afternoon cooling requirements, the 193 HC Free Energy Band Pneumatic Room
Thermostat two temperature thermostat controls valves, damper actuators and
mechanical heating and cooling equipment. Providing energy management and
occupant comfort, the thermostat automatically reduces heating load and
increases cooling load.
pipe (dual 1-pipe): Use when a limited air capacity is required to
operate a single valve and/ or actuator.
pipe (dual 2-pipe): Use for multiple valves and actuators with or without
high/ low limiting controls which require higher air capacities.
Click on this link for 193 HC Technical Instructions
193 HC Hesitation Free Energy Band Heating/ Cooling Room Thermostats
Features
- Dual setpoint dials available in Fahrenheit or Celsius scales.
- Sensitive bimetallic element responds to temperature changes
- Integral, adjustable limit stops.
- Adjustable Free Energy Band.
- Wall mounting plate included.
Applications
The 193 HC Hesitation Free Energy Band Heating/ Cooling Pneumatic Room
Thermostat is an excellent choice for saving energy by sequencing heating and
cooling valves. In most heat/ cool pneumatic applications, a 3 to 8 psi (21 to
55 kPa) heating valve and a 10 to 14 psi (69 to 103 kPa) cooling valve are
used. By design, this provides a 2 psi (14 kPa) deadband where no heating and
cooling is occurring. The hesitation feature allows you to change the deadband
range to a 3, 4 or 5 psi (21, 28, or 34 kPa) range to save energy.
Click on this link for 193 HC Hesitation Technical Instructions
Thermostat Covers Thermostat Accessories
Thermostat Cover Features
- Covers are available with concealed or exposed setpoint adjustment, room temperature indication, and setpoint indicator.
- Available for 192, 193, and 832 series.
- 192 plastic covers in desert beige and white.
- 192 metal covers available in desert beige only.
Click on this link for Thermostat Covers Specification
Thermostat Accessories
- Thermostat accessories and calibration tools are available for the POWERS 192, 193, and 832 pneumatic thermostat series.
Click on this link for Pneumatic Thermostat Accessories Specification
832 D “All-M etal” Pneumatic Room Thermostat
Features
- All metal, rugged construction for dependable long-term service.
- Rapid response to temperature change
- Unique design of supply and exhaust air valves prevents waste.
- Quiet operation.
- Easy-to-calibrate and service.
Applications
Designed for controlling rooms heated or cooled by radiation, ventilation, or
an air conditioning system, the 832 D Pneumatic Room Thermostat is versatile
and responsive for individual room control.
Other applications include room control of radiant panels, finned radiation,
and unit ventilators.
Click on this link for 832 D Technical Instructions
Retroline™ Powerstar Pneumatic Room Retrostats
Features
- Complete kit including Retrostat cover kit with exposed or concealed setpoint adjustment.
- Setpoint dials available in Fahrenheit or Celsius scale.s
- Factory calibrated for accuracy.
- All installation hardware and calibration wrench provided.
- Integral, field adjustable limit stops.
Applications
Retroline Retrostat kits are available for most 2-pipe applications in direct
reverse acting models including single temperature, day/ night, and heat/
cool.
Click on this link for Retroline Installation Instructions
356 Limitem™ Rigid Bulb Thermostats
Features
- Durable copper motor tube and 18” (457mm) steel rod temperature sensing element.
- Two-valve design reduces air waste.
- Direct or reverse acting models.
- Duct mount hardware included.
- Rugged, all metal construction.
Applications
The 356 Limitem™ Rigid Bulb Thermostat provides primary control for unit
ventilators, fan coils and other air handling units. This device can also be
used as low limit control for air flow to a controlled space.
Available in three temperature operating ranges:
- 0 to 100 °F (-18 to +38°C)
- 30 to 180°F (-1 to +82°C)
- 100 to 250°F (38 to 121°C)
Click on this link for 356 Limitem Rigid Bulb Technical Instructions
188 Unit M ounted Thermostats
Features
- Liquid-filled thermal system temperature sensing element.
- Durable die-cast metal case with rugged setpoint knob.
- Adjustable sensitivity.
- Universal mounting bracket for easy installation.
- Integral adjustable limit stops.
Applications
The 188 Unit Mounted Thermostats are designed primarily for use in fan coil
induction units and unit ventilators to control the temperature within an
occupied space. The thermostat’s temperature range is limited to applications
at ambient temperatures.
Available with three control actions:
- Direct Acting only (Heating)
- Reverse Acting only (Cooling)
- Heat or Cool depending on supply air pressure
Click on this link for 188 Unit Mount Thermostat Technical Instructions
357 D Limitem™ Remote Bulb Thermostats
Features
- Direct acting operation only.
- Remote or averaging bulbs for flexibility in installation
- Liquid-filling sensing element for rapid response to changes in temperature.
- Two-valve design reduces air waste.
- Adjustable sensitivity.
Applications
The 357 D Limitem Remote Bulb Thermostat provides primary monitoring and
control for air handling units or a low limit control.
Available in three temperature operating ranges:
- Averaging Bulb Model: 35 to 145°F (2 to 63°C)
- Remote Bulb Model: 20 to 100°F (-7 to +38°C)
- Remote Bulb Model: 120 to 230°F (48.9 to 110°C)
134 Pneumatic High and Low Temperature Detection Thermostats
Features
- Snap-acting pneumatic switch.
- Sight-set calibrated setpoint scale.
- No leakage of air prior to reset of switch
- Easily adju.stable settings.
- Normally closed air valve; bleeds to less than 2 psi (14 kPa) when supplied through a restrictor.
Applications
The 134 Pneumatic High and Low Temperature Detection Thermostats are used on
pneumatic heating and cooling systems in areas protected from the weather.
On a typical high limit application, the thermostat shuts down air
conditioning or ventilating fans when the duct temperature becomes excessively
high. A normally closed switch opens at setpoint.
On a typical high limit application, the thermostat stops the fan or closes a
damper when the temperature drops to the setpoint at any one foot (30.5 cm) or
more of the sensing element.
Click on this link for 134 High-Low Temp Detect Technical Instructions
Information in this document is based on specifications believed correct at the time of publication. The right is reserved to make changes as design improvements are introduced. POWERS is a trademark of Siemens Industry Inc. Product or company names mentioned herein may be the trademarks of their respective owners. © 2017 Siemens Industry, Inc.
Siemens Industry, Inc. Building Technologies Division 1000 Deerfield Parkway
Buffalo Grove, IL 60089-4513 USA
+ 1 847-215-1000
Your feedback is important to us. If you have comments about this document,
please send them to
SBT_technical.editor.us.sbt@siemens.com
Document No. A6V112210116 Printed in the USA
Scan code to download this reference guide
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>