PENTAIR G2DT-01 1 Phase Simplex Control Panel for Grinder and Vortex Pumps User Manual

June 9, 2024
Pentair

PENTAIR logo

PENTAIR G2DT-01 1 Phase Simplex Control Panel for Grinder and Vortex

Pumps

Introduction

Before proceeding with the installation or operation of the control panel read all instructions thoroughly as well as comply with all Federal, State and Local Codes, Regulations and Practices. The control panel must be installed by qualified personnel familiar with all applicable local electrical and mechanical codes. Refer to the National Electrical Code (NFPA 70). Failure to properly install and test this product can result in personal injury or equipment malfunction. All conduit connected to the panel must be sealed with conduit sealant to prevent moisture or gases from entering the panel. NEMA 1 enclosures are for indoor use only while NEMA 4X panel enclosures may be used indoors or outdoors. Refer to panel model name-plate on inside of door for enclosure rating. Note: If options are ordered that affect the number of floats, refer to the panel schematic for complete information.

This Control Panel Is Used With The Following Pumps

G2DT-01   G2DT-21     V1D-01     V1D-21     G2D-01     G2D-21     V15D-01
V15D-21    V2D-21       G3D-01     G3D-21     V2D-01     V3D-01      V3D-21

Safety Guidelines

  1. DO NOT USE WITH FLAMMABLE OR EXPLOSIVE FLUIDS SUCH AS GASOLINE, FUEL OIL, KEROSENE, ETC. DO NOT USE IN EXPLOSIVE ATMOSPHERES. CONTROL PANEL SHOULD ONLY BE USED IN WATER AND WASTEWATER APPLICATIONS THAT ARE NOT RATED AS A HAZARDOUS LOCATION.
  2. DO NOT WORK ON THE CONTROL PANEL WITH LIVE VOLTAGE APPLIED TO THE CONTROL PANEL WITH WET HANDS OR WHEN STANDING ON A WET SURFACE.
  3. DISCONNECT ALL ELECTRICAL SERVICE BEFORE WORKING OR HANDLING THE CONTROL PANEL.
  4. INCOMING VOLTAGE MUST MATCH THE CONTROL PANEL VOLTAGE. REFER TO THE PANEL SCHEMATIC FOR COMPLETE INFORMATION.

Installation of the Control Panel

  1. Determine mounting location for the control panel. If splicing is required between the level switches and the panel, we recommend a junction box. CAUTION! Use conduit sealant and waterproof wire nuts for connections. Make sure all connections are water tight.
  2. Determine conduit entrance locations on control panel and install per local codes. Check schematic and determine number of power sources required. Use conduit sealant on all conduits to prevent moisture and gases from entering control panel.
  3. Connect control/alarm and pump power conductors to the proper terminals. The schematic and terminal blocks will be labeled for proper connection.
  4. Verify correct panel operation after installation of panel, power and level switches are complete.

Installing the Starter Pack

1. The Starter Pack (Fig. A) comes pre assembled with the start capacitor (1)

run capacitor (2) and start relay (3) mounted on a plug and play bracket.

PENTAIR G2DT-01 1 Phase Simplex Control Panel for Grinder and Vortex Pumps
1

2. Use the empty space on the top right side of the control panel to mount

the Starter Pack. (Fig. 1). To secure the Starter Pack to the control panel, place (Fig. 3) on top of (Fig. 2) by setting the bracket on top of the screws (Fig. 4), then slide the bracket down so the screws are in the narrow part of the mounting holes (Fig. 5), then tighten the screws.

PENTAIR G2DT-01 1 Phase Simplex Control Panel for Grinder and Vortex Pumps
2

3. After securing the Starter Pack inside of the control panel (Fig. 6) you

will connect the wires from the Starter Pack to the top of the terminal blocks (Fig. 7). W=White, B=Black, R=Red

PENTAIR G2DT-01 1 Phase Simplex Control Panel for Grinder and Vortex Pumps
3

Connecting the Pump and Thermal Wires:
Your pump has 5 colored wires. White, Black, Red, Blue and Orange
Pump Connection: The White, Black and Red wires connect to the terminal block labeled Pump Connection.W=White, B=Black, R=Red
Pump 1 Thermal Sensor: The remaining two wires will be Blue and Orange. They are connected to the terminal block labeled Pump 1 Thermal Sensor. BL=Blue, OR=Orange

Testing the Thermal Sensor:

1. Put one ohm meter probe on the Blue wire and one on the Orange wire.

2. If the reading is 0 or near 0 the thermal sensor is good.

If the reading is OL the pump has been or currently is overloaded.

PENTAIR G2DT-01 1 Phase Simplex Control Panel for Grinder and Vortex Pumps
4

PENTAIR G2DT-01 1 Phase Simplex Control Panel for Grinder and Vortex Pumps
5

Pump 1 Seal Fail Probe: (Seal Fail may not be an option on your pump)
The Seal Probe wires are connected to terminals 9 and 10 which are labeled Pump 1 Seal Sensor. The Black wire from the Seal Probe is connected to terminal 9 which is labeled BK for Black. The Yellow wire from the Seal Probe is connected to terminal 10 which is labeled YW

PENTAIR G2DT-01 1 Phase Simplex Control Panel for Grinder and Vortex Pumps
6

Testing Seal Fail Probes:

  1. Put one ohm meter probe on the Black wire of the sensor.
  2. Place the other ohm meter probe on the “Hex” Nut portion of the sensor. The ohm meter should read “continuity” or close to zero ohms, If it reads “open” or “High” ohms then the sensor is defective.
  3. Put one ohm meter probe on the seal probe.
  4. Place the other ohm meter probe on the yellow wire. The ohm meter should read “continuity” or close to zero ohms, If it reads “open” or “High” ohms then the sensor is defective.

PENTAIR G2DT-01 1 Phase Simplex Control Panel for Grinder and Vortex Pumps
7

Setting Overload FLA to Pump FLA:
Use a phillips head screwdriver to adjust the yellow dial to the full load amps (FLA) of your pump. i.e. If the FLA of your pump is 6.0 you would set the yellow dial on the overload relay to 6.

PENTAIR G2DT-01 1 Phase Simplex Control Panel for Grinder and Vortex Pumps
8

Mounting Level Switches:
Float switches are most commonly used, but 1 Phase Simplex Grinder & Vortex control panels can also be used with any dry contact type of level or pressure switch. Illustration shows float switches installed for pump down applications. Refer to float switch instructions for mounting of clamp or weighted floats.

PENTAIR G2DT-01 1 Phase Simplex Control Panel for Grinder and Vortex Pumps
9

To verify the Overload has tripped.
Use an ohm meter to verify if an overload has tripped. Place one of the ohm meter probes on terminal 97 of the overload and place the other probe of the ohm meter on 98 of the overload. If your reading is high the overload is not tripped. If your reading shows continuity or 0 ohms, the unit is tripped and should be reset.

PENTAIR G2DT-01 1 Phase Simplex Control Panel for Grinder and Vortex Pumps
10

PENTAIR G2DT-01 1 Phase Simplex Control Panel for Grinder and Vortex Pumps
11

PENTAIR G2DT-01 1 Phase Simplex Control Panel for Grinder and Vortex Pumps
12

Incoming Power Configurations:
Illustrations below shows how to connect power for the pump and the control circuits. Use two incoming power sources. (A) is the pump circuit and (B) is the alarm circuit.

PENTAIR G2DT-01 1 Phase Simplex Control Panel for Grinder and Vortex Pumps
13

Simplex Circuit Board Command Center

  • There is one HOA (Hand-Off-Auto) switch. This HOA switch is also used as the System Test switch for diagnosing the control panel.
  • Two green power “on” indicators provide visual indication for the control and alarm fuses. Fuses must be replaced with 1 amp fast acting 5mm X 20mm fuses.
  • The Pump Run indicator light is green. If this light is illuminated the pump is running.
  • The Stop float, Start float and Alarm float indicator lights are red.

PENTAIR G2DT-01 1 Phase Simplex Control Panel for Grinder and Vortex Pumps
14

Circuit Board Terminal Blocks:
1 Phase Simplex Grinder & Vortex control panels use two terminal blocks for alarm mode configura-tions. An 8 position main terminal block is for power and level switch connections. A separate 3 posi-tion terminal block is used for dry auxiliary contacts. A 5 amp, 120 VAC max load can be applied to the auxiliary terminals. The auxiliary contacts are Form C, Single Pole, Double Throw. (Common, Normally Open, Normally Closed). Contacts change state when in alarm condition.

PENTAIR G2DT-01 1 Phase Simplex Control Panel for Grinder and Vortex Pumps
15

1 Phase Simplex – How to use the System Test switch

  1. Check the incoming power on the top of the command center.PENTAIR G2DT-01 1 Phase Simplex Control Panel for Grinder and Vortex Pumps 16
  2. View the current status of your system. The indicator lights illuminate as each float rises with the liquid level in the tank.

PENTAIR G2DT-01 1 Phase Simplex Control Panel for Grinder and Vortex Pumps
17

PENTAIR G2DT-01 1 Phase Simplex Control Panel for Grinder and Vortex Pumps
18

Operating the pump manually with the HOA (Hand-Off-Auto)

PENTAIR G2DT-01 1 Phase Simplex Control Panel for Grinder and Vortex Pumps
19

PENTAIR G2DT-01 1 Phase Simplex Control Panel for Grinder and Vortex Pumps
20

Using the System Test switch to troubleshoot your control panel.

PENTAIR G2DT-01 1 Phase Simplex Control Panel for Grinder and Vortex Pumps
21

  • Place the HOA (Hand-Off-Auto) switch in the “Hand” position. The Pump Run indicator light will illuminate and the pump will turn on.
  • Place the HOA (Hand-Off-Auto) switch in the “Hand” position and you will be automatically checking the true status of the floats.
    EXAMPLE: Fig #2. The green pump run light is illuminated because the HOA switch is in the hand mode.

PENTAIR G2DT-01 1 Phase Simplex Control Panel for Grinder and Vortex Pumps
22

PENTAIR G2DT-01 1 Phase Simplex Control Panel for Grinder and Vortex Pumps
23

PENTAIR G2DT-01 1 Phase Simplex Control Panel for Grinder and Vortex Pumps
24 293 S. Wright St, Delavan, WI 53115 Phone: 1-866-973-6835 Fax: 800-426-9446

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Pentair User Manuals

Related Manuals