PENTAIR SSM33I Submersible Sump Effluent Owner’s Manual
- June 9, 2024
- Pentair
Table of Contents
- TYPICAL SECTION DRAWING FOR SSM33/SSM33I SERIES
- TYPICAL SECTION DRAWING FOR SRM4 SERIES
- PARTS LIST SSM33/SSM33I AND SRM4
- \CHART
- DESCRIPTION AND APPLICATION
- AIR LOCKING
- PACKAGING
- LEVEL CONTROLS
- DESIGN OF PRESSURE SEWER SYSTEMS
- CSA APPROVED
- INSTALLATION
- POINTS TO CHECK IF PUMP DOES NOT RUN OR DOES NOT RUN PROPERLY
- BEFORE DISMANTLING PUMP FOR REPLACEMENT OF PARTS
- TYPICAL SUMP INSTALLATION FOR SSM33/SSM33I Series
- TYPICAL SUMP INSTALLATION FOR SRM4 SERIES
- TO REPLACE AUTOMATIC FLOAT
- TO REPLACE THE AUTOMATIC VERTICAL FLOAT SWITCH
- TO REPLACE THE AUTOMATIC VERTICAL AND DIAPHRAGM FLOAT SWITCH
- SRM4 SHAFT SEAL REPLACEMENT
- POWER CORD REPLACEMENT
- MOTOR REPLACEMENT
- PERFORMANCE CURVES
- CUSTOMER SUPPORT
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
PENTAIR SSM33I Submersible Sump Effluent
TYPICAL SECTION DRAWING FOR SSM33/SSM33I SERIES
TYPICAL SECTION DRAWING FOR SRM4 SERIES
PARTS LIST SSM33/SSM33I AND SRM4
Ref No. | No. Description | Part Reqd | Numbers |
---|---|---|---|
2 | Ring, Lift | 1 | 26230A000 |
3 | Plug, 1/4” NPT | 1 | 05022A056 |
4 | Plate, Name (Not Stamped) | 1 | 23780A000 |
5 | Tapping, Screw (SSM33/SSM33I) | 1 | 09822A032 |
5 | Tapping, Screw (SRM4P Auto.) | 1 | 09822A006 |
5A | Screw, Cap #10 x ¾ Vertical Float Switch | 2 | 18475A004 |
6 | Oil, Transformer (1 Qt. In Can) | 1 | 11009A002 |
8 | Rotor with Shaft (SSM33/SSM33I) | 1 | 22821A010 |
8 | Rotor with Shaft (SRM4) | 1 | 22821A000 |
9 | Washer, Thrust, SST | 1 | 05030A243 |
10 | Washer, Thrust, Graphite | 1 | 05030A244 |
11 | Housing, Motor | 1 | 23770D002 |
Housing w/Stator 115V (SRM4P) |
230V (SRM4P)
115V (SSM33/SSM33I)| | 23770D060K
23770D061K
23770D062K
12| Seal, ½” Shaft| 1| 21607A001
13| Gasket, Rubber| 1| 05014A172
14| Screw, Cap, 1/4-20 x 7/8 Lg. (SSM33/SSM33I) (SRM4)| 3
6| 18475A003
18475A003
15| Case, Volute (SSM33)| 1| 23771D001
15| Case, Volute (SSM33I)| 1| 23771D101
16| Impeller (SSM33)| 1| 22370B000
16| Impeller (SSM33I)| 1| 084980031
17| Plate, Bottom, with Volute Case| 1| 27005D000
Ref No. | No. Description | Part Req’d | Numbers |
---|---|---|---|
18 | Screw, Tapping, #10 x 1” Lg. |
(SSM33, SRM4)
| 3| 09822A036
18| Screw, Tapping, #10 x ¾” Lg.
(SSM33I)
| 3| 18475A008
19| Screw, Tapping, #10 x 1¾” Lg.
(SSM33, SRM4)
| 3| 09822A040
19| Screw, Tapping, #10 x 1-5/8” Lg.
(SSM33I)
| 3| 18475A009
20| Control, Level, 115V, 10’
Piggy-Back Float Switch
| 1| 21813B130
20| Control, Level, 115V, 20’
Piggy-Back Float Switch
| 1| 21813B131
20| Control, Level, 230V, 10’
Piggy-Back Float Switch
| 1| 21813B132
20| Control, Level, 230V, 20’
Piggy-Back Float Switch
| 1| 21813B133
20| Vertical Control Switch – 10’ Cord| 1| 26292B140
20| Vertical Control Switch – 20’ Cord| 1| 26292B141
20| Diaphragm Control Switch – 20’ Cord| 1| 149740195-01
20A| Mounting Bracket, Control Switch| 1| 26291B010
21| Tie, Cable| 1| 17190A008
22| Plate, Seal (SRM4)| 1| 23773D002
23| Case, Volute (SRM4)| 1| 21612D000
24| Impeller (SRM4)| 1| 21610B000
Not Shown| Bracket, Float (SSM33/SSM33I)| 1| 24003A000
Not Shown| Bracket for Diaphragm (SRM4D-1 Only)| 1| 055020111
\CHART
Pump Catalog Number| Pump Engineering Number| Pump Switch|
HP| V| Ph| Cord, Electric| Cord Length| 7
Stator Only| Winding Resistance in Ohms| Max. Amps| Locked
Rotor Amps| Switch
---|---|---|---|---|---|---|---|---|---|---|---|---
On| Off
SSM33IM1C| 26235D100| Manual| 1/3| 115| 1| 21628B048| 20′| 22757B010| 1.3| 9|
12.5| –| –
SSM33IP-1| 26235D110| Automatic| 1/3| 115| 1| 21628B046| 10′| 22757B010| 1.3|
9| 12.5| 9 – 15/16″| 4 – 1/16″
SSM33IPC-1| 26235D111| Automatic| 1/3| 115| 1| 21628B048| 20′| 22757B010| 1.3|
9| 12.5| 9 – 15/16″| 4 – 1/16″
SSM33IPV1| 26235D120| Automatic| 1/3| 115| 1| 21628B046| 10′| 22757B010| 1.3|
9| 12.5| 5 – 7/8″| 1 – 3/4″
SSM33IPV1C| 26235D121| Automatic| 1/3| 115| 1| 21628B048| 20′| 22757B010| 1.3|
9| 12.5| 5 – 7/8″| 1 – 3/4″
SRM4M1C| 26236D001| Manual| 4/10| 115| 1| 21628B048| 20′| 21599B026| 1.2| 12|
16| –| –
SRM4M2C| 26236D003| Manual| 4/10| 230| 1| 21628B049| 20′| 21599B027| 4.3| 6|
8.2| –| –
SRM4P-1| 26236D010| Automatic| 4/10| 115| 1| 21628B046| 10′| 21599B026| 1.2|
12| 16| 13 – 7/8″| 8 – 1/8″
SRM4PC-1| 26236D011| Automatic| 4/10| 115| 1| 21628B048| 20′| 21599B026| 1.2|
12| 16| 13 – 7/8″| 8 – 1/8″
SRM4PC-2| 26236D013| Automatic| 4/10| 230| 1| 21628B049| 20′| 21599B027| 4.3|
6| 8.2| 13 – 7/8″| 8 – 1/8″
SRM4V-1| 26236D041| Automatic| 4/10| 115| 1| 21628B048| 20′| 21599B026| 1.2|
12| 16| 6 – 1/4″| 2 – 7/8″
SRM4V-2| 26236D043| Automatic| 4/10| 230| 1| 21628B049| 20′| 21599B027| 4.3|
6| 8.2| 6 – 1/4″| 2 – 7/8″
SRM4D-1| 26236D061| Automatic| 4/10| 115| 1| 21628B048| 20′| 21599B026| 1.2|
12| 16| 11″| 3″
NOTE: READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO INSTALL PUMP
DESCRIPTION AND APPLICATION
SM33, SSM33I and SRM4 Myers SSM33, SSM33I and SRM4 Series Pumps are single seal units, available in automatic or manual. The SSM33 and SSM33I series pumps are designed for normal sump and dewatering, and can also be used in effluent applications. When used in effluent dosing or S.T.E.P. applications,the pump must be installed in a separate tank or compartment at the discharge side of the septic tank. NEVER INSTALL PUMP IN MAIN TANK WHERE SLUDGE COLLECTS. DONOT USE THE SSM33 OR SSM33I PUMP SERIES FOR RAW SEWAGE. The SRM4 series pumps are designed forresidential sewage and dewatering applications where a larger solid size is required.
General
The SSM33, SSM33I and SRM4 pumps use shaded pole,1550 RPM motors. SSM33 and
SSM33I are available in 115 volt only and the SRM4 is available in 115 or 230
volt and all are single phase only. Both the manual and automaticmodels come
standard with a 10 ft. power cord. A 20 ft. cord and switch length are
optionally available. All automatic models come with a mechanical (mercury
free) piggy-back float switch or a vertical float switch. The SSM33 and SSM33I
pumps are designed to handle 1/2” spherical solids and have a 1-1/2” NPT
discharge threading. The SRM4 pumps are designed to handle 2” spherical solids
and have a 2” NPT discharge threading. The SSM33, SSM33I and the SRM4use an
engineered thermoplastic vortex impeller designed to efficiently produce the
required pressures and flows.
WARNING! THESE PUMPS ARE NOT APPROVED FOR, AND SHOULD NOT BE USED IN
SWIMMING POOLS, FOUNTAINS OR PUMPING POTABLE (DRINKING) WATER.
AIR LOCKING
A pump is said to be air locked if water traps air in the pump and it cannot
get out, thus preventing the pump from operating.
The SSM33, SSM33I and SRM4 sump pumps have a 1/16” air vent hole in the
impeller chamber to let out trapped air. If this hole becomes plugged, pump
may air lock. As a secondary precaution a 1/8” hole should be drilled in
thedischarge pipe below the check valve. The check valve should be 12 to 18
inches above pump discharge. Do not put check valve directly into pump
discharge opening
PACKAGING
Each pump is packaged separately in a carton marked with a catalog number and Myers engineering number. The pumps are carefully packaged to prevent damage in shipping. However, occasionally damage may result due to rough handling. Carefully go over the pump and check for damage that could cause the pump to fail.
LEVEL CONTROLS
The automatic models come with 10’ or 20’ power cord and mechanical (mercury
free), piggy-back float switch. The 115 or 230 volt piggy-back switch is
tethered directly to the pump. The switch can optionally be mounted to the
discharge pipe using a minimum 3-5/8” tether length. The switch must float
free from pump and basin wall. Plug the switch cord plug into a properly
grounded, rated voltage receptacle. Plug the power cord into the back of the
switch cord and tape the cords to the discharge pipe every 12”. The power
receptacle must be located outside the wet sump or basin due to the DANGER of
current leakage.
On all duplex units or simplex installations with additional options like high
water alarm, the power cord plug must be cut off and wired into a control
panel or into a sealed junction box if used in wet sump or basin. The AWS-1
control also acts as a sealed junction box for connecting power cord to pump
cord.
DESIGN OF PRESSURE SEWER SYSTEMS
Myers has available complete computer SOFTWARE for designing PRESSURE SEWER SYSTEMS. This gives pipe sizes to use and gives exact flow from any pump or group of pumps in the system when operating simultaneously. This design DISK for IBM® or COMPATIBLE computers is available to engineers on request.
MOTOR TYPE
WARNING: Risk of electric shock. Pumps are supplied with a grounding
conductor and grounding-type attachment plug on the power cord. To reduce the
risk of electric shock, be certain that it is connected only to a properly
grounded, grounding-type receptacle. DO NOT cut off ground pin or use an
adapter fitting. DO NOT use an extension cord with this pump.
All pumps have a GROUND WIRE that is connected to the motor. This wire goes
to the receptacle or control panel whichmust be connected to a good outside
GROUND. When wiring this pump follow all local electrical and safety codes and
ordinances as well as the most recent National Electric Code (NEC-ANSI/NFPA
70).
CALIFORNIA PROPOSITION 65 WARNING
This product and related accessories contain chemicals known to the State of California to cause cancer, birth defects or other reproductive harm.
CSA APPROVED
All pumps have CSA approval. Myers is a SSPMA certified pump member.
INSTALLATION
WARNING: Basin or tank must be vented in accordance with local plumbing
codes. These pumps are not designed for and CANNOT be installed in locations
classified as hazardous in accordance with the National Electric Code
ANSI/NFPA 70.
CAUTION: Never enter pump chamber after sewage or effluent has been in
basin. Sewage water can give off methane, hydrogen sulfide and other gasses
which are highly poisonous. For this reason, Myers recommends installing
effluent pumps with a quick removal system. The quick removal system may be a
union or coupling if the pipe or discharge hose is within reach from the
surface, or a rail system type quick disconnect on deeper installations. See
installation drawings for suggested installation.
The dosing tank or pumping chamber must be constructed of corrosion resistant
materials and must be capable of withstanding all anticipated internal and
external loads. It also must not allow infiltration or exfiltration. The tank
must have provisions for anti-buoyancy. Access holes or covers must be
adequate size and be accessible from the surface to allow for installation and
maintenance of the system. Access covers must be lockable or heavy enough to
prevent easy access by unauthorized personnel. The pumping chamber holding
capacity should be selected to allow for emergency conditions.
The discharge pipe must be the same size as the pump discharge 1-1/2” for
SSM33 and SSM33I, 2” for SRM4 or larger. In order to insure sufficient fluid
velocity to prevent any residual solids from collecting in the discharge pipe,
it is recommended that a minimum flow of 2’ per second be maintained. (12 GPM
through 1-1/2” pipe, 21 GPM through 2” pipe and 46 GPM through 3” pipe). It is
recommended thatPVC or equal pipe is used for corrosion resistance. A full
flow (ball or gate) shut off valve must be installed to prevent back flow of
effluent if the pump must be removed for service. A check valve must be
installed on pressure sewer systems and on other systems where conditions
allow to prevent backflow and to reduce wear on the pump system.
A high water alarm must be installed on a separate circuit from the pump
circuit. The alarm should have the ability to be tested for proper operation.
POINTS TO CHECK IF PUMP DOES NOT RUN OR DOES NOT RUN PROPERLY
-
Pump does not run or start when water is up in tank.
(a) Check for blown fuse or tripped circuit breaker.
(b) Check for defective level switch
(c) Where control panel is used be sure H-O-A switch is in the AUTO position. If it does not run, turn switch to the HAND position and if the pump runs then thetrouble is in the automatic electrical system. Have ELECTRICIAN make electrical checks.
(d) Check for burned out motor. Occasionally lightning can damage a motor even with lightning protection.
(e) Where plug-in cords are used be sure contact blades are clean and making good contact. DO NOT USE PLUG-IN CORDS INSIDE A SUMP OR WET WELL.
(f) Level control ball or weight may be stuck on side of basin. Be sure it floats freely. -
Pump runs but does not deliver flow.
(a) Check for airlock. Start and stop pump several times,if this does not help it may be necessary to loosen a union in the discharge line to relieve airlock.
(b) Check valve may be installed backwards. Check flow arrow on valve body. Check shut-off valve. It may be closed.
(c) Check vertical elevation. It may be higher than pump can develop. (See pump curve).
(d) Pump inlet may be plugged. Remove pump to check.
CAUTION: ALWAYS UNPLUG POWER CORDS OR TURN OFF ALL MAIN AND BRANCH CIRCUIT BREAKERS BEFORE DOING ANY WORK ON THE PUMP. If control panel is remote from pump, disconnect lead wires to motor so that no one can turn the circuit breaker back on.
BEFORE DISMANTLING PUMP FOR REPLACEMENT OF PARTS
Clean pump thoroughly. Knock off all scale and deposits. Submerge complete unit on Clorox solution for one hour before taking apart.
TYPICAL SUMP INSTALLATION FOR SSM33/SSM33I Series
TYPICAL SUMP INSTALLATION FOR SRM4 SERIES
CAUTION: FOR ANY WORK ON PUMP OR SWITCH, ALWAYS UNPLUG POWER CORD. DO NOT JUST TURN OFF CIRCUIT BREAKER OR UNSCREW FUSE.
TO REPLACE AUTOMATIC FLOAT
- Unplug the pump power cord from the back of the piggyback float plug.
- Unplug the piggy-back float plug from the power receptacle.
- Remove the pump from the sump if access to the tether point is inaccessible.
- Disconnect the switch from its tether point and remove from the discharge piping.
- Re-tether the new cord to the pump or discharge piping.
- Cable tie or tape the power and switch cords to the discharge piping.
- Plug the switch into the power receptacle.
- Plug the power cord into the switch plug.
- Fill basin and test switch operation.
ALL PUMP REPAIRS SHOULD BE DONE AT AN AUTHORIZED MYERS SERVICE CENTER.
TO REPLACE THE AUTOMATIC VERTICAL FLOAT SWITCH
- Unplug the pump power cord from the back of the piggyback plug.
- Unplug the piggy-back plug from the power receptacle.
- Remove the two mounting screws in the switch bracket that attached the switch assembly to the pump and remove from the discharge piping.
- Mount new switch assembly to pump. Be sure to install plastic tie provided and re-tether to mounting screw.
- Cable tie or tape the power and switch cords to the discharge piping.
- Plug the piggy-back switch in the power receptacle.
- Plug power cord into the piggy-back switch plug.
- ill basin and test switch operation.
TO REPLACE THE AUTOMATIC VERTICAL AND DIAPHRAGM FLOAT SWITCH
- Remove the oil fill plug located on the top of the motor housing and drain the oil in the housing. Properly dispose of the used oil. Do not reuse old oil since it may contain water from seal failure.
- Lay the pump on its side. Remove the six screws holding the suction bottom onto the volute case. Remove the suction bottom.
- Insert a slotted screwdriver through the center of the impeller hub into the slot in the shaft. With a rubber mallet, carefully tap the impeller in a counter rotating direction while holding the shaft with the screwdriver.
- Remove the rotating portion (ceramic) of the seal with fingers. Pry on the stationary portion (carbon) with a pair of slotted screwdrivers to remove from volute casing. Discard the old seal assembly parts. NEVER USE OLD SEAL PARTS, REBUILD PUMP WITH ONLY NEW SEAL ASSEMBLY.
- Thoroughly clean the shaft and volute casing with a clean cloth. If the drained oil showed signs of water, then the motor should be air dried for several days to remove any remaining moisture. refully
- Carefully remove the new seal assembly from the package. Add a film of new oil to the rubber O.D. on the stationary portion (carbon), and insert into the seal cavity on the volute casing. Using a pushing tool (a piece of PVC pipe works well), push on the rubber portion of the stationary seal until it is evenly seated into the seal cavity. With a clean cloth, carefully wipe the seal face.
- Remove the rotating portion (ceramic) from the package and carefully wipe with a clean cloth. Add a film of new oil onto the motor shaft. Slide the rotating portion over the shaft with the rubber surface of the seal facing away from the stationary seal face. Center the seal on the shaft.
- Place the impeller onto the shaft. Screw the impeller clockwise onto the shaft using a screwdriver to hold the shaft from turning and tighten impeller. Check to see that the impeller spins freely after tightening.
- Replace the suction bottom onto the volute casing and retain with the six screws. Evenly tighten screws.
- Replace oil in the motor housing using only Myers submersible transformer oil. The level should be 3/4” below the top of the motor housing. Check with dip stick to assure that the pump is properly filled.
- Plug pump into grounded receptacle to test operation. Pump must run quiet and free of vibration.
SRM4 SHAFT SEAL REPLACEMENT
- Remove the oil fill plug located on the top of the motor housing and drain the oil in the housing. Properly dispose of the used oil. Do not reuse old oil since it may contain water from seal failure.
- Remove the three cap screws holding the volute case onto the seal plate. Lift the motor assembly up and out of the volute case.
- Lay the motor assembly on its side. Insert a slotted screwdriver into the slot in the center of the shaft. With\ a rubber mallet, carefully tap the impeller in a counter rotating direction while holding the shaft with the screwdriver.
- Remove the rotating portion (ceramic) of the seal with fingers. Pry on the stationary portion (carbon) with a pair of slotted screwdrivers to remove from volute casing. Discard the old seal assembly parts. NEVER USE OLD SEAL PARTS. REBUILD PUMP WITH ONLY NEW SEAL ASSEMBLY.
- Thoroughly clean the shaft and volute casing with a clean cloth. If the drained oil showed signs of water, then the motor should be air dried for several days to remove any remaining moisture.
- Carefully remove the new seal assembly from the package. Add a film of new oil to the rubber O.D. on the stationary portion (carbon), and insert into the seal cavity on the volute casing. Using a pushing tool (a piece of PVC pipe works well), push on the rubber portion of the stationary seal until it is evenly seated into the seal cavity. With a clean cloth, carefully wipe the seal face.
- Remove the rotating portion (ceramic) from the package and carefully wipe with a clean cloth. Add a film of new oil into the motor shaft. Slide the rotating portion over the shaft with the rubber surface of the seal facing away from the stationary seal face. Center the seal on the shaft.
- Place the impeller onto the shaft. Screw the impeller clockwise onto the shaft using a screwdriver to hold the shaft from turning and tighten impeller. Check to see that the impeller spins freely after tightening
- Place the pump motor assembly upright and set it into the volute case. Replace the four cap screws and tighten.
- Replace oil in the motor housing using only Myers submersible transformer oil. The level should be 3/4” below the top of the motor housing. Check with dip stick to assure that the pump is properly filled.
- Plug pump into grounded receptacle to test operation
POWER CORD REPLACEMENT
- Loosen the plastic compression nut that retains the power cord. Slide nut out of the motor housing.
- Pull the power cord from the motor housing by hand.The cord may need to be wiggled back and forth several times to loosen from the housing. Pull the power cord out until the connecting wires are fully exposed. Disconnect the motor power and ground leads with a pair of pliers.
- Reconnect the motor power leads and ground to the new power cord. The ground terminal on the power cordhas a male connector, and the power terminals on the new power cord are female.
- Carefully push the connected wires into the motor housing until the molded body of the power cord seats. Make sure that the wires stay away from the rotor and shaft. Slide the nut into place and hand tighten. Tighten the nut with 13/16” wrench until snug, but do not over tighten.
- Plug pump into grounded receptacle to test operation. Pump must run quiet, free of vibration, without tripping out breaker.
MOTOR REPLACEMENT
- Disconnect the power cord and drain the oil as noted in the previous sections. If the oil shows signs of water or other contamination, it may be necessary to replace the seal assembly as noted in a previous section.
- Loosen and remove the three cap screws retaining the motor housing. Lift the motor housing off of the pump assembly.
- Remove the O-ring from the remaining pump assembly. Clean surface area and place new o-ring into position. Be careful not to cut o-ring when installing.
- Position new motor housing (with new stator), onto the pump assembly. Align the screw bosses, and insert the three cap screws. Evenly tighten the cap screws.
- Reinstall the power cord as noted in the previous section.
- Replace oil in the motor housing using only Myers submersible transformer oil. The level should be 3/4” below the top of the motor housing. Check with dip stick to assure that the pump is properly filled.
- Plug pump into grounded receptacle to test operation. Pump must run quiet, free of vibration, without tripping out breaker.
PERFORMANCE CURVES
Limited Warranty
Myers® warrants to the original consumer purchaser (“Purchaser” or “You”) of the products listed below, that they will be free from defects in material and workmanship for the Warranty Period shown below.
Product | Warranty Period |
---|---|
Jet pumps, small centrifugal pumps, submersible pumps and related accessories |
whichever occurs first: 12 months from date of original installation, or 18
months from date of manufacture
Fibrewound Tanks| 5 years from date of original installation
Fibrewound Tanks| 5 years from date of original installation
Sump/Sewage/Effluent Products| 12 months from date of original installation,
or 36 months from date of manufacture
Wastewater Solids Handling Pumps| 12 months from date of shipment from factory
or 18 months from date of manufacture
Our warranty applies only where such products are used in compliance with the requirements of the applicable product catalog and/or manuals. For additional information, please refer to the applicable standard limited warranty featured in the product manual.
Our warranty will not apply to any product that, in our sole judgement, has been subject to negligence, misapplication, improper installation, or improper maintenance. Without limiting the foregoing, operating a three phase motor with single phase power through a phase converter will void the warranty. Note also that three phase motors must be protected by three- leg, ambient compensated, extra-quick trip overload relays of the recommended size or the warranty is void.
Your only remedy, and MYERS’s only duty, is that MYERS repair or replace defective products (at MYERS’s choice). You must pay all labor and shipping charges associated with this warranty and must request warranty service through the installing dealer as soon as a problem is discovered. No request for service will be accepted if received after the Warranty Period has expired. This warranty is not transferable.
MYERS SHALL NOT BE LIABLE FOR ANY CONSEQUENTIAL, INCIDENTAL, OR CONTINGENT DAMAGES WHATSOEVER.
THE FOREGOING LIMITED WARRANTIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER EXPRESS AND IMPLIED WARRANTIES, INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. THE FOREGOING LIMITED WARRANTIES SHALL NOT EXTEND BEYOND THE DURATION PROVIDED HEREIN.
Some states do not allow the exclusion or limitation of incidental or consequential damages or limitations on the duration of an implied warranty, so the above limitations or exclusions may not apply to You. This warranty gives You specific legal rights and You may also have other rights which vary from state to state.
This Limited Warranty is effective February 7, 2014 and replaces all undated warranties and warranties dated after February 7, 2014.
CUSTOMER SUPPORT
F.E. MYERS
293 Wright Street, Delavan, WI 53115
Phone:888-987-8677 • Fax: 800-426-9446 • www.femyers.com
In Canada: 490 Pinebush Road, Unit 4, Cambridge, Ontario N1T 0A5 Phone:800-363-7867 • Fax: 888-606-5484
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>