GAGGENAU AR403122 Remote Fan Motor Instruction Manual

June 9, 2024
Gaggenau

GAGGENAU - logo AR403122 Remote Fan Motor
Instruction ManualGAGGENAU AR403122 Remote Fan
Motor

Installation instructions

AR403122 Remote Fan Motor

GAGGENAU AR403122 Remote Fan Motor - figGAGGENAU
AR403122 Remote Fan Motor - fig1GAGGENAU
AR403122 Remote Fan Motor - fig2GAGGENAU
AR403122 Remote Fan Motor - fig3

General information

  • Keep the instruction manual and the product information safe for future reference or for the next owner.
  • The appliance can only be used safely if it is correctly installed according to the safety instructions. The installer is responsible for ensuring that the appliance works  perfectly at its installation location.
  •  This instruction manual is intended for the installer of the optional accessory.
  • Only a licensed expert may connect the appliance.
  • Switch off the power supply before carrying out any work.

Safe installation
Follow these safety instructions when installing the appliance.

WARNING ‒ Risk of poisoning!
Risk of poisoning from flue gases being drawn back in. Room-air-dependent heat-producing appliances (e.g. gas, oil, wood or coal-operated heaters, continuous flow heaters  or water heaters) obtain combustion air from the room in which they are installed and discharge the exhaust gases into the open through an exhaust gas system (e.g. a chimney).
With the extractor hood switched on, air is extracted from the kitchen and the adjacent rooms. Without an adequate supply of air, the air pressure falls below atmospheric  pressure. Toxic gases from the flue or the extraction shaft are sucked back into the living space.

▶ Always ensure adequate fresh air in the room if the appliance is being operated in exhaust air mode at the same time as a room-air-dependent heat- producing appliance is being operated.
▶ It is only possible to safely operate the appliance if the pressure in the room in which the heating appliance is installed does not drop more than 4 Pa (0.04 mbar) below  atmospheric pressure. This can be achieved whenever the air needed for combustion is able to enter through openings that cannot be sealed, for example in doors, windows, incoming/exhaust air wall boxes or by other technical means. An incoming/exhaust air wall box alone does not ensure compliance with the limit.
▶ In any case, consult your responsible chimney sweep. They are able to assess the house’s entire ventilation setup and will suggest the suitable ventilation measures to you.
Risk of poisoning from flue gases being drawn back in.
▶ Do not emit the exhaust air into a smoke or exhaust gas flue that is in operation.
▶ Do not emit the exhaust air into a shaft that is used to ventilate installation rooms for heat-producing appliances.
▶ If the exhaust air is to be conveyed into a smoke or exhaust gas flue, you must obtain the consent of the heating engineer responsible. Risk of poisoning from flue gases being drawn back in.
▶ If an extractor hood with an open-flued heat production source is installed, the power supply for the extractor hood must be provided with a suitable safety switch.

WARNING ‒ Risk of suffocation!
Children may put packaging material over their heads or wrap themselves up in it and suffocate.
▶ Keep packaging material away from children.
▶ Do not let children play with packaging material.

WARNING ‒ Risk of electric shock!
It must always be possible to disconnect the appliance from the electricity supply. The appliance must only be connected to a protective contact socket that has been correctly installed.
▶ The mains plug for the mains power cable must be easily accessible after the appliance is installed.
▶ If this is not possible, an all-pole isolating switch must be integrated into the permanent electrical installation according to the conditions of overvoltage category III and  according to the installation regulations.
▶ The permanent electrical installation must only be wired by a professional electrician. We recommend installing a residual-current circuit breaker (RCCB) in the appliance’s  power supply circuit.

WARNING ‒ Risk of injury!
Changes to the electrical or mechanical assembly are dangerous and may lead to malfunctions.
▶ Do not make any changes to the electrical or mechanical assembly. Components inside the appliance may have sharp edges.
▶ Wear protective gloves.

Scope of delivery
After unpacking all parts, check for any damage in transit and completeness of the delivery.
→ Fig. 1
A connecting piece with a diameter of 150 mm is supplied with the appliance.

Appliance dimensions
You will find the dimensions of the appliance here
→ Fig. 2
Optional accessories
This is where you can find an overview of the optional accessories for different installation variants.
Air collector box for flat ducts
Order number

  • AD854048
    → Fig. 3

Air collector box for flat ducts
Order number

  • AD704050
    → Fig. 4

Air collector box for round ducts
Order number

  • AD754048
    → Fig. 5

Information about the electrical connection
In order to safely connect the appliance to the electrical system, follow these instructions.

WARNING ‒ Risk of electric shock!
Sharp-edged components inside the appliance may damage the connecting cable.
▶ Do not kink or trap the connecting cable.

  • The connection data can be found on the rating plate.

  •  This appliance complies with the EC interference suppression regulations.

  • The appliance corresponds to protection class 1.
    You should therefore only use the appliance with a protective earth connection.

  • Do not connect the appliance to the power supply during installation.

Information about air extraction mode
If the exhaust air is conveyed through the external wall, a telescopic duct should be used.
Instructions for the exhaust air pipe
The appliance manufacturer does not provide any warranty for faults attributable to the pipeline.

  • Use a short, straight exhaust air pipe with as large a pipe diameter as possible.
  • Long, rough exhaust air pipes, many pipe bends or small pipe diameters reduce the suction power and increase the fan noise.
  • Use an exhaust pipe that is made of non-combustible material.

Flat ducts
Use flat ducts with an inner cross-section that corresponds to the diameter of the round pipes:

  • Diameter of 150 mm corresponds to approx. 177 cm².
  • Use sealing strips for different pipe diameters.
  • Do not use any flat ducts with sharp bends.

Round pipes
Round pipes with an inner diameter of 150 mm.
General information
Follow these general instructions during the installation.

  • For the installation, observe the currently valid building regulations and the regulations of the local electricity and gas suppliers.
  • When discharging the exhaust air, the official and legal regulations, such as the regional building code., must be observed.

Installation

Checking the wall

  1. Check whether the wall is vertical and has sufficient load-bearing capacity.
    The weight of the appliance is approx. 10 kg.

  2. Ensure that there are no electrical wires, gas pipes or water pipes in the area where holes are to be drilled.

  3. Drill the hole depth in accordance with the length of the screws.

  4. Ensure that the wall plugs are firmly in place.

  5. Use suitable fixing material depending on the construction type, e.g. solid brickwork, plasterboard, porous concrete, Poroton brick.

Checking the units

  1. Check whether the fitted unit is level and has sufficient load-bearing capacity.
  2. Ensure that the clearance between the unit feet is at least 500 mm.

Preparing the units

  1. Position the unit cut-out depending on the local conditions.

  2. For a base height lower than 130 mm, provide an opening towards the front.
    ‒ If required, reinsert the section of the bottom plate following installation.
    → Fig. 6

  3. Mark the unit cut-out in accordance with the installation diagram and depending on the installation position.
    → Fig.7

  4. Establish a cut-out in the bottom plate.

  5. Ensure that the fitted unit is still stable after the cut-outs have been made.

  6. Seal the cut surfaces so that they are heat-resistant and waterproof.
    → Fig. 8

  7. Remove any shavings.

Preparing the appliance
▶ When installing on the back panel of the unit, install the enclosed bracket on the side of the appliance.
→ Fig. 9

Sliding the appliance under the unit
WARNING ‒ Risk of electric shock!
Sharp-edged components inside the appliance may damage the connecting cable.
▶ Do not kink or trap the connecting cable.
▶ Slide the appliance under the unit.
→ Fig. 10 , → Fig. 11
The appliance has rubber feet. It is not necessary to secure it to the ground.
Fasten the appliance to the back panel of the unit
WARNING ‒ Risk of electric shock!
Sharp-edged components inside the appliance may damage the connecting cable.
▶ Do not kink or trap the connecting cable.
▶ When installing on the back panel of the unit, secure the appliance using 4 screws.
‒ Align the appliance horizontally.
→ Fig. 12

Establishing the piping

  1. Use the connecting piece or screw an air collector box onto the appliance. → “Screwing in accessories”, Page 9
    The air collector boxes are available as optional accessories
    → Page 8.

  2. Secure the exhaust air pipe to the connecting piece and seal it appropriately.

Screwing in accessories

  1. Screw in one air collector box for two flat ducts.
    → Fig. 13 , → Fig. 14

  2. Screw in one air collector box for two round ducts.
    → Fig. 15

Connecting the appliance

  1. Use the control cable to connect the remote fan unit and the fan.
    → Fig. 16

  2. Ensure that the plug connections between the remote fan unit and the fan click into place.

  3. Insert the mains plug of the remote fan module into the mains socket.
    → Fig. 17

Checking the functionality

  1. Check the functionality of the appliance.
  2. If the appliance does not work, check the control cable’s plug connections.
    The connection sockets X1 and X2 are identical.

Removing the appliance
WARNING ‒ Risk of injury!
Components inside the appliance may have sharp edges.
▶ Wear protective gloves.

  1. Disconnect the appliance from the power supply.
  2. Loosen the control cable.
  3. Loosen the exhaust connections.
  4. Pull out the appliance.

Additional switching output
The appliance has an additional switching output X16 (potential-free contact) that can be used to connect other appliances, such as a ventilation system that is available at the  installation site. The contact is closed when the fan is switched on, and is opened when the fan is switched off.
Work must only be carried out on the additional switching output by a qualified electrician in accordance with the country-specific requirements and standards.
The switching output is located under a cover.
Maximum switching power 30 V/1 A (AC/DC). The signal that is connected to the contact must correspond to protection class 3.

Window contact switch
The appliance has an X17 connection for a window contact switch. If a window contact switch is connected, the extractor hood’s ventilation system only works with the  window open. The lighting works even if the window is closed. If you switch on the ventilation system with the window closed, the button for the fan setting you have selected flashes and the ventilation system does not switch on. If you close the window while the ventilation system is on, the appliance switches the ventilation system off within 5 seconds. The button for the selected fan setting flashes.
The entire ventilation system and window contact switch must be assessed by a master chimney sweep. Only a qualified electrician may work on the connection for the  window contact switch, in accordance with the country-specific requirements and standards. Observe the installation instructions provided with the window contact switch.
The window contact switch can be flush-mounted or surface-mounted. The window contact switch AA400510 is available as an accessory.

Networked operation
Multiple appliances can be networked together. The lighting and the fan of up to 20 appliances are operated synchronously. A qualified electrician must check that the appliance is working correctly during the initial installation.
The total length of all of the network cables must not exceed 40 m.
The failure of an appliance due to a voltage interruption or a network cable being disconnected blocks the fan function for the entire system, and all of the buttons on the  appliance flash.
When changing the configuration, an electrician must re-initialise the system.

Networking appliances
Requirement: A qualified electrician networks the appliances.

  1. Connect the appliances in series via the connector sockets X1 and X2.
    X1 and X2 are equivalent.
    The sequence of the networking does not have any effect.

  2. If the enclosed network cables are too short, use a commercially available network cable (shielded, min. CAT 5).

Re-initialising the system
Requirement: A qualified electrician carries out the initialisation and the test.

  1. Unscrew the cover plate.
    → Fig. 18

  2. Press and hold the reset button until both LEDs light up continuously.
    ‒ Press and hold the reset button for approx. 5 seconds.
    ‒ Release the reset button within 5 seconds.
    → Fig. 19

  3. Screw on the cover plate.

  4. Check that the system is working correctly.

GAGGENAU - logo

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals