Lumination Allusion Series Linear Suspended Slot Instruction Manual

June 9, 2024
Lumination

Lumination Allusion Series Linear Suspended Slot Instruction Manual
Lumination Allusion Series Linear Suspended Slot

CONSTRUCTION

Housing: Aluminum extruded housing. Diecast endcaps

Lens: Impact resistent Medium Flush, Glow, and Wall Wash lenses. Powdercoated metal Louvers
Paint: Powder painted, standard Black/White/Silver.
Custom colors available
Weight: 8-22 Lbs
Optical Precision formed high efficiency reflector and
Assembly: optical diffuser

OPTICAL SYSTEM

Delivered Down Lumens: 400-1100 lm/LFT
100 lumen Increments per linear foot (LFT)

Down Distribution **** Medium Flush, Louver (no lens),

Pattern: Glow, Wall Wash

Delivered Up Lumens: 400-1100 lm/LFT

100 lumen Increments per linear foot (LFT)

Up Distribution Pattern: Batwing
System Efficacy (LPW): ** >90 LPW
CCT: 3000K, 3500K, 4000K, 5000K
CRI (Min): TriGain® 90, 90
Color Consistency: ** 4 Step MacAdam Ellipse

LUMEN AMBIENT TEMPERATURE

Product ID Operating Temperature
LALS -10° TO 30° C

ELECTRICAL

Input Voltage: 120-277V, 347V
Input Frequency: 50/60Hz
Standard Dimming Control: 0-10V 1%, Daintree Wireless Controls,

Lutron Eco System
Power Factor (PF):| > 90%
Total Harmonic Distortion (THD)
:
| < 20%
EMBB:| Integral Emergency Battery (optional)
Maximum Run Length:| 100 ft per 1 powerdrop

CONTROLS

Dimming: Standard 0-10V, 1%
Daintree® Wireless
Lutron EcoSystem, Hi-lume 1% with Soft-on,
Fade-to-Black

MOUNTING
  • Non-powered Cable Suspension (10ft length)
  • Color-matched canopy, power and dimming cord (10ft length)
ADDITIONAL NOTES
  • No visible LEDs for for MM, GL, and WW down light lens options
  • Independent (IN), single-fixture option is available and comes with factory-installed endcaps and knockout plates. All hardware is included within fixture box
  • Suitable for dry and damp locations
  • Starter kits must be ordered separately and must match fixture voltage and down distribution

Catalog Logic

FAMILY| FIXTURE WIDTH| FIXTURE LENGTH| GEN| VOLTAGE| UP LIGHT DISTRIBUTION| DOWN LIGHT DISTRIBUTION| DOWN LIGHT LUMENS/FOOT| T CRI/CC| CONTROLS| MOUNTING| FINISH| OPTIONS
---|---|---|---|---|---|---|---|---|---|---|---|---
2 = 2 inch 4 = 4 inch| 21,8,11 = 2’ Length 4 = 4’ Length 5 = 5’ Length 6 = 6’ Length 8 = 8’ Length| A| 02,5 = 120-277V D2,11 = 347V| BW3 = Batwing NA = No Uplight| 0 = 1,000 LM/FT 09 = 900 LM/FT 08 = 800 LM/FT 07 = 700 LM/FT 06 = 600 LM/FT 05 = 500 LM/FT 04 = 400 LM/FT 00 = No Uplight| MM = Medium Flush Lens LW4,10 = Louver, Matte White GL= Glow Lens (1/2 inch) WW10 = Wall Wash| 10 = 1,000 LM/FT 09 = 900 LM/FT 08 = 800 LM/FT 07 = 700 LM/FT 06 = 600 LM/FT 05 = 500 LM/FT 04 = 400 LM/FT| 830 = 83 CRI 3000K T35 = TriGain® 3500K T40 = TriGain® 4000K| VQ8 = 0-10V no controls TQ5 = Wireless Enabled, Daintree Compatible TS5 = Wireless Enabled, W/Daintree WFA100| CM = Cable Mount, 10ft length Patterns: L94,6,8,10= 90o L| WHTE = White BLCK = Black SLVR = Silver| BLANK = No Options EL8 = Emergency Light IN9 = Independen

Ordering Notes:

  1. 2ft length must have a minimum 800lm/ft for up light and down light.

  2. Starter Kit must match fixture voltage, ordered separately. Refer to Kits Section.

  3. Batwing (BW option) is not available without lumen output (00 LM/FT option).

  4. Louvers (LW option) are field installed and have no lens.

  5. Daintree controls (TQ or TS option) are only available with 120-277V (0 voltage option).

  6. Corner fixture (L9 option) is only available in 4ft length (length option 4). Refer to Dimensional information.
    Verify T-Grid dimensional information for proper layout.

  7. Contact manufacturer for quote on custom colors. Additional lead times and minimum order quantities are applicable.

  8. Integral Emergency Battery (EL option) only available with 120-277V (0 voltage option) and 0-10V controls (VQ option).
    EL is not available for 2ft lengths or Corner fixtures (L9 option).

  9. Independent fixture (IN option) has factory installed endcaps and KO plates.
    Power cord and suspension cables are provided and must be field installed.

  10. Corner fixture (L9 option) with Wall Wash (WW) or Louver (LW) not available.

  11. 2 ft length not available with 347V option (D).

Product Dimensions

Linear LALS
Product Dimensions

  • Fixture is provided with non powered suspension kit.
  • Starter kit which includes power connection, pair of end caps and additional suspension kit is required.
  • If Independent (IN) option is ordered all hardware included along with factory installed endcaps.

See “Flexibility in Design” for additional information.

Corner Intersection Pattern (L9 option)
  • Fixture is provided with the L9 corner specific suspension kit, linear non-power suspension kit,(2) Knockout plates, (1) male/male and (1) female/female leader cables.

LALS Corner fixtures are continuous and intended to be installed with additional linear luminaries. A linear fixture is recommended to provide end caps and power connections.

Note: If no linear fixtures are needed, as shown below, need to separately order the Power feed/Canopy Kit for Independent up light control (see Kits Section in LAL Replacement Guide for additional information).

Louvers (LW option)
Louvers
Louver Length = 12 inches
One used per every foot in LALS fixtures

  • Provided in separate packs with fixtures, to be installed on site (see Install Guide for proper orientation).
  • Louvers are matte white painted finish.
  • Louvered fixtures do not have a lens.

Glow Lens (GL option)
Glow Lens

Length of Glow Lens is equal to fixture lengths available
Note: All Glow Lens Starter Kits are provided with Glow Lens end caps. Glow Lens end caps are 1/2” larger than flush lens end caps. Refer to p. 5.\
Standard endcaps

Glow endcaps are larger than standard endcaps

Wall Wash (WW option)
Wall Wash
Length of Wall Wash Lens is equal to fixture lengths available
Note: All Wall Wash Lens Starter Kits are provided with flush lens end caps. Refer to p. 5
Wall Wash Lens

Kits and Accessories

STARTER KIT
Starter Kit

Fixture| Voltage           Description             Color Part Number
---|---

LALS2

|

120-277V

Voltage = 0

| MM = Medium

Flush Lens

WW = Wall Wash LW = Louver

| White| 93100034
Black| 93100035
Silver| 93100156
GL = Glow Lens (0.5”)| Black| 93129673
White| 93129674
Silver| 93129675

347V

Voltage = D

| MM = Medium Flush Lens

WW = Wall Wash LW = Louver

| Black| 93119005
White| 93119036
Silver| 93119037
GL = Glow Lens (0.5”)| Black| 93129686
White| 93129687
Silver| 93129688
Fixture| Voltage           Description             Color Part Number
---|---

LALS4

|

120-277V

Voltage = 0

| MM = Medium

Flush Lens

WW = Wall Wash LW = Louver

| White| 93100157
Black| 93100158
Silver| 93100159
GL = Glow Lens (0.5”)| Black| 93129689
White| 93129690
Silver| 93129691

347V

Voltage = D

| MM = Medium Flush Lens

WW = Wall Wash LW = Louver

| Black| 93119053
White| 93119054
Silver| 93119055
GL = Glow Lens (0.5”)| Black| 93129692
White| 93129693
Silver| 93129694

COLOR NOTES:
White= 120-277V (18GA) & 347 (14GA): White Endcaps / White Power Cords / White Canopy Covers
Black= 120-277V (18GA) & 347 (14GA): Black Endcaps / Black Power Cords / Black Canopy Covers
Silver= 120-277V (18GA): Silver Endcaps / Silver Power Cords / White Canopy Covers
347V (14GA): Silver Endcaps / White Power Cords / White Canopy Covers

NOTE: Refer to Install Instructions for visuals.

  • Voltage of Starter Kit must match Voltage of Fixture
  • Glow Lens starter kits contain larger end cap

REPLACEMENT PARTS:
Refer to our online replacement parts guide, found on the LAL product web page
Lumination LED Linear Architectual – LAL
Series – Replacement Guide | IND546

OPTIONAL POWERFEED/CANOPY KIT

NON-POWERED SUSPENSION CABLES – (1 EACH) INCLUDED WITH EACH FIXTURE
SUSPENSION CABLES

OPTIONAL POWERFEED/CANOPY KIT FOR INDEPENDENT UPLIGHT CONTROL
CANOPY KIT

Fixture               Voltage          Description             Color SAP Part Number

LALS2

| 120-277V

Voltage = 0

|

Universal

| White| 93076445
Black| 93076446
Silver| 93084573
347V

Voltage = D

| Universal| Black| 93101364
White| 93101363

COLOR NOTES

White= 120-277V (18GA) & 347 (14GA): White Endcaps / White Power Cords / White Canopy Covers
Black= 120-277V (18GA) & 347 (14GA): Black Endcaps / Black Power Cords / Black Canopy Covers
Silver= 120-277V (18GA): Silver Endcaps / Silver Power Cords / White Canopy Covers
347V (14GA): Silver Endcaps / White Power Cords / White Canopy Covers
NON-POWERED SUSPENSION CABLES – (1 EACH) INCLUDED WITH EACH FIXTURE
OPTIONAL POWERFEED/CANOPY KIT FOR INDEPENDENT UPLIGHT CONTROL

NOTE: Refer to Install Instructions for visuals.

  • Voltage of Starter Kit must match Voltage of Fixture
  • Glow Lens starter kits contain larger end caps.

Performance

**LALS2 Up Light***

Product

Width & Length

|

CAT

Logic

|

Lm/ft

| Nominal Lumen| 4000K

TriGain®

Wattage

| 3500K

TriGain®

Wattage

| 3000K

Standard Wattage

---|---|---|---|---|---|---
22| 08| 800| 1600| 13.9| 14.3| 15.0
22| 09| 900| 1800| 15.8| 16.2| 17.0
22| 10| 1000| 2000| 17 .6| 18.2| 19.0
24| 04| 400| 1600| 13.4| 13.8| 14.5
24| 05| 500| 2000| 14.8| 15.3| 16.1
24| 06| 600| 2400| 18.3| 18.8| 19.8
24| 07| 700| 2800| 21.6| 22.4| 23.4
24| 08| 800| 3200| 25.1| 25.9| 27.1
24| 09| 900| 3600| 28.4| 29.4| 30.9
24| 10| 1000| 4000| 31.9| 32.9| 34.4
25| 04| 400| 2000| 14.8| 15.3| 16.1
25| 05| 500| 2500| 19.1| 19.6| 20.6
25| 06| 600| 3000| 23.4| 24.1| 25.4
25| 07| 700| 3500| 27.6| 28.4| 29.9
25| 08| 800| 4000| 31.9| 32.9| 34.4
25| 09| 900| 4500| 36.2| 37.2| 39.2
25| 10| 1000| 5000| 40.5| 41.7| 43.7
26| 04| 400| 2400| 17 .2| 17 .7| 18.7
26| 05| 500| 3000| 22.4| 22.9| 24.1
26| 06| 600| 3600| 27.4| 28.4| 29.6
26| 07| 700| 4200| 32.6| 33.6| 35.3
26| 08| 800| 4800| 37.7| 39.0| 40.8
26| 09| 900| 5400| 43.1| 44.4| 46.8
26| 10| 1000| 6000| 48.3| 49.9| 50.4
28| 04| 400| 3200| 23.4| 24.1| 25.4
28| 05| 500| 4000| 29.9| 30.9| 32.3
28| 06| 600| 4800| 36.3| 37.6| 39.3
28| 07| 700| 5600| 42.8| 44.3| 46.3
28| 08| 800| 6400| 50.2| 51.7| 54.3
28| 09| 900| 7200| 57.7| 59.5| 62.4
28| 10| 1000| 8000| 65.2| 67.0| 70.7

**LALS4 Up Light***

Product Width & Length| CAT

Logic

| Lm/ft| Nominal Lumen| 4000K TriGain® Wattage| 3500K TriGain® Wattage| S3000K tandard Wattage
---|---|---|---|---|---|---
42| 08| 800| 1600| 13.9| 14.3| 15.0
42| 09| 900| 1800| 15.8| 16.2| 17.0
42| 10| 1000| 2000| 17 .6| 18.2| 19.0
44| 04| 400| 1600| 13.4| 13.8| 14.5
44| 05| 500| 2000| 14.8| 15.3| 16.1
44| 06| 600| 2400| 18.3| 18.8| 19.8
44| 07| 700| 2800| 21.6| 22.4| 23.4
44| 08| 800| 3200| 25.1| 25.9| 27.1
44| 09| 900| 3600| 28.4| 29.4| 30.9
44| 10| 1000| 4000| 31.9| 32.9| 34.4
45| 04| 400| 2000| 14.8| 15.3| 16.1
45| 05| 500| 2500| 19.1| 19.6| 20.6
45| 06| 600| 3000| 23.4| 24.1| 25.4
45| 07| 700| 3500| 27.6| 28.4| 29.9
45| 08| 800| 4000| 31.9| 32.9| 34.4
45| 09| 900| 4500| 36.2| 37.2| 39.2
45| 10| 1000| 5000| 40.5| 41.7| 43.7
46| 04| 400| 2400| 17 .2| 17 .7| 18.7
46| 05| 500| 3000| 22.4| 22.9| 24.1
46| 06| 600| 3600| 27.4| 28.4| 29.6
46| 07| 700| 4200| 32.6| 33.6| 35.3
46| 08| 800| 4800| 37.7| 39.0| 40.8
46| 09| 900| 5400| 43.1| 44.4| 46.8
46| 10| 1000| 6000| 48.3| 49.9| 50.4
48| 04| 400| 3200| 23.4| 24.1| 25.4
48| 05| 500| 4000| 29.9| 30.9| 32.3
48| 06| 600| 4800| 36.3| 37.6| 39.3
48| 07| 700| 5600| 42.8| 44.3| 46.3
48| 08| 800| 6400| 50.2| 51.7| 54.3
48| 09| 900| 7200| 57.7| 59.5| 62.4
48| 10| 1000| 8000| 65.2| 67.0| 70.7

NOTE:

  • Total fixture performance is the summation of both the Down and Up wattages and nominal lumens.
  • Corner (L9) option, use LALS24 (24) or LALS44 (44) only from the Product Column in table above.

UP ONLY – BATWING
LALS-4-4-A-0-BW-07-XX-XX-XXX-XX-XX-WHTE-XX

ZONAL LUMEN SUMMARY ZONA L LUMEN SUMMARY
Zone Lumens Zone
0-10° 0 0-30°
10-20° 0 0-60°
20-30° 0 0-90°
30-40° 0 90-120°
40-50° 0 90-150°
50-60° 0 90-180°
60-70° 0 0-180°
70-80° 0
80-90° 0
90-100° 57
100-110° 255
110-120° 414
120-130° 493
130-140° 506
140-150° 451
150-160° 345
160-170° 207
170-180° 66

POLAR GRAPH
POLAR GRAPH

For more information please see IES files at
www.LED.com

**LALS2 Down Light***

Product Width & Length| CAT Logic| Lm/ft| Nominal Lumen| 4000K TriGain® Wattage| 3500K TriGain® Wattage| S3000K tandard Wattage
---|---|---|---|---|---|---
22| 08| 800| 1600| 16.7| 17.2| 18.2
22| 09| 900| 1800| 18.9| 19.7| 20.4
22| 10| 1000| 2000| 21.2| 22.0| 23.0
24| 04| 400| 1600| 15.1| 15.6| 16.4
24| 05| 500| 2000| 19.2| 19.7| 20.8
24| 06| 600| 2400| 23.1| 23.8| 25.1
24| 07| 700| 2800| 27.1| 27.9| 29.4
24| 08| 800| 3200| 31.2| 32.3| 33.8
24| 09| 900| 3600| 35.3| 36.6| 38.4
24| 10| 1000| 4000| 40.5| 41.8| 43.9
25| 04| 400| 2000| 18.8| 19.3| 20.2
25| 05| 500| 2500| 23.4| 24.2| 25.4
25| 06| 600| 3000| 28.3| 29.3| 30.8
25| 07| 700| 3500| 33.5| 34.5| 36.2
25| 08| 800| 4000| 38.7| 39.9| 41.8
25| 09| 900| 4500| 44.0| 45.3| 47.7
25| 10| 1000| 5000| 47.2| 48.7| 49.4
26| 04| 400| 2400| 22.7| 23.5| 24.7
26| 05| 500| 3000| 28.7| 29.8| 31.3
26| 06| 600| 3600| 35.0| 36.1| 37.8
26| 07| 700| 4200| 41 .4| 42.6| 44.6
26| 08| 800| 4800| 47.7| 49.2| 51.7
26| 09| 900| 5400| 54.5| 56.0| 58.8
26| 10| 1000| 6000| 61 .0| 63.0| 66.1
28| 04| 400| 3200| 29.3| 30.2| 31.6
28| 05| 500| 4000| 36.7| 37.7| 39.6
28| 06| 600| 4800| 44.4| 46.0| 48.3
28| 07| 700| 5600| 52.8| 54.7| 57.7
28| 08| 800| 6400| 60.9| 63.0| 66.4
28| 09| 900| 7200| 69.8| 72.1| 75.8
28| 10| 1000| 8000| 75.0| 77.6| 77.9

**LALS4 Down Light***

Product

Width & Length

|

CAT

Logic

|

Lm/ft

|

Nominal Lumen

| 4000K

TriGain® Wattage

| 3500K

TriGain® Wattage

| S3000K

tandard

Wattage

---|---|---|---|---|---|---
42| 08| 800| 1600| 15.2| 15.7| 16.4
42| 09| 900| 1800| 17.4| 17.9| 18.7
42| 10| 1000| 2000| 19.4| 19.9| 21.0
44| 04| 400| 1600| 14.9| 14.9| 14.9
44| 05| 500| 2000| 17.4| 17.9| 18.7
44| 06| 600| 2400| 21.0| 21.8| 22.8
44| 07| 700| 2800| 24.6| 25.4| 26.6
44| 08| 800| 3200| 28.4| 29.4| 30.7
44| 09| 900| 3600| 32.3| 33.3| 34.8
44| 10| 1000| 4000| 36.9| 37.9| 39.7
45| 04| 400| 2000| 17.1| 17.6| 18.5
45| 05| 500| 2500| 21.5| 22.0| 23.2
45| 06| 600| 3000| 25.9| 26.6| 28.1
45| 07| 700| 3500| 30.6| 31.5| 33.0
45| 08| 800| 4000| 35.2| 36.2| 38.2
45| 09| 900| 4500| 40.1| 41.3| 43.3
45| 10| 1000| 5000| 45.0| 46.5| 48.7
46| 04| 400| 2400| 20.7| 21.3| 22.4
46| 05| 500| 3000| 26.2| 27.0| 28.3
46| 06| 600| 3600| 31.8| 32.8| 34.4
46| 07| 700| 4200| 37.5| 38.7| 40.6
46| 08| 800| 4800| 43.4| 44.8| 47.0
46| 09| 900| 5400| 49.4| 51.0| 53.5
46| 10| 1000| 6000| 55.6| 57.3| 60.2
48| 04| 400| 3200| 26.7| 27.4| 28.8
48| 05| 500| 4000| 33.3| 34.3| 35.9
48| 06| 600| 4800| 40.4| 41.6| 43.7
48| 07| 700| 5600| 47.8| 49.4| 52.0
48| 08| 800| 6400| 55.3| 57.1| 60.2
48| 09| 900| 7200| 63.3| 65.1| 68.5
48| 10| 1000| 8000| 71.3| 73.7| 77.6

NOTE:

  • Total fixture performance is the summation of both the Down and Up wattages and nominal lumens.
  • Corner (L9) option, use LALS24 (24) or LALS44 (44) only from the Product Column in table above.
  • Glow (GL) Option is 5% less lumens than values shown above.
  • Wall Wash (WW) Option is 7% more lumens than values shown above.

DOWN ONLY – MEDIUM FLUSH LENS
LALS-4-4-A-0-NA-00-MM-07-XXX-XX-XX-WHTE-XX

Zone

0-10°

| Lumens

100

| Zone

0-30°

| Lumens

804

| % of Fixture

29

---|---|---|---|---
10-20°| 283| 0-60°| 2233| 80
20-30°| 420| 0-90°| 2800| 100
30-40°| 493| 90-120°| 0| 0
40-50°| 497| 90-130°| 0| 0
50-60°| 438| 90-150°| 0| 0
60-70°| 328| 90-180°| 0| 0
70-80°| 186| 0-180°| 2800| 100.0
80-90°| 49|
90-100°| 0|
100-110°| 0|
110-120°| 0|
120-130°| 0|
130-140°| 0|
140-150°| 0|
150-160°| 0|
160-170°| 0|
170-180°| 0|

**POLAR GRAPH

**

Photometrics

DOWN ONLY – GLOW LENS
LALX-4-4-A-0-NA-00-GL-07-XXX-XX-WHTE-XX

ZONAL LUMEN SUMMARY

Zone| Lumens
0-10°| 78
10-20°| 224
20-30°| 338
30-40°| 408
40-50°| 426
50-60°| 393
60-70°| 318
70-80°| 213
80-90°| 101
ZONAL LUMEN SUMMARY

Zone| Lumens| % of Fixture
0-30°| 640| 24
0-60°| 1867| 70
0-90°| 2499| 94
90-120°| 119| 5
90-130°| 140| 5
90-150°| 159| 6
90-180°| 161| 6
0-180°| 2660| 100

DOWN ONLY – WHITE LOUVERS (NO LENS )
LALS-4-4-A-0-NA-00-LW-07-XXX-XX-WHTE-XX

Zone

0-10°

| Lumens

130

---|---
10-20°| 369
20-30°| 546
30-40°| 562
40-50°| 507
50-60°| 345
60-70°| 206
70-80°| 108
80-90°| 27
90-100°| 0
ZONAL LUMEN SUMMARY

Zone| Lumens| % of Fixture
0-30°| 1045| 37
0-60°| 2459| 89
0-90°| 2800| 100
90-120°| 0| 0
90-1 30°| 0| 0
90-150°| 0| 0
90-1 80°| 0| 0
0-180°| 2800| 1 00

DOWN ONLY – WALL WASH
LALS-4-4-A-0-NA-00-WW-07-XXX-XX-WHTE-XX

ZONAL LUMEN SUMMARY

Zone| Lumens| % of Fixture
0-30°| 934| 31
0-60°| 2467| 82
0-90°| 2996| 100
90-120°| 0| 0
90-130°| 0| 0
90-150°| 0| 0
90-180°| 0| 0
0-180°| 2996| 100
ZONAL LUMEN SUMMARY

Zone| Lumens| % of Fixture
0-30°| 934| 31
0-60°| 2467| 82
0-90°| 2996| 100
90-120°| 0| 0
90-130°| 0| 0
90-150°| 0| 0
90-180°| 0| 0
0-180°| 2996| 100

For more information please see IES files at
www.LED.com

Controls & Sensors

DAINTREE CONTROLS

Daintree® Wireless Controls:
There is no one size fits all for wireless controls. Some networks want simple solutions that reduce energy consumption and meet code compliance while others are more ambitious, looking to capitalize on the LED and controls savings to fund a scalable, enterprise-grade, internet of things solution. The advantage of the Daintree Wireless platform is it’s ability to integrate into indoor, outdoor and high bay environments. The Daintree Wireless Controls provide the infrastructure to future proof your buildings, easily upgrade to Networked solutions and provide the ability to integrate into IoT solutions that are right for your business.

  • Daintree One: Standalone Wireless Controls
  • Daintree EZ Connect: Room-Based Wireless Lighting Controls
  • Daintree Networked: Networked Lighting Controls for Smart Building & IoT Enablement

Daintree Wireless Controls are already integrated in your favorite Current LED fixtures. Integrating the controls into the fixture cuts labor costs considerably since the sensors are already embedded in the lighting fixtures. There’s no need to get above the ceiling plenum and install additional devices. Visit our website https://products.gecurrent.com for a complete list of LED Fixtures that have Daintree integrated controls.

The LALS Series Architectural Luminaire will offer Daintree Networked integral controls (Controls option TQ). Integral sensors and IOT devices are not offered at this time.

LUTRON CONTROLS

Lutron Eco System: Eco System technology is a control method for LEDs that provides addressing of individual fixtures and status feedback from the LED drivers. This makes it easy to digitally assign occupancy sensors, daylight sensors, time clocks, manual controls and other controls to one or many fixtures without complicated wiring. This opens up an entire suite of energy-saving, system monitoring and system-control schemes where the design, setup and rezoning are all done within software, making the electrical and control design simple.

Support

gecurrent.com/lumination
© 2022 Current Lighting Solutions, LLC. All rights reserved. Information and specifications subject to change without notice. All values are design or typical values when measured under laboratory conditions.
Page 10 of 10
(Rev 08/25/22)
IND501

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals