LinkedGO Ultimate Thermostat ST1000EZ0 Manual

June 8, 2024
LinkedGO

LinkedGO

Ultimate Thermostat

SKU: ST1000EZ0

Quickstart

This is a
secure
HVAC-Thermostat
for
CEPT (Europe)
.

To run this device please connect it to your mains power supply.

To add this device to your network execute the following action:
Hold the “+” button 5 seconds, until the display show “Add”.

Please refer to the
Manufacturers Manual
for more information.

Important safety information

Please read this manual carefully. Failure to follow the recommendations in this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any loss or damage resulting from failure to comply with the instructions in this manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal instructions.

Do not dispose of electronic equipment or batteries in a fire or near open heat sources.

What is Z-Wave?

Z-Wave is the international wireless protocol for communication in the Smart Home. This
device is suited for use in the region mentioned in the Quickstart section.

Z-Wave ensures a reliable communication by reconfirming every message ( two- way
communication
) and every mains powered node can act as a repeater for other nodes
( meshed network ) in case the receiver is not in direct wireless range of the
transmitter.

This device and every other certified Z-Wave device can be used together with any other
certified Z-Wave device regardless of brand and origin
as long as both are suited for the
same frequency range.

If a device supports secure communication it will communicate with other devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to maintain
backward compatibility.

For more information about Z-Wave technology, devices, white papers etc. please refer
to www.z-wave.info.

Product Description

LinkedGo’s Ultimate Thermostat has built-in temperature and humidity sensor to control room environment more comfortable. And it has 3.5 inch TFT display, resolution is 320*480. User interface and human-computer interaction is very friendly. We also have fashionable appearance, the depth only 0.39 inch (10mm).

Prepare for Installation / Reset

Please read the user manual before installing the product.

In order to include (add) a Z-Wave device to a network it must be in factory default
state.
Please make sure to reset the device into factory default. You can do this by
performing an Exclusion operation as described below in the manual. Every Z-Wave
controller is able to perform this operation however it is recommended to use the primary
controller of the previous network to make sure the very device is excluded properly
from this network.

Reset to factory default

This device also allows to be reset without any involvement of a Z-Wave controller. This
procedure should only be used when the primary controller is inoperable.

Go to the third page, find “About”, select “Reset all settings”, and confirm.Please use this procedure only when the network primary controller is missing or otherwise inoperable.

Safety Warning for Mains Powered Devices

ATTENTION: only authorized technicians under consideration of the country- specific
installation guidelines/norms may do works with mains power. Prior to the assembly of
the product, the voltage network has to be switched off and ensured against re-switching.

Inclusion/Exclusion

On factory default the device does not belong to any Z-Wave network. The device needs
to be added to an existing wireless network to communicate with the devices of this network.
This process is called Inclusion.

Devices can also be removed from a network. This process is called Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network. This
controller is turned into exclusion respective inclusion mode. Inclusion and Exclusion is
then performed doing a special manual action right on the device.

Inclusion

Hold the “+” button 5 seconds, until the display show “Add”.

Exclusion

Hold the “-” button 5 seconds, until the display show “Remove”.

Quick trouble shooting

Here are a few hints for network installation if things dont work as expected.

  1. Make sure a device is in factory reset state before including. In doubt exclude before include.
  2. If inclusion still fails, check if both devices use the same frequency.
  3. Remove all dead devices from associations. Otherwise you will see severe delays.
  4. Never use sleeping battery devices without a central controller.
  5. Dont poll FLIRS devices.
  6. Make sure to have enough mains powered device to benefit from the meshing

Association – one device controls an other device

Z-Wave devices control other Z-Wave devices. The relationship between one device
controlling another device is called association. In order to control a different
device, the controlling device needs to maintain a list of devices that will receive
controlling commands. These lists are called association groups and they are always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’ Command.

Association Groups:

Group NumberMaximum NodesDescription

1| 5| Thermostat supports 1 association group (0x01), which can include five Node ID. A gateway is suggested to associatewith thisgroup. Then if any changes happen, such as: temperature, working mode, fan status etc., the thermostat will report to this associated device (gateway). All the reports sentvia Lifeline group.Commands sent via Lifeline:COMMAND_CLASS_THERMOSTAT_MODE, COMMAND_CLASS_THERMOSTAT_SETPOINT, COMMAND_CLASS_THERMOSTAT_FAN_MODE, COMMAND_CLASS_SENSOR_MULTILEVEL, COMMAND_CLASS_CONFIGURATION,COMMAND_CLASS_DEVICE_RESET_LOCALLY
---|---|---

Configuration Parameters

Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock further
enhanced features.

IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200 it may be needed to set a value of 200 minus 256 = minus 56.
In case of a two byte value the same logic applies: Values greater than 32768 may
needed to be given as negative values too.

Parameter 10: Algorithm enable

Disable
Size: 2 Byte, Default Value: 0

SettingDescription

0 – 1 Enable

Parameter 17: Theme style

0-classic
Size: 2 Byte, Default Value: 0

SettingDescription

0 – 1 weather
1 – 2 Digital clock
2 – 3 Rome clock
3 – 4 Cartoon clock

Parameter 20: Min. temperature limit

Value range:50~350(50 means for 5, 350 means 35)Precision:1
Size: 2 Byte, Default Value: 50

SettingDescription

50 – 160 The minimum setting temperature become 16 degree C

Parameter 21: Max. temperature limit

Value range:50~350(50 means for 5, 350 means 35)Precision:1
Size: 2 Byte, Default Value: 350

SettingDescription

350 – 280 The maximum setting temperature become 28 degree C

Parameter 25: Winter temperature difference calibration

Value range:-50~50(-50 means T=-50)Precision:1Calibration for the temp.sensor in winter
Size: 2 Byte, Default Value: 0

SettingDescription

0 – 10 The temperature probe should be calibrated +1 degree C.

Parameter 4: Custom mode

0-standard mode
Size: 2 Byte, Default Value: 0

SettingDescription

0 – 2 Sleeping night mode
2 – 3 Sleeping noon mode

Parameter 5: Heating method

0-Heating by fan coil only
Size: 2 Byte, Default Value: 0

SettingDescription

0 – 1 Floor heating only
1 – 2 Fan coil and floor heating both

Parameter 6: Master and slave setting

Slave-it can be switched on/off by Master unit.
Size: 2 Byte, Default Value: 0

SettingDescription

0 – 1 Master

Parameter 82: Outdoor temperature

Value range:-50 ~ 50Precision:1Display outdoor temperature on screen
Size: 2 Byte, Default Value: 0

SettingDescription

0 – 15 Outdoor temperature is 15 degree C

Parameter 84: Local weather

0-sunnyShow local weather on the display
Size: 2 Byte, Default Value: 0

SettingDescription

0 – 1 windy
1 – 2 snow
2 – 3 rain
3 – 4 cloudy
4 – 5 partly cloudy

Parameter 85: PM2.5 level

Excellent
Size: 2 Byte, Default Value: 0

SettingDescription

0 – 1 Good
1 – 2 Light pollution
2 – 3 Heavy pollution

Parameter 9: Summer temperature difference calibration

Value range:-50~50(-50 means T=-5)Precision:1Calibration for the temp.sensor in summer
Size: 2 Byte, Default Value: 0

SettingDescription

0 – -10 The temperature probe should be calibrated -1 degree C.

Technical Data

Hardware Platform ZM5101
Device Type Thermostat – HVAC
Network Operation Always On Slave
Firmware Version HW: 255 FW: 4.01:03.69
Z-Wave Version 6.81.02
Certification ID ZC10-19046458
Z-Wave Product Id 0x0391.0x0003.0x0024
Communications Protocol Manufacturer’s Open/Documented Protocol
Supported Notification Types ClockWeather Alarm
Sensors Air TemperatureDew PointHumidityTime
Thermostat Power Source Mains powered (120V/240V)
Neutral Wire Required ok
Color Polished Brass
Firmware Updatable Updatable by Professional/Technician
Thermostat HVAC Systems Supported Cool OnlyHeat OnlyHeat PumpHumidity

ControlMulti StageSimple RelaySingle StageVentilation Control
Communications Connections| Ethernet (Wireless/WiFi)RS-485 (Serial)
Thermostat Modes| AutoCoolDry AirEnergy Save CoolEnergy Save HeatFan OnlyHeatResume
Security V2| S2_UNAUTHENTICATED
Frequency| XXfrequency
Maximum transmission power| XXantenna

Supported Command Classes

  • Association Grp Info
  • Association V2
  • Basic V2
  • Configuration
  • Device Reset Locally
  • Firmware Update Md V4
  • Manufacturer Specific V2
  • Powerlevel
  • Security
  • Security 2
  • Sensor Multilevel V9
  • Supervision
  • Thermostat Fan Mode V4
  • Thermostat Mode V3
  • Thermostat Setpoint V2
  • Time Parameters
  • Transport Service V2
  • Version V3
  • Zwaveplus Info V2

Explanation of Z-Wave specific terms

  • Controller — is a Z-Wave device with capabilities to manage the network.
    Controllers are typically Gateways,Remote Controls or battery operated wall controllers.

  • Slave — is a Z-Wave device without capabilities to manage the network.
    Slaves can be sensors, actuators and even remote controls.

  • Primary Controller — is the central organizer of the network. It must be
    a controller. There can be only one primary controller in a Z-Wave network.

  • Inclusion — is the process of adding new Z-Wave devices into a network.

  • Exclusion — is the process of removing Z-Wave devices from the network.

  • Association — is a control relationship between a controlling device and
    a controlled device.

  • Wakeup Notification — is a special wireless message issued by a Z-Wave
    device to announces that is able to communicate.

  • Node Information Frame — is a special wireless message issued by a
    Z-Wave device to announce its capabilities and functions.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals