Climax Technology Acoustic Glass Break Detector ACGS-23ZW Manual Acoustic Glass Break Detector

October 28, 2023
Climax Technology

Climax Technology

Acoustic Glass Break Detector

SKU: ACGS-23ZW

Quickstart

This is a
secure
Alarm Sensor
for
CEPT (Europe)
.

Please make sure the internal battery is fully charged.

To add this device to your network execute the following action:
This product can be included and operated in any Z-Wave network with other Z-Wave certified devices from other manufactures and/or other applications. All non-battery operated nodes within the network will act as repeaters regardless of vendor to increase reliability of the network.1. Insert the 3V CR123A Lithium battery into the battery compartment connecting the correct polarity as shown on the battery compartment lid.2. Put the Z-Wave gateway or control panel into Inclusion or Learning mode (please refer to the Z-Wave gateway or control panel manual).3. Within 1 second, press the Function Button 3 times. 4. Refer to the operation manual of the Z-Wave gateway or control panel to complete the learn-in process.5.If the sensor has already been included (learnt) into another Z-Wave Gateway/Control Panel, or if the sensor is unable to be learnt into the current Z-Wave Gateway/Control Panel, please exclude it first (see Exclusion) before attempting to include it into the current Z-Wave Gateway/Control Panel.

Please refer to the
Manufacturers Manual
for more information.

Important safety information

Please read this manual carefully. Failure to follow the recommendations in this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any loss or damage resulting from failure to comply with the instructions in this manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal instructions.

Do not dispose of electronic equipment or batteries in a fire or near open heat sources.

What is Z-Wave?

Z-Wave is the international wireless protocol for communication in the Smart Home. This
device is suited for use in the region mentioned in the Quickstart section.

Z-Wave ensures a reliable communication by reconfirming every message ( two- way
communication
) and every mains powered node can act as a repeater for other nodes
( meshed network ) in case the receiver is not in direct wireless range of the
transmitter.

This device and every other certified Z-Wave device can be used together with any other
certified Z-Wave device regardless of brand and origin
as long as both are suited for the
same frequency range.

If a device supports secure communication it will communicate with other devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to maintain
backward compatibility.

For more information about Z-Wave technology, devices, white papers etc. please refer
to www.z-wave.info.

Product Description

ACGS-23ZW Acoustic Glassbreak Sensor is an excellent first line of defense for perimeter protection. This wireless sensor will alert when a glass window or door is being smashed or broken, providing an extra layer of advanced security for your property.Our proprietary microphone technology recognizes acoustic patterns to provide full coverage, with a maximum of 8m radius from sensor to glass. With four selectable sensitivity levels, ACGS-23ZW can be easily adjusted to fit large or small rooms. It can also be integrated into security system to activate a siren upon glass break, thereby detering burglars and preventing a full break-in.

Prepare for Installation / Reset

Please read the user manual before installing the product.

In order to include (add) a Z-Wave device to a network it must be in factory default
state.
Please make sure to reset the device into factory default. You can do this by
performing an Exclusion operation as described below in the manual. Every Z-Wave
controller is able to perform this operation however it is recommended to use the primary
controller of the previous network to make sure the very device is excluded properly
from this network.

Reset to factory default

This device also allows to be reset without any involvement of a Z-Wave controller. This
procedure should only be used when the primary controller is inoperable.

Factory Reset(Only use factory reset when network Control Panel/Gateway is missing or inoperable).1. Remove the batteries of the Glass Break Detector first.2. Press and hold the Function Button. While holding the Function Button, power on the Glass Break Detector by re-inserting the batteries, wait for 10 seconds to factory reset.1. Factory resetting the Glass Break Detector will restore it to factory default settings (excluded from the Z-Wave network). The Z-Wave gateway or control panel will still keep its Z-Wave settings. Please refer to the gateway or control panel manual on how to remove the Glass Break Detectors Z-Wave settings.

Inclusion/Exclusion

On factory default the device does not belong to any Z-Wave network. The device needs
to be added to an existing wireless network to communicate with the devices of this network.
This process is called Inclusion.

Devices can also be removed from a network. This process is called Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network. This
controller is turned into exclusion respective inclusion mode. Inclusion and Exclusion is
then performed doing a special manual action right on the device.

Inclusion

This product can be included and operated in any Z-Wave network with other Z-Wave certified devices from other manufactures and/or other applications. All non-battery operated nodes within the network will act as repeaters regardless of vendor to increase reliability of the network.1. Insert the 3V CR123A Lithium battery into the battery compartment connecting the correct polarity as shown on the battery compartment lid.2. Put the Z-Wave gateway or control panel into Inclusion or Learning mode (please refer to the Z-Wave gateway or control panel manual).3. Within 1 second, press the Function Button 3 times. 4. Refer to the operation manual of the Z-Wave gateway or control panel to complete the learn-in process.5.If the sensor has already been included (learnt) into another Z-Wave Gateway/Control Panel, or if the sensor is unable to be learnt into the current Z-Wave Gateway/Control Panel, please exclude it first (see Exclusion) before attempting to include it into the current Z-Wave Gateway/Control Panel.

Exclusion

The Glass Break Detector must be removed from existing Z-Wave network before being included into another. There are two methods available to exclude a device.Exclusion Mode1. Put the Z-Wave gateway or control panel into Exclusion mode (please refer to the Z-Wave gateway or control panel manual).2. Within 1 second, press the Function Button 3 times and the Glass Break Detector will be removed from the Z-Wave network.

Communication to a Sleeping device (Wakeup)

This device is battery operated and turned into deep sleep state most of the time
to save battery life time. Communication with the device is limited. In order to
communicate with the device, a static controller C is needed in the network.
This controller will maintain a mailbox for the battery operated devices and store
commands that can not be received during deep sleep state. Without such a controller,
communication may become impossible and/or the battery life time is significantly
decreased.

This device will wakeup regularly and announce the wakeup
state by sending out a so called Wakeup Notification. The controller can then
empty the mailbox. Therefore, the device needs to be configured with the desired
wakeup interval and the node ID of the controller. If the device was included by
a static controller this controller will usually perform all necessary
configurations. The wakeup interval is a tradeoff between maximal battery
life time and the desired responses of the device. To wakeup the device please perform
the following action:

This function uses the Z-Wave Wake Up Command Class. The Wake Up Command Class allows the battery-powered Glass Break Detector to notify the Control Panel/Gateway that it is awake and ready to receive any queued commands. The wake up time is programmed automatically according to Control Panels setting when The Glass Break Detector is included. The recommended setting of the wake up time is 60 minutes above.

Quick trouble shooting

Here are a few hints for network installation if things dont work as expected.

  1. Make sure a device is in factory reset state before including. In doubt exclude before include.
  2. If inclusion still fails, check if both devices use the same frequency.
  3. Remove all dead devices from associations. Otherwise you will see severe delays.
  4. Never use sleeping battery devices without a central controller.
  5. Dont poll FLIRS devices.
  6. Make sure to have enough mains powered device to benefit from the meshing

Association – one device controls an other device

Z-Wave devices control other Z-Wave devices. The relationship between one device
controlling another device is called association. In order to control a different
device, the controlling device needs to maintain a list of devices that will receive
controlling commands. These lists are called association groups and they are always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’ Command.

Association Groups:

Group NumberMaximum NodesDescription

1| 1| Group 1 for LifeLine (max node = 1):Notification CC,V3 (COMMAND_CLASS_NOTIFICATION)Battery CC (COMMAND_CLASS_BATTERY)Device Reset Locally CCNotification Report1. If Glass Break Detector is triggered, it will send a Notification Report (Type: 0x07, Event 0x06).2. If tamper is open, it will send Notification Report (Type: 0x07, Event: 0x03)3. If tamper is closed, it will send Notification Report (Type: 0x07, Event: 0x00, Parmeter:0x03).Battery Report1. If battery level changes, it will send Battery Report (0x64, 0x4B, 0x32, 0x19, or 0xFF) respectively.0x64 — 100% Battery Full0x4B — 75% Battery0x32 — 50% Battery0x19 — 25% Battery0xFF — Battery Dead (Cut Off)Device Reset1. To perform factory reset, press and hold the Function Button for 10 seconds, the device will send a DEVICE_RESET_LOCALLY_NOTIFICATION report.
---|---|---
2| 1| Group 2 for Basic Set (max node = 1):BASIC CC (COMMAND_CLASS_BASIC)1. When the detector is triggered, it will send BASIC SET (0xFF). The device does NOT support Restore Event report.

Technical Data

Hardware Platform ZM5202
Device Type Notification Sensor
Network Operation Reporting Sleeping Slave
Firmware Version HW: 255 FW: 4.01
Z-Wave Version 6.81.04
Certification ID ZC10-19066571
Z-Wave Product Id 0x018E.0x0003.0x000E
Firmware Updatable Updatable by Consumer by RF
Supported Notification Types Home Security
Security V2 S2_UNAUTHENTICATED
Frequency XXfrequency
Maximum transmission power XXantenna

Supported Command Classes

  • Association Grp Info
  • Association V2
  • Battery
  • Device Reset Locally
  • Firmware Update Md V4
  • Manufacturer Specific V2
  • Multi Channel Association V3
  • Notification V8
  • Powerlevel
  • Security 2
  • Supervision
  • Transport Service V2
  • Version V3
  • Wake Up V2
  • Zwaveplus Info V2

Controlled Command Classes

  • Basic

Explanation of Z-Wave specific terms

  • Controller — is a Z-Wave device with capabilities to manage the network.
    Controllers are typically Gateways,Remote Controls or battery operated wall controllers.

  • Slave — is a Z-Wave device without capabilities to manage the network.
    Slaves can be sensors, actuators and even remote controls.

  • Primary Controller — is the central organizer of the network. It must be
    a controller. There can be only one primary controller in a Z-Wave network.

  • Inclusion — is the process of adding new Z-Wave devices into a network.

  • Exclusion — is the process of removing Z-Wave devices from the network.

  • Association — is a control relationship between a controlling device and
    a controlled device.

  • Wakeup Notification — is a special wireless message issued by a Z-Wave
    device to announces that is able to communicate.

  • Node Information Frame — is a special wireless message issued by a
    Z-Wave device to announce its capabilities and functions.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Climax Technology User Manuals

Related Manuals