SE Devices Multifunction Switch FMS Manual
- June 8, 2024
- SE Devices
Table of Contents
- SE Devices
- Multifunction Switch
- SKU: FMS
- Quickstart
- Important safety information
- What is Z-Wave?
- Product Description
- Prepare for Installation / Reset
- Inclusion/Exclusion
- Quick trouble shooting
- Association – one device controls an other device
- Configuration Parameters
- Parameter 10: Dimming Speed
- Parameter 11: Dimmer Mode
- Parameter 12: Maximum Level
- Parameter 13: Minimum Level
- Parameter 14: Button Mode
- Parameter 15: Light Zone Control Mode
- Parameter 17: Back Unit Role
- Parameter 18: Back Unit Light Zone
- Parameter 240: Floor Sensor Temperature Offset
- Parameter 241: Room Sensor Temperature Offset
- Parameter 32: Thermostat Set Point Max
- Parameter 34: Thermostat Set Point Min
- Parameter 36: Thermostat Control Resend Interval
- Parameter 37: Thermostat Minimum On/Off Interval
- Parameter 38: Thermostat Floor Temp Max
- Parameter 4: Safety Activate Delay
- Parameter 40: Temperature Sensor Select
- Parameter 44: Cold Start Minimum Level
- Parameter 5: Safety OFF Period
- Parameter 6: Safety ON Period
- Parameter 64: Temperature Report Inteval
- Parameter 66: Temperature Report Threshold
- Parameter 67: Thermostat OnOff Interval Override Threshold
- Parameter 80: Button LED Mode
- Technical Data
- Supported Command Classes
- Controlled Command Classes
- Explanation of Z-Wave specific terms
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
SE Devices
Multifunction Switch
SKU: FMS
Quickstart
This is a
secure
Wall Controller
for
CEPT (Europe).
To run this device please connect it to your mains power supply.
To add this device to your network execute the following action:
Push and Hold both Lower buttons simultaneously for 5 seconds. Inclusion is
indicated by the LEDs flashing in a “U” shaped pattern.
Please refer to the
Manufacturers
Manual
for more information.
Important safety information
Please read this manual carefully. Failure to follow the recommendations in
this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any
loss or damage resulting from failure to comply with the instructions in this
manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal
instructions.
Do not dispose of electronic equipment or batteries in a fire or near open heat sources.
What is Z-Wave?
Z-Wave is the international wireless protocol for communication in the Smart
Home. This
device is suited for use in the region mentioned in the Quickstart section.
Z-Wave ensures a reliable communication by reconfirming every message ( two-
way
communication) and every mains powered node can act as a repeater for other
nodes
( meshed network ) in case the receiver is not in direct wireless range of
the
transmitter.
This device and every other certified Z-Wave device can be used together
with any other
certified Z-Wave device regardless of brand and origin as long as both are
suited for the
same frequency range.
If a device supports secure communication it will communicate with other
devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to
maintain
backward compatibility.
For more information about Z-Wave technology, devices, white papers etc.
please refer
to www.z-wave.info.
Product Description
The Multifunction Switch is a Z-Wave Plus mains powered Wallbox mountable Wall Controller. It can be configured to control up to Four separate Light Zones or Central Scenes. Each Light Zone can consist of both Dimmers and Switches. The device can be combined with a Back Unit, which provide local Switch or Dimmer functionality.Room and Floor temperature sensors can also be connected to the device, which enables the device to function as a head-less Thermostat. The Thermostat is fully controllable from a Z-Wave Controller, and can control both a Local and Remote heating relay.
Prepare for Installation / Reset
Please read the user manual before installing the product.
In order to include (add) a Z-Wave device to a network it must be in factory
default
state. Please make sure to reset the device into factory default. You can do
this by
performing an Exclusion operation as described below in the manual. Every
Z-Wave
controller is able to perform this operation however it is recommended to use
the primary
controller of the previous network to make sure the very device is excluded
properly
from this network.
Reset to factory default
This device also allows to be reset without any involvement of a Z-Wave
controller. This
procedure should only be used when the primary controller is inoperable.
Push and Hold both Left buttons simultaneously for 15 seconds, until the Lower Left LED starts blinking. Push and Hold the Lower Right button to confirm Factory Reset. The procedure can be aborted at any time, and will also be aborted if any other button than the Lower Right is pushed after the initial 15 second push and hold.WARNING! Executing a Factory Reset will set all configuration to factory defaults, and remove the device from the Z-Wave network. As all configuration is reset, the device may stop operating as intended and may require a re-configuration. Please use this procedure only when the network primary controller is missing or otherwise inoperable.
Safety Warning for Mains Powered Devices
ATTENTION: only authorized technicians under consideration of the country-
specific
installation guidelines/norms may do works with mains power. Prior to the
assembly of
the product, the voltage network has to be switched off and ensured against
re-switching.
Inclusion/Exclusion
On factory default the device does not belong to any Z-Wave network. The
device needs
to be added to an existing wireless network to communicate with the
devices of this network.
This process is called Inclusion.
Devices can also be removed from a network. This process is called
Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network.
This
controller is turned into exclusion respective inclusion mode. Inclusion and
Exclusion is
then performed doing a special manual action right on the device.
Inclusion
Push and Hold both Lower buttons simultaneously for 5 seconds. Inclusion is indicated by the LEDs flashing in a “U” shaped pattern.
Exclusion
Push and Hold both Lower buttons simultaneously for 5 seconds. Exclusion is indicated by the LEDs flashing in a “U” shaped pattern.
Quick trouble shooting
Here are a few hints for network installation if things dont work as expected.
- Make sure a device is in factory reset state before including. In doubt exclude before include.
- If inclusion still fails, check if both devices use the same frequency.
- Remove all dead devices from associations. Otherwise you will see severe delays.
- Never use sleeping battery devices without a central controller.
- Dont poll FLIRS devices.
- Make sure to have enough mains powered device to benefit from the meshing
Association – one device controls an other device
Z-Wave devices control other Z-Wave devices. The relationship between one
device
controlling another device is called association. In order to control a
different
device, the controlling device needs to maintain a list of devices that will
receive
controlling commands. These lists are called association groups and they are
always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’
Command.
Association Groups:
Group NumberMaximum NodesDescription
1| 5| Z-Wave Plus Lifeline – Supports MultichannelOnly local Light Zone
changes are reported if Multichannel association is not used.Commands issued:-
Basic Report: Reports Light Zone state and level changes- Central Scene
Notification: Notifies activated Scenes- Sensor Multilevel Report: Power
Consumption and Air Temperature (if a sensor is connected)- Meter: Reports
energy consumption- Device Reset Locally – Reports device Factory Reset
---|---|---
2| 5| Controls devices in Light Zone 1. Supports Multichannel
AssociationCommands Issued:- Basic Set: Controlled by Light Zone 1. Dimmer or
Switch mapped Basic command values is configurable
3| 5| Controls devices in Light Zone 2. Supports Multichannel
AssociationCommands Issued:- Basic Set: Controlled by Light Zone 1. Dimmer or
Switch mapped Basic command values is configurable
4| 5| Controls devices in Light Zone 3. Supports Multichannel
AssociationCommands Issued:- Basic Set: Controlled by Light Zone 1. Dimmer or
Switch mapped Basic command values is configurable
5| 5| Controls devices in Light Zone 4. Supports Multichannel
AssociationCommands Issued:- Basic Set: Controlled by Light Zone 1. Dimmer or
Switch mapped Basic command values is configurable
6| 5| Enables control of external Heating Thermostats in the same heating
zone.Commands Issued:- Thermostat Setpoint Set: Sent on local Thermostat Set-
Point changes- Thermostat Mode Set: Sent on local Thermostat Mode changes
7| 5| Enables the Thermostat to control Remote Heating Relays.Commands
issued:- Basic Set: Value ON (255) or OFF (0), according to Thermostat Heating
State changes.
Configuration Parameters
Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock
further
enhanced features.
IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200 it may be needed to set a value of 200 minus 256 = minus
56.
In case of a two byte value the same logic applies: Values greater than 32768
may
needed to be given as negative values too.
Parameter 10: Dimming Speed
Defines the u0022fadeu0022 time when setting a dim level from a controller.
Fade time is defined as the time it takes to dim from MIN level to MAX level,
which means an increase of 10% in light level takes 1/10th of the configured
time. The value defines the dim time in 1/100’th of a second, which means a
value of 200 means the Dimming Speed is 2.0 seconds from MIN to MAX. Max time
is 327.67 seconds (around 5.5 minutes). Values below 300 (0.3 seconds) are
ignored and values below 1000 (1 second) are discouraged.
Size: 1 Byte, Default Value: 200
SettingDescription
30 – 32767 | Dimmer Speed in 1/100th of a Second |
---|
Parameter 11: Dimmer Mode
Defines if Dimmer should operate in Leading or Tailing Edge mode. Most
Lights work quite OK in the default Leading Edge mode, but this mode also
usually cause some noise from the dimmer unit. During installation it is
therefore recommended to try TE mode, and use this if the Light operates
properly. Tailing Edge mode is known to cause instability in some type of
Lights! This configuration does not have an effect on 1-10V Dimmer Back
Units!0 = Leading Edge Mode (LE)1 = Tailing Edge Mode (TE)
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 1 | Dimmer Operation Mode |
---|
Parameter 12: Maximum Level
The Maximum Light level of the dimmer. Typically there is no visible
difference when the dimming level reaches a point in the range 75 – 90, and
the installer should set this value to the lowest value where no change is
visible. The default value of 90 is usually OK. Range 1-99.
Size: 1 Byte, Default Value: 90
SettingDescription
1 – 99 | Maximum Dimmer Level |
---|
Parameter 13: Minimum Level
The Minimum Light Level of the dimmer. This should be adjusted so the
controlled Light is still ON and stable. Remember that LED type lights may
work if dimmed down to a low value, but may not start if the light is turned
OFF and ON again. Range 1-99.
Size: 1 Byte, Default Value: 12
SettingDescription
1 – 99 | Minimum Dimmer Level |
---|
Parameter 14: Button Mode
Controls the operation mode of the buttons. Valid configuration values
are:0Single Switch Mode (default)1Dual Switch Mode2Quadruple Switch
Mode3Legacy Scenario Mode4Central Scene Controller Mode(See detailed
description in manual)
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 4 | Set Button Mode |
---|
Parameter 15: Light Zone Control Mode
Controls if the Light Zones should operate in Switch or Dimmer Mode (only
used in Button Modes 0, 1 and 2):0All Light Zones in Dimmer Mode (default)1All
Light Zones in Switch Mode (default with Relay back unit)To control Light
Zones mode individually, add any of the following values to enable switch mode
individually (dimmer is default):2Light Zone 1 Switch Mode4Light Zone 2 Switch
Mode8Light Zone 3 Switch Mode16Light Zone 4 Switch ModeExample: A value of 10
(8 + 2) enables switch mode in Light Zone 1 and 3.
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 1 | Common Mode for all Light Zones |
---|---|
2 – 30 | Switch Mode for individual Light Zones |
Parameter 17: Back Unit Role
Configures the Role of the Back Unit, which dictates what Local
functionality controls it.Valid configuration values are:0 – The Thermostat
will control the Back Unit (if the back unit is a dimmer, then this value has
no effect as Thermostats requires a relay to function)1 – The Light Control
feature (buttons) will control the Back Unit.2 – Disconnected mode means the
Back Unit is not controlled by any local UI or features, and can only be
controlled via Z-Wave End-Point 5 (or non-channel encapsulated commands).
Size: 1 Byte, Default Value: 1
SettingDescription
0 – 2 | Selected Back Unit Role |
---|
Parameter 18: Back Unit Light Zone
Selects which Light Zone the Back Unit should be assigned to. Possible
values are:1Light Zone 1 (Button and Z-Wave) (default)2Light Zone 2 (Button
and Z-Wave)3Light Zone 3 (Button and Z-Wave)4Light Zone 4 (Button and
Z-Wave)This can be used to assign the back unit control to any of the
Multiswitch buttons (Light Zone 1 – 4). This does not have any effect however
when the BU role is set to Thermostat or Disconnected!
Size: 1 Byte, Default Value: 1
SettingDescription
1 – 4 | Selected Back Unit Light Zone |
---|
Parameter 240: Floor Sensor Temperature Offset
Defines an offset to the Floor Temperature, given as a signed integer at
1/10 of a degree celcius. This provides an offset range of 12.8 to +12.7
degrees celcius (-128 to 127).
Size: 1 Byte, Default Value: 0
SettingDescription
-128 – 127 | Temperature Offset in 1/10th of a degree Celcius |
---|
Parameter 241: Room Sensor Temperature Offset
Defines an offset to the Room Temperature, given as a signed integer at 1/10
of a degree celcius. This provides an offset range of 12.8 to +12.7 degrees
celcius (-128 to 127).
Size: 1 Byte, Default Value: 0
SettingDescription
-128 – 127 | Temperature Offset in 1/10th of a degree Celcius |
---|
Parameter 32: Thermostat Set Point Max
Maximum Heat Set Point the Thermostat is allowed to be set to. If the
Thermostat is used for Floor Heating, please make sure that this value is
configured to the same value as (or lower than) the Max Floor Temperature.
Given in 1/10 of a degree Celcius, which means a value of 300 means 30 degrees
C. Range: 0500 (0-50 degrees).
Size: 2 Byte, Default Value: 270
SettingDescription
0 – 500 | Set Point Max in 1/10th of a degree Celcius |
---|
Parameter 34: Thermostat Set Point Min
Minimum Heat Set Point the Thermostat is allowed to be set to. Given in 1/10
of a degree Celcius, which means a value of 50 means 5 degrees C. Range: 0500
(0-50 degrees).
Size: 2 Byte, Default Value: 50
SettingDescription
0 – 500 | Set Point Min in 1/10th of a degree Celcius |
---|
Parameter 36: Thermostat Control Resend Interval
Defines the interval between each time the Thermostat will repeat its last
control command. This is used in combination with the Relay Safety
configuration when controlling external Relays. If the Thermostat should fail,
it would then stop sending control commands which in turn means the Relay will
turn itself OFF after the safety mode delay has expired. This insures that
heating will not be left ON indefinitely in failure situations. Range: 6032767
seconds
Size: 2 Byte, Default Value: 3600
SettingDescription
0 – 32767 | Resend Interval in seconds |
---|
Parameter 37: Thermostat Minimum On/Off Interval
This configuration defines the minimum interval the controlled Thermostat
Relays will be ON and OFF. This is a feature intended to avoid turning control
relays ON and OFF too frequently, which should insure a better lifetime of
controlled relays. The default value is 5 minutes, which is OK for most
electrical heating control. If used to control Water based heating, the value
MUST be adjusted in accordance with the manufacturers specifications. Range:
6032767 seconds
Size: 2 Byte, Default Value: 300
SettingDescription
60 – 32767 | Minimum On/Off interval in seconds |
---|
Parameter 38: Thermostat Floor Temp Max
Max floor temperature if a local floor sensor is connected. If the Floor
Sensor reads a temperature Higher than the configured value, it will
immediately turn the relay (or any associated relays) OFF. The relay will stay
off until the temperature sinks below this value, and the Thermostat issues
it’s next control command. Disabled if zero (0) value, or if no floor sensor
is connected. The value is given as 1/10th of a degree Celcius. Range: 0500
(0-50 degrees). NOTE! MAX 27 degrees is recommended for Wooden Floors! NOTE!
This function is always active as long as a Floor Sensor is connected,
regardless of the sensor configuration described below.
Size: 2 Byte, Default Value: 270
SettingDescription
0 – 500 | Floor Temp Max in 1/10th of a degree Celcius |
---|
Parameter 4: Safety Activate Delay
Safety Mode is activated after the configured number of seconds has elapsed.
It will start by turning OFF the Back Unit when activated. A 0 value Disables
Safety Mode. The MAX limit is 32767 seconds (9 hours, 6 minutes and 7
seconds). The minimum Actication delay is 60 seconds, and values from 1 to 59
will automatically be translated to a 60 second delay.
Size: 2 Byte, Default Value: 0
SettingDescription
0 – 32767 | Safety Activate Delay in seconds |
---|
Parameter 40: Temperature Sensor Select
Defines which temperature Sensor should be used for Heating Control. The
default value is Both (3), which should work well in most scenarios (even when
only a Floor or Room sensor is present). If both a Room and Floor sensor is
used, the Thermostat will always control heating based on the lowest
temperature reading of the two, to insure a comfortable floor temperature even
if the room is already warm enough. If this is not wanted, the Thermostat
should be configured to use the Room sensor Only. NOTE! The Floor Max
Temperature feature will ALWAYS be active as long as a floor sensor is
available, even if the Thermostat is configured to only use the Room Sensor. 1
– Local Room – Use temperature from Locally connected Room sensor ONLY. Max
Floor Temp protection is still active as long as a floor sensor is available.
2 – Local Floor – Use temperature from Locally connected Floor sensor ONLY 3 –
Both (auto) – Use temperature from Locally connected Floor AND Room sensor if
available (Default).
Size: 1 Byte, Default Value: 3
SettingDescription
1 – 3 | Temperature Sensor Select |
---|
Parameter 44: Cold Start Minimum Level
Sets the minimum level the Dimmer should go to when the light is switched
ON. This is typically used for LED lamps which does not switch ON correctly
when the dimming level is at the Minimum. See detailed description below.
Size: 1 Byte, Default Value: 12
SettingDescription
1 – 99 | Cold Start Minimum Level |
---|
Parameter 5: Safety OFF Period
The number of seconds to stay in OFF mode when Safety is activated. The Back
unit turns ON when the timer have elapsed. If value is 0, the Back Unit will
not turn back ON. The MAX limit is 32767 seconds (9 hours, 6 minutes and 7
seconds). A 60 second minimum period applies.
Size: 2 Byte, Default Value: 600
SettingDescription
0 – 32767 | Safety OFF Period in seconds |
---|
Parameter 6: Safety ON Period
The number of seconds to stay in ON mode when Safety is activated. The Back
Unit turns back OFF when the timer have elapsed (and continues to turn ON and
OFF alternately). If value is 0, the Back Unit WILL NOT turn ON at all. The
MAX limit is 32767 seconds (9 hours, 6 minutes and 7 seconds). A 60 second
minimum period applies.
Size: 2 Byte, Default Value: 300
SettingDescription
0 – 32767 | Safety ON Period in seconds |
---|
Parameter 64: Temperature Report Inteval
Defines the Periodic Report interval for temperature readings. This can be
configured to a minimum of 60 seconds and maximum of (32767 seconds. A 0 value
disables the Interval based Periodic reporting, and any value below 60 results
in a 60 second interval.
Size: 2 Byte, Default Value: 600
SettingDescription
0 – 32767 | Report Interval in seconds |
---|
Parameter 66: Temperature Report Threshold
Defines a temperature change threshold where a temperature report is sent
regardless of the Report Interval. This also works if the report interval is
disabled. The value is given in 1/10 of a degree celsius, and can be in the
range 1-127. A zero value disables the Threshold.
Size: 1 Byte, Default Value: 10
SettingDescription
0 – 127 | Report Threshold in 1/10th of a degree Celcius |
---|
Parameter 67: Thermostat OnOff Interval Override Threshold
Defines a temperature threshold at which the configured On/Off interval is
overridden and the Heating relay state will change regardless. The value is
given in 1/10th of a degree, supporting a max threshold of 12.7 degrees
celcius. A Zero (0) value disables this feature (the default)
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 127 | Temperature Threshold in 1/10th of a degree Celcius |
---|
Parameter 80: Button LED Mode
Controls the operation of the LEDs. Possible values are:0LEDs are always OFF
(default)1Momentary ON2Stable ONThe LED operation is described in details in
the User Manual, and also depends on the Button Mode configuration.
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 2 | Selected LED Mode |
---|
Technical Data
Hardware Platform | ZM5202 |
---|---|
Device Type | Wall Controller |
Network Operation | Always On Slave |
Firmware Version | HW: 30 FW: 3.00:03.00 |
Z-Wave Version | 6.71.01 |
Certification ID | ZC10-18026000 |
Z-Wave Product Id | 0x024F.0x0003.0x1002 |
Sensors | |
Thermostat HVAC Systems Supported | |
Thermostat Power Source | |
Thermostat Modes | |
Color | |
Z-Wave Scene Type | |
Electric Load Type | |
Firmware Updatable | |
Switch Type | |
Supported Meter Type | |
Neutral Wire Required | ok |
Security V2 | S2_UNAUTHENTICATED |
Frequency | XXfrequency |
Maximum transmission power | XXantenna |
Supported Command Classes
- Association Grp Info
- Association V2
- Basic
- Central Scene V3
- Configuration
- Device Reset Locally
- Firmware Update Md V4
- Manufacturer Specific V2
- Meter V2
- Multi Channel Association V3
- Multi Channel V4
- Powerlevel
- Security
- Security 2
- Sensor Multilevel V5
- Supervision
- Switch Binary
- Switch Multilevel
- Thermostat Mode
- Thermostat Setpoint
- Transport Service V2
- Version V2
- Zwaveplus Info V2
Controlled Command Classes
- Basic
- Thermostat Mode
- Thermostat Setpoint
Explanation of Z-Wave specific terms
-
Controller — is a Z-Wave device with capabilities to manage the network.
Controllers are typically Gateways,Remote Controls or battery operated wall controllers. -
Slave — is a Z-Wave device without capabilities to manage the network.
Slaves can be sensors, actuators and even remote controls. -
Primary Controller — is the central organizer of the network. It must be
a controller. There can be only one primary controller in a Z-Wave network. -
Inclusion — is the process of adding new Z-Wave devices into a network.
-
Exclusion — is the process of removing Z-Wave devices from the network.
-
Association — is a control relationship between a controlling device and
a controlled device. -
Wakeup Notification — is a special wireless message issued by a Z-Wave
device to announces that is able to communicate. -
Node Information Frame — is a special wireless message issued by a
Z-Wave device to announce its capabilities and functions.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>