Solarclarity SPA4-10K series solar system Instruction Manual
- June 8, 2024
- Solarclarity
Table of Contents
SPA4-10K series solar system
ON
DIP
ON
DIP
Auto Loop Display
WorkMode Input&Output Para
Offline
WorkMode (Lead acid)Vb:xx.xV (Lithium)Vb/Cb:xx.xVxxx%
Battery information
WorkMode
Battery power
Pbat: (+/-)XXXX W
Online
WorkMode EPS_R:xxxV/xxHz
EPS-R information
WorkMode Grid_R:xxxV/xxHz
GridR information
WorkMode EPS_S:xxxV/xxHz
EPS-S information
WorkMode Grid_S:xxxV/xxHz
GridS information
WorkMode EPS_T:xxxV/xxHz
WorkMode EPS_R: xx.xkW
WorkMode EPS_S: xx.xkW
WorkMode EPS_T: xx.xkW
EPS-T information
EPS-R output power
EPS-S output power EPS-T output power
Power to grid or to user To grid is To user is +
WorkMode Grid_T:xxxV/xxHz
GridT information
WorkMode Po: xx.xkW
WorkMode Po: xx.xkVA
Output AC Power
Cycle display 2 times in 6 seconds
WorkMode Per_Load: %
Load ratio
WorkMode Pm: (+/-)XXXXW
Button operation display
WorkMode Ec_d:xxxx.x KWh
BAT Charge_Etoday energy
WorkMode Ec_a:xxxx.x KWh
BAT Charge_Etotal energy
WorkMode Ed_d:xxxx.x KWh
BAT Discharge_Etoday energy
WorkMode Ed_a:xxxx.x KWh
BAT Discharge_Etotal energy
Press up key
WorkMode Eac_d:xxxx.x KWh
AC output_Etoday energy
WorkMode Eac_a:xxxx.x KWh
AC output_Etotal energy
WorkMode 20XX/XX/XX/XX:XX
System Time
WorkMode SerNo:xxxxxxxxxx
Serial number
WorkMode Model:xxxxxxxxxx
Machine model
WorkMode FW Version:xxxx
Firmware version
Press “enter” key more than 3 seconds into setup mode
WorkMode Configuration
WorkMode Basic Parameter
Press “down” key to the next item
WorkMode BackUp
WorkMode Priority
WorkMode Mode Change
WorkMode ExportLimit
WorkMode Default Set
WorkMode Auto Test
Press “enter” key more than 1 seconds to make sure
Press “enter” key more than 1 seconds to make sure
WorkMode
WorkMode
Basic Parameter
Language
Press “down” key to the next item
WorkMode
Lead-acid LV
Only display when battery type is lead-acid
WorkMode Lead-acid CC
WorkMode Lead-acid CV
WorkMode System time
Press “enter” key more than 1 seconds to make sure
WorkMode English
Italian German
WorkMode 1600V
Range from 100 to 550V, and the accuracy is 1V
WorkMode 205 A
Range from 0 to 25A, and the accuracy is 1A
WorkMode 550V
Range from 100 to 550V, and the accuracy is 1V
WorkMode xxD/xxM/xxxxY XX:XX
Press “enter” key more than 1 seconds to make sure
WorkMode BackUp
EPS setup
Press “enter” key more than 1 seconds to make sure
WorkMode Backup: Enable
Press “down”
Disable
key to the next item
WorkMode ACVolt: 230 V
240 208
WorkMode AC Freq: 50 Hz
60
WorkMode Priority
Press “down” key to the next item
WorkMode Opt: Load First
Bat First Grid First
If battery first is choosen
WorkMode Bat First: OK
NO
Choose “OK” to the next item
If you need to enable AC charging function, you need key password
WorkMode SC :
WorkMode AC CHG: Enable
Disable
WorkMode Time
WorkMode 00:00 00:00
If Grid first is choosen
WorkMode Grid First: OK
NO
Choose “OK” to the next item
Press “down” key to the next item
WorkMode Stop SOC: 100%
Range from 5% to 100%, and the accuracy is 1%
WorkMode Power Rate: 100 %
Range from 5% to 100%, and the accuracy is 1%
WorkMode Save OK
NO
WorkMode Time
WorkMode 00:00 00:00
WorkMode Stop SOC: 5%
Range from 5% to 100%, and the accuracy is 1%
WorkMode Power Rate: 100 %
Range from 5% to 100%, and the accuracy is 1%
WorkMode Save OK
NO
Press “enter” key to make sure
WorkMode Mode Change
Press “down” key to the next item
WorkMode Battery Type
Press “enter” key to make sure
WorkMode
Lithium Lead-acid
Press “enter” key more than 1 seconds to make sure
WorkMode ExportLimit
Press “enter” key to make sure
WorkMode ExportLimit: OFF
Press “down”
ON
key to the next item
WorkMode PowerRate: 00.0%
Range from 00.0% to 100.0%, and the accuracy is 0.1%
WorkMode Fail Safe: ON
OFF
Press “enter” key to make sure
WorkMode Default Set
Press “enter” key more than 3 seconds to make sure
WorkMode YES
WorkMode Auto Test
WorkMode YES ?
Press “enter”more than 3 seconds to enter
59.S2 Limit Waiting to start
59.S2 Limit 264.5 V 200ms
59.S2 Testing 230.8 V – xxx V
59.S2 Pass 264.7 V 180ms
27.S1 Limit 195.5 V 400ms
59.S2 Testing 230.8 V – xxx V
59.S2 Pass 194.7 V 380ms
81>S2 Limit 51.5Hz 100ms
81>S2 Testing 50.01-xxxxHz
81>S2 Pass 51.52Hz 80ms
81<S2 Limit 47.50Hz 100ms
81<S2 Testing 50.01-xxxxHz
81<S2 Pass 47.49Hz 80ms
59.S1 Limit 253.0V 3000ms
59.S1 Testing 230.4 – xxxxV
59.S1 Pass 254.7V 3000ms
27.S2 Limit 92.0V 200ms
27.S2 Testing 230.4- xxxxV
27.S2 Pass 90.8V 180ms
81>S1 Limit 50.5Hz 100ms
81>S1 Testing 50.01- xxxxHZ
81>S1 Pass 50.05Hz 80ms
81<S1 Limit 49.5Hz 100ms
81<S1 Testing 50.01- xxxxHZ
81<S1 Pass 49.5Hz 80ms
Auto Testing Auto Test Passed