Solarclarity SPA4-10K series solar system Instruction Manual

June 8, 2024
Solarclarity

SPA4-10K series solar system

ON

DIP

ON

DIP

Auto Loop Display

WorkMode Input&Output Para

Offline

WorkMode (Lead acid)Vb:xx.xV (Lithium)Vb/Cb:xx.xVxxx%

Battery information

WorkMode

Battery power

Pbat: (+/-)XXXX W

Online

WorkMode EPS_R:xxxV/xxHz

EPS-R information

WorkMode Grid_R:xxxV/xxHz

GridR information

WorkMode EPS_S:xxxV/xxHz

EPS-S information

WorkMode Grid_S:xxxV/xxHz

GridS information

WorkMode EPS_T:xxxV/xxHz
WorkMode EPS_R: xx.xkW
WorkMode EPS_S: xx.xkW
WorkMode EPS_T: xx.xkW

EPS-T information
EPS-R output power
EPS-S output power EPS-T output power
Power to grid or to user To grid is To user is +

WorkMode Grid_T:xxxV/xxHz

GridT information

WorkMode Po: xx.xkW
WorkMode Po: xx.xkVA

Output AC Power
Cycle display 2 times in 6 seconds

WorkMode Per_Load: %

Load ratio

WorkMode Pm: (+/-)XXXXW

Button operation display

WorkMode Ec_d:xxxx.x KWh

BAT Charge_Etoday energy

WorkMode Ec_a:xxxx.x KWh

BAT Charge_Etotal energy

WorkMode Ed_d:xxxx.x KWh

BAT Discharge_Etoday energy

WorkMode Ed_a:xxxx.x KWh

BAT Discharge_Etotal energy

Press up key

WorkMode Eac_d:xxxx.x KWh

AC output_Etoday energy

WorkMode Eac_a:xxxx.x KWh

AC output_Etotal energy

WorkMode 20XX/XX/XX/XX:XX

System Time

WorkMode SerNo:xxxxxxxxxx

Serial number

WorkMode Model:xxxxxxxxxx

Machine model

WorkMode FW Version:xxxx

Firmware version

Press “enter” key more than 3 seconds into setup mode
WorkMode Configuration

WorkMode Basic Parameter

Press “down” key to the next item

WorkMode BackUp

WorkMode Priority

WorkMode Mode Change
WorkMode ExportLimit

WorkMode Default Set

WorkMode Auto Test

Press “enter” key more than 1 seconds to make sure

Press “enter” key more than 1 seconds to make sure

WorkMode

WorkMode

Basic Parameter

Language

Press “down” key to the next item

WorkMode

Lead-acid LV

Only display when battery type is lead-acid

WorkMode Lead-acid CC

WorkMode Lead-acid CV

WorkMode System time

Press “enter” key more than 1 seconds to make sure
WorkMode English
Italian German

WorkMode 1600V

Range from 100 to 550V, and the accuracy is 1V

WorkMode 205 A

Range from 0 to 25A, and the accuracy is 1A

WorkMode 550V

Range from 100 to 550V, and the accuracy is 1V

WorkMode xxD/xxM/xxxxY XX:XX

Press “enter” key more than 1 seconds to make sure
WorkMode BackUp
EPS setup

Press “enter” key more than 1 seconds to make sure

WorkMode Backup: Enable

Press “down”

Disable

key to the next item

WorkMode ACVolt: 230 V
240 208

WorkMode AC Freq: 50 Hz
60

WorkMode Priority

Press “down” key to the next item
WorkMode Opt: Load First
Bat First Grid First

If battery first is choosen
WorkMode Bat First: OK
NO

Choose “OK” to the next item

If you need to enable AC charging function, you need key password
WorkMode SC :

WorkMode AC CHG: Enable
Disable

WorkMode Time

WorkMode 00:00 ­ 00:00

If Grid first is choosen
WorkMode Grid First: OK
NO

Choose “OK” to the next item
Press “down” key to the next item

WorkMode Stop SOC: 100%

Range from 5% to 100%, and the accuracy is 1%

WorkMode Power Rate: 100 %

Range from 5% to 100%, and the accuracy is 1%

WorkMode Save OK
NO

WorkMode Time

WorkMode 00:00 ­ 00:00

WorkMode Stop SOC: 5%

Range from 5% to 100%, and the accuracy is 1%

WorkMode Power Rate: 100 %

Range from 5% to 100%, and the accuracy is 1%

WorkMode Save OK
NO

Press “enter” key to make sure
WorkMode Mode Change

Press “down” key to the next item
WorkMode Battery Type

Press “enter” key to make sure
WorkMode
Lithium Lead-acid

Press “enter” key more than 1 seconds to make sure
WorkMode ExportLimit

Press “enter” key to make sure

WorkMode ExportLimit: OFF

Press “down”

ON

key to the next item

WorkMode PowerRate: 00.0%

Range from 00.0% to 100.0%, and the accuracy is 0.1%

WorkMode Fail Safe: ON
OFF

Press “enter” key to make sure
WorkMode Default Set

Press “enter” key more than 3 seconds to make sure
WorkMode YES

WorkMode Auto Test

WorkMode YES ?
Press “enter”more than 3 seconds to enter

59.S2 Limit Waiting to start
59.S2 Limit 264.5 V 200ms
59.S2 Testing 230.8 V – xxx V
59.S2 Pass 264.7 V 180ms
27.S1 Limit 195.5 V 400ms
59.S2 Testing 230.8 V – xxx V
59.S2 Pass 194.7 V 380ms
81>S2 Limit 51.5Hz 100ms
81>S2 Testing 50.01-xxxxHz
81>S2 Pass 51.52Hz 80ms
81<S2 Limit 47.50Hz 100ms
81<S2 Testing 50.01-xxxxHz
81<S2 Pass 47.49Hz 80ms

59.S1 Limit 253.0V 3000ms
59.S1 Testing 230.4 – xxxxV
59.S1 Pass 254.7V 3000ms
27.S2 Limit 92.0V 200ms
27.S2 Testing 230.4- xxxxV
27.S2 Pass 90.8V 180ms
81>S1 Limit 50.5Hz 100ms
81>S1 Testing 50.01- xxxxHZ
81>S1 Pass 50.05Hz 80ms
81<S1 Limit 49.5Hz 100ms
81<S1 Testing 50.01- xxxxHZ
81<S1 Pass 49.5Hz 80ms
Auto Testing Auto Test Passed