Introduction

Thank you for purchasing this quality product. To minimize the risk of injury we urge that our clients take some basic safety precautions when using this device. Please read the operation instructions carefully and make sure you have understood its content.
Keep these operation instructions safe.

DQ320 (50651)

In general

The electrically operated ball valves of the series DQ320 are used for switching on/off the tap water pipes of the heating and air conditioning systems. It consists of a pump casing and an electric servomotor. The servomotor activates the ball valve. It is equipped with alarm contacts, which holds ball valve in end position “wide open” or “completely closed.” The valve body is made of forged brass and nickel plated.

Technical data

Energy supply 230 V ±10 %, 50/60 Hz
Power consumption (VA) 4
Engine Synchronized motor
Setting time (s) 15
Length (㎜) 70
Pressure (㍴) 16
Differential pressure (closed) (㍴) < 6
Differential pressure (leakage free) (㍴) < 4
Connectors (㎜) 20 (¾″) internal thread
Liquid Chilled or hot water, 50 % glycol
Liquid temperature (℃) 2–90
Material Brass HPb59–1

Dimensions

Dimensions

Type Model DN (㎜)
3-way DQ320 20
C onnectors (″) Height (㎜) Length (㎜)
¾ 75 125

DQ220 (50650)/DQ225 (50654)

In general

The electrically operated ball valves of the series DQ220 are used for switching on/off the tap water
pipes of the heating and air conditioning systems. It consists of a pump casing and an electric servomotor. The servomotor activates the ball valve. It is equipped with alarm contacts, which holds ball valve in end position “wide open” or “completely closed.” The valve body is made of forged brass and nickel plated.

Technical data

Energy supply 230 V ±10 %, 50/60 Hz
Power consumption (VA) 4
Engine Synchronized motor
Setting time (s) 15
Length (㎜) 70
Pressure (㍴) 16
Differential pressure (closed) (㍴) < 6
Differential pressure (leakage free) (㍴) < 4
Connectors (㎜) 20 (¾″) internal thread
Liquid Chilled or hot water, 50 % glycol
Liquid temperature (℃) 2–90
Material Brass HPb59–1

Dimensions

Dimensions

Type Model DN (㎜)
2-way DQ220 DQ225 20

25
C onnectors (″)| Height (㎜)| Length (㎜)
¾| 64| 110
1| 70| 11

Electrical connection

Electrical connection

Assignment of connection cable

Ball valve open

Supply lines:

  • black = phase (230 V)
  • blue = neutral wire

Control line:

  • red = zero potential

Ball valve closed

Supply lines:

  • black = phase (230 V)
  • blue = neutral wire

Control line:

  • red = phase (230 V)

Connection description

For using the valve, the blue and the black supply lines must be connected to the mains voltage, here connect the black line/cable with the phase and the blue line/cable with the neutral wire. Ball valve position is determined via the red control line. If the supply line is connected to the mains voltage, the ball valve changes the position from closed to open, or in the case of the DQ320 valve, it changes the position from “AB-A” to “AB–B.”

Sectional representation

Sectional representation

Note:

  1. The actuator may only be installed horizontally.
  2. When installing do not tighten the screw so fast
  3. Use only exact threaded connectors.
  4. Check if the pipeline and the valve are clean before installing
  5. The valve and the pipeline can be installed in any direction between vertically and horizontally, but not with the actuator downwards.
  6. If the pipeline system is heat insulated make sure that the actuator is located outside of the insulation
  7. If damaged due to improper installation the warranty ceases to apply.

Troubleshooting

Problem Reason Solution
Reverse of “valve open” and “valve closed” Wrong cable connection Change

cable connections.
Actuator does not func- tion| Wrong connection of the control device (thermostat) or of the cable| Control device (thermostat) or cable must be checked.
Actuator contains water or engine dam- aged| Change actuator.
Pipe connection leaks| Threads do not match or screwing is incor- rect (threads damaged)| Change valve body.
Valve does not open and close completely| Valve is stuck, sized up, or water quality is poor| Clean pipeline, change valve body.

Disposal regulations

EU guidelines regarding the disposal of scrap electric appliances (WEEE, 2012/19/EU) were implemented in the law related to electrical and electronic equipment and appliances.

All WilTec electric devices that fall under the WEEE regulations are labelled with the crossed-out wheeled waste bin logo. This logo indicates that this electric equipment must not be disposed with the domestic waste.

The company WilTec Technik GmbH has been registered in the German registry EAR under the WEEE registration number DE45283704.

Disposal of used electrical and electronic appliances (intended for use in the countries of the European Union and other European countries with a separate collection system for these appliances).
The logo on the article or on its packaging points out that this article must not be treated as normal household waste but must be disposed to a recycling collection point for electronic and electrical waste equipment.
By contributing to the correct disposal of this article you protect the environment and the health of your fellow men. Environment and health are threatened by inappropriate disposal.
Disposal icon

Material recycling helps reduce the consumption of raw materials.
Additional information on recycling this article can be provided by your local community, municipal waste disposal facilities, or the store where you purchased the article.

Address:
WilTec Wildanger Technik GmbH
Königsbenden 12 / 28
D-52249 Eschweiler

Important notice:
The reprint or reproduction, even of excerpts, and any commercial use, even in part, of this instruction manual require the written permission of WilTec Wildanger Technik GmbH.

Customer Service

The information contained in this document may alter at any time without previous notice. It is prohibited to copy or spread any parts of this document in any way without prior written allowance. All rights reserved.

The WilTec Wildanger Technik GmbH cannot be held accountable for any possible mistakes in this operating manual, nor in the diagrams and figures shown.
Even though, the WilTec Wildanger Technik GmbH has undergone biggest possible efforts to ensure that the operating manual is complete, faultless, and up to date, mistakes cannot be entirely avoided.
If you should find a mistake or wish to make a suggestion for improvement, we look forward to hearing from you.

Send an e-mail to:
[email protected]
or use our contact form:
https://www.wiltec.de/contacts/
The most recent version of this manual in various languages can be found in our online shop via:
https://www.wiltec.de/docsearch

Our postal address is:
WilTec Wildanger Technik GmbH
Königsbenden 12
52249 Eschweiler
Germany

To return orders for exchange, repair, or other purposes, please use the following address. Attention!
To allow for a smooth execution of your complaint or return, it is important to contact our customer service team before returning the goods.

Returns Department
WilTec Wildanger Technik GmbH
Königsbenden 28
52249 Eschweiler

E-mail: [email protected]
Tel: +49 2403 55592–0
Fax: +49 2403 55592–15

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

XPOtool User Manuals

Related Manuals