B METERS iSMA-B-4I40-H Multiprotocol I/O Module Installation Guide
- September 3, 2024
- B METERS
Table of Contents
iSMA-B-4I40-H Multiprotocol I/O Module
“`html
Product Specifications:
- Power supply: Digital inputs
- Digital outputs: 4x relay output
- Interface: RS485 half-duplex, Modbus or BACnet
- Address: Set by switch in range from 0 to 99
- Baudrate: Set by switch in range from 4800 to 115200 bps
- Ingress protection rating: IP40 – for indoor installation
- Temperature: Refer to specification
- Relative humidity: Refer to specification
- Connectors: Refer to specification
Product Usage Instructions:
1. Power Supply:
Ensure the power supply matches the specified requirements in
the manual before connecting the device.
2. Digital Inputs and Outputs:
Connect the digital inputs and outputs as per the provided
guidelines in the manual.
3. Communication Interface:
Set the communication interface according to the desired
protocol (Modbus or BACnet) and configure the address and baudrate
accordingly.
4. Ingress Protection:
Install the device indoors in an IP40 rated environment to
ensure proper protection against dust and other particles.
5. Mounting:
Mount the device securely following the mounting instructions
provided in the manual to avoid any potential hazards.
6. Housing Material:
Ensure the device is housed in a suitable material as specified
in the manual for safe operation.
Frequently Asked Questions (FAQ):
Q: What should I do if I encounter difficulties during
installation?
A: If you face any challenges during installation or operation,
please contact the iSMA CONTROLLI Support Team at
support@ismacontrolli.com for assistance.
“`
iSMA-B-4I40-H Installation Instructions
Follow us on:
/bmetersuk
B METERS UK | www.bmetersuk.com | iSMA
iSMA-B-4I4O-H
Power supply Digital inputs
Digital outputs
Interface Address Baudrate Ingress protection rating Temperature Relative
humidity Connectors Dimension Mounting Housing material
SPECIFICATION
DC: 24 V ± 20%, 1.2 W; AC: 24 V ± 20%, 1.8 VA
4x dry contact input, high-speed pulse counter up to 100 Hz
4x relay output
Maximum ratings
UL compliant ratings
Resistive load max.
3 A @ 230 V AC 3 A @ 30 V DC
3 A @ 24 V AC 3 A @ 30 V DC
Inductive load max.
75 VA @ 230 V AC 30 W @ 30 V DC
8 VA @ 24 V AC 30 W @ 30 V DC
RS485 half-duplex, Modbus or BACnet, up to 128 devices on the bus
Set by switch in range from 0 to 99
Set by switch in range from 4800 to 115200 bps
IP40 – for indoor installation
Operating: -10°C to +50°C (14°F to 122°F) Storage: -40°C to +85°C (-40°F to 185°F) 5 to 95% RH (without condensation) Separable, max 2.5 mm2 (18 12 AWG) 37x110x62 mm (1.45×4.33×2.44 in) DIN rail mounting (DIN EN 50022 norm) Plastic, self-extinguishing PC/ABS
TOP PANEL
DIGITAL INPUTS Dry Contact
Connection of electrovalve
DIGITAL OUTPUTS Connection of resistive load
Connection of inductive load
COMMUNICATION
POWER SUPPLY
Follow us on:
/bmetersuk
B METERS UK | www.bmetersuk.com | iSMA
rd
WARNING
TERMINALS OF THE DEVICE
· Note, an incorrect wiring of this product can damage it and lead
to other hazards. Make sure the product has been correctly wired
before turning the power ON.
· Before wiring, or removing/mounting the product, be sure to turn
the power OFF. Failure to do so might cause electric shock.
· Do not touch electrically charged parts such as the power
terminals. Doing so might cause electric shock.
· Do not disassemble the product. Doing so might cause electric shock or faulty operation.
· Use the product within the operating ranges recommended in the
specification (temperature, humidity, voltage, shock, mounting
direction, atmosphere etc.). Failure to do so might cause fire or
faulty operation.
· Firmly tighten the wires to the terminal. Insufficient tightening of
the wires to the terminal might cause fire.
EN 60730-1 POWER SUPPLY CONSIDERATIONS
· Electrical safety in the building automation and control systems is essentially based on the use of extra low voltage which is strictly separated
from the mains voltage. This low voltage is either SELV or PELV according to EN 60730-1.
· Protection against electric shock is ensured by the following measures:
o limitation of voltage (low voltage AC/DC 24V supply, either SELV or PELV)
o protective-separation of the SELV-system from all circuits other than SELV and PELV
o simple-separation of the SELV-system from other SELV-systems, from PELV- systems and earth
· Field devices such as sensors, status contacts and actuators connected to the low-voltage inputs and outputs of I/O modules must comply with
the requirements for SELV or PELV. The interfaces of field devices and other systems must also satisfy SELV or PELV requirements.
· When the supply of SELV or PELV circuits is obtained from supply mains of higher voltages it shall be provided by safety transformer or a
converter designed for continuous operation to supply SELV or PELV circuits.
FCC COMPLIANCE NOTE
Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and
can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio
communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful
interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct
the interference by one or more of the following measures:
· Reorient or relocate the receiving antenna.
· Increase the separation between the equipment and receiver.
· Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
· Consult the dealer or an experienced radio/TV technician for help.
WIRING
· Line power cables must be routed with spatial separation from signal and data transmission cables.
· Analogue and digital signal cables should also be separated.
· It is recommended to use shielded cables for analogue signals, cable shields should not be interrupted by intermediate terminals.
· The shielding should be earthed directly after the cable enters the cabinet.
· It is recommended to install interference suppressors when switching inductive loads (e.g. coils of contactors, relays, solenoid valves). RC
snubbers or varistors are suitable for AC voltage and freewheeling diodes for DC voltage loads. The suppressing elements must be connected as
close to the coil as possible
Follow us on:
/bmetersuk
B METERS UK | www.bmetersuk.com | iSMA
rd
INSTALLATION GUIDELINE
Please read the instruction before use or operating the device. In case of any
questions after reading this document, please contact the iSMA CONTROLLI
Support Team (support@ismacontrolli.com).
· Before wiring or removing/mounting the product, make sure to turn the power
off. Failure to do so might cause an electric shock. · Improper wiring of the
product can damage it and lead to other hazards. Make sure that the product
has been correctly wired before turning the power on. · Do not touch
electrically charged parts such as power terminals. Doing so might cause an
electric shock. · Do not disassemble the product. Doing so might cause an
electric shock or faulty operation. · Use the product only within the
operating ranges recommended in the specification (temperature, humidity,
voltage, shock, mounting direction, atmosphere, etc.). Failure to do so might
cause a fire or faulty operation. · Firmly tighten the wires to the terminal.
Failure to do so might cause a fire. · Avoid installing the product in close
proximity to high-power electrical devices and cables, inductive loads, and
switching devices. Proximity of such objects may cause an uncontrolled
interference, resulting in an instable operation of the product. · Proper
arrangement of the power and signal cabling affects the operation of the
entire control system. Avoid laying the power and signal wiring in parallel
cable trays. It can cause interferences in monitored and control signals. · It
is recommended to power controllers/modules with AC/DC power suppliers. They
provide better and more stable insulation for devices compared to AC/AC
transformer systems, which transmit disturbances and transient phenomena like
surges and bursts to devices. They also isolate products from inductive
phenomena from other transformers and loads. · Power supply systems for the
product should be protected by external devices limiting overvoltage and
effects of lightning discharges. · Avoid powering the product and its
controlled/monitored devices, especially high power and inductive loads, from
a single power source. Powering devices from a single power source causes a
risk of introducing disturbances from the loads to the control devices. · If
an AC/AC transformer is used to supply control devices, it is strongly
recommended to use a maximum 100 VA Class 2 transformer to avoid unwanted
inductive effects, which are dangerous for devices. · Long monitoring and
control lines may cause loops in connection with the shared power supply,
causing disturbances in the operation of devices, including external
communication. It is recommended to use galvanic separators. · To protect
signal and communication lines against external electromagnetic interferences,
use properly grounded shielded cables and ferrite beads. · Switching the
digital output relays of large (exceeding specification) inductive loads can
cause interference pulses to the electronics installed inside the product.
Therefore, it is recommended to use external relays/contactors, etc. to switch
such loads. The use of controllers with triac outputs also limits similar
overvoltage phenomena. · Many cases of disturbances and overvoltage in control
systems are generated by switched, inductive loads supplied by alternating
mains voltage (AC 120/230 V). If they do not have appropriate built-in noise
reduction circuits, it is recommended to use external circuits such as
snubbers, varistors, or protection diodes to limit these effects.
Electrical installation of this product must be done in accordance with
national wiring codes and conform to local regulations.