GENERAL RS35 Elite Steam Residential Steam Humidifiers User Manual
- August 2, 2024
- GENERAL
Table of Contents
RS35 Elite Steam Residential Steam Humidifiers
“`html
Specifications:
-
Product: GENERAL RS35 Elite Steam Residential Steam
Humidifier -
Model: RS35
-
Warranty: 2 years on materials (excluding consumable
parts)
Product Usage Instructions:
1. How The Elite Steam Works:
The Elite Steam is an electrode humidifier that produces steam
for humidification by passing electric current through water in the
steam plastic generator cylinder between metal electrodes. The
steam output is directly proportional to the conductivity of the
water and the amount of electrode immersed in the water.
When humidity is needed, the Elite Steam controller will open
the water fill valve and allow water to enter the cylinder. The
water flow is regulated by a flow restrictor to prevent
overfilling. Water then flows through the fill tube into the bottom
of the steam cylinder. Any backflow or overflow of water is
directed to the drain.
As the water fills the cylinder, it reaches the electrodes, and
current begins to flow. The current is monitored by an amperage
transformer connected to the power wires. When the desired current
is reached, the fill valve closes, and the water begins to warm and
produce steam. If water levels rise too high or current levels
increase excessively, the system will drain some water to maintain
proper levels.
2. Maintenance:
Periodically, based on incoming water conductivity, the unit
will open the drain valve to reduce mineral concentration. A
strainer in the cylinder helps prevent mineral debris from clogging
the drain valve. If the Elite Steam remains powered but idle for
more than 72 hours, the cylinder will be emptied to avoid stagnant
water.
Frequently Asked Questions (FAQ):
Q: How often should I clean my Elite Steam humidifier?
A: It is recommended to clean your humidifier at least once a
month to ensure optimal performance and prevent mineral
buildup.
Q: Can I use distilled water in the humidifier?
A: Yes, you can use distilled water in the Elite Steam
humidifier to minimize mineral deposits and prolong the life of the
unit.
Q: What should I do if my Elite Steam does not produce
steam?
A: If your humidifier is not producing steam, check the water
levels, ensure proper electrical connections, and clean any mineral
deposits that may be obstructing the electrodes.
“`
This Owner’s Manual is provided and hosted by Appliance Factory Parts.
GENERAL RS35 Owner’s Manual
Shop genuine replacement parts for GENERAL RS35
Find Your GENERAL Humidifier Parts – Select From 70 Models ——– Manual
continues below ——–
Elite Steam Residential Steam Humidifiers
User manual
We wish to save you time and money! We can assure you that the thorough
reading of this manual will guarantee correct installation and safe use of the
product described
WARNINGS
BEFORE INSTALLING OR HANDLING THE HUMIDIFIER PLEASE CAREFULLY READ AND FOLLOW
THE INSTRUCTIONS AND SAFETY STANDARDS DESCRIBED IN THIS MANUAL AND ON THE
LABELS ATTACHED TO THE Elite Steam. CAUTION: ALWAYS DISCONNECT THE MAIN POWER
BEFORE OPENING OR SERVICING THE HUMIDIFIER! Elite Steam produces non-
pressurized steam by means of electrodes immersed in the water contained in
the plastic steam generator cylinder. Electric current passes through the
water between the electrodes, heating the water into steam, which is then used
to humidify the air. The quality of the water used affects the operation of
this unit, so the Elite Steam may be supplied with untreated water, as long as
this is drinkable and not softened or demineralized. The water converted into
steam is automatically replaced through an electric fill valve. Periodically,
based on the water quality, the unit will also drain some water to dilute the
build-up of minerals in the steam generator and thus extend its life. This
humidifier has been designed exclusively to directly humidify rooms or ducts,
using a distribution system. The installation, use and maintenance operations
must be carried out according to the instructions contained in this manual and
on the labels applied internally and externally. IMPORTANT: BEFORE beginning
installation:
· Check for shipping damage to cartons. Mark the shipping waybill accordingly.
· Open cartons and check for any hidden damage. Mark the shipping waybill
accordingly. · Check packing slip to ensure all items have been received.
Notify General Filters of any shortages or damaged parts. You must notify
General
Filters within 5 working days of any shortages. The conditions of the
environment and the power supply voltage must comply with the specified values
listed on the data label in the humidifier. All other uses and modifications
made to the humidifier that are not authorized by the manufacturer are
considered incorrect, and the manufacturer assumes no liability for the
consequences of any such unauthorized use. Please note that the humidifier
contains powered electrical devices and hot surfaces. All service and/or
maintenance operations must be performed by qualified personnel who are aware
of the necessary precautions and are capable of performing the operations
correctly. Disconnect the humidifier from the main power supply before
accessing any internal parts. The humidifier must be installed in accordance
with all local and national standards. The humidifier is made of metallic and
plastic parts. All parts must be disposed of according to the local and
national standards for waste disposal.
WARNING: Your humidifier requires water to operate. Do NOT mount it above
materials or machinery that could be damaged if a leak occurs. Carel assumes
no responsibility for consequential or inconsequential damage as a result of
any leaks.
Disposal of the parts of the humidifier: the humidifier is made up of metallic
and plastic parts. All parts must be disposed of according to the local
standards on waste disposal. Warranty on materials: 2 years (from the date of
production, excluding the consumable parts).
3
CONTENTS
1. How The El it e St eam Works . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . 7 2. Models. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . 8 3. Inst all at ion . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3. 1 Posit ioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . 9 3. 2 Mount ing . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . 10 3. 3 Pl umbing . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 3. 4 St eam
dist ribut ion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . 12 3. 5 Power wiring. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 3. 6 Cont
rol wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . 15 3. 7 Wiring Connect ions: . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 4. St art -Up .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . 17 4. 1 St art up Checklist . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
17 4. 2 The Elit e St eam Cont roller . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . 17 4. 3 St art ing Elit e St eam . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 4. 4 St art
ing wit h a new cyl inder . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . 18 5. Operat ing El it e St eam . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . 18 5. 1 Displaying Inf ormat
ion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. 18 5. 2 Changing The Maximum Product ion. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . 18 5. 3 Act ivat ing Manual Drain. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . 18 5. 4 Reset t ing t he hour count er.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 5. 5 E2
Humidist at . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . 19 5. 6 Alarms . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. 20 6. Trouble-Shoot ing . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . 21 7. Maint enance. . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . 22 7. 1 Periodic checks. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . 22 7. 2 Cylinder maint
enance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . 22 7. 3 Repl acement Part s . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . 23 8. Technical Specif icat ions. . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
5
1. How The Elit e St eam Works
Elite Steam is an electrode humidifier. It produces steam for humidification by passing electric current through the water in the steam plastic generator cylinder between metal electrodes. There are no heating elements. Steam output is directly proportional to the conductivity of the water, and the amount of electrode immersed in the water.
On a call for humidity, the Elite Steam controller will open the water fill valve (1) and allow water to
enter the cylinder. A flow restrictor (2) prevents the unit from filling too quickly or with too much
pressure. The water flows up the fill tube (3) and into the fill cup (7). Water then flows over the dam
in the fill cup (7), which creates a 1″ air gap to prevent backflow of contaminated water into the feed
lines, and through the fill tube (4) and into the bottom of the steam cylinder (11). Any backflow or
overflow of water travels through the overflow hose (5) to the drain.
10
As the water fills the cylinder, it will reach the electrodes (10) and current will begin to flow. As the
water continues to fill the cylinder, the current will increase, and this is monitored by an amperage
transformer connected to one of the power wires (9) and located on the electronic controller. When
the desired current is reached, the fill valve will close (1) and the water will then begin to warm and
produce steam. If the water reaches the cylinder full probes (8) prior to reaching the desired current
12
level, the fill valve (1) will be closed to prevent overflow and the drain valve (13) will be opened to
11
drain away some water so as to move the water apart from the cylinder’s top. If the current rises too
much as the water fills the cylinder, the drain valve (13) will be activated to drain away some water
and reduce the current flow to acceptable levels. Note that, any time the drain valve is activated, the
tempering valve (14) will be opened for tempering the hot drained water down to 140 °F / 60 °C in
accordance to local and national standards.
9
8
13
7
6 5 4 3
15 2 14 1
Fig. 1.a
Periodically, based on the incoming water conductivity, the unit will open the
drain valve (13) and drain some water to reduce the mineral concentration. A
strainer (12) in the cylinder helps to prevent mineral debris from jamming the
drain valve (13). In case Elite Steam remains powered but idle, i.e. without
producing steam, for more than 72 hours (3 days), the cylinder will be emptied
to not have stagnant water inside.
If there is no water in the cylinder, there will be no current flow and no
steam production. The electrodes do not burn out, but they will eventually
become completely coated with mineral and the cylinder will then need to be
replaced or cleaned.
2
No. Description
1 Steam generator cylinder
2 Room blower/manifold (optional)
3
3 User interface/display 4 On/Off, SET buttons
5 Fill & tempering valves
6 Fill & drain connections
1
7 Drain valve
4
Tab. 1.a
7
5
6
Fig. 1.b
7
2. Models
There are two basic models for steam distribution: Duct Injection
Direct Room Discharge
Fig. 2.a
Elite Steam comes in two capacities and voltages:
DS35 RS35 DS20A RS20A DS15 RS15
Duct Steam Injection, 35 gallons per day, (12 Lbs per hour), 220-240V. Room Steam Discharge, 35 gallons per day, (12 Lbs per hour), 220-240V. Duct Steam Injection, 20 gallons per day, (7 Lbs per hour), 220-240V. Room Steam Discharge, 20 gallons per day, (7 Lbs per hour), 220-240V. Duct Steam Injection, 15 gallons per day, (5.5 Lbs per hour), 115-120V. Room Steam Discharge, 15 gallons per day, (5.5 Lbs per hour), 115-120V.
Fig. 2.b
8
3. Installation
3. 1 Positioning
The Elite Steam has been designed for wall mounting and, since it is an
atmospheric steam humidifier, should be placed close to the point where the
steam will be used, to minimize the steam hose length (and the amount of
condensate). Certain clearances must be maintained around the unit for safety
and maintenance.
Duct Injection
A 6″ (150 mm) B 6″ (150 mm) C 6″ (150 mm) D 6″ (150 mm) E 24″ (600 mm) F max.
0.2°
Tab. 3.a
Direct Room Discharge
A 6″ (150 mm)
B 36″ (900 mm)
C 72″ (1800 mm)
D
D 24″ (600 mm)
Tab. 3.b
C
Fig. 3.a
Unit Dimensions: Duct and Room Units:
A B C Weight empty Weight packaged Weight installed with water
13.5″ (341 mm) 8.1″ (204 mm) 23.7″ (600 mm) 18 lbs (8 kg) 22 lbs (10 kg) 26
lbs (12 kg)
Tab. 3.c
Fig. 3.b
Fig. 3.c 9
3. 2 Mounting
3.2.1 Removing the front cover The front cover is secured by four screws
located at the four corners of the unit. Use a phillips head screwdriver to
remove the four cover screws. Then simply pull the front cover away from the
back part of the unit. Return it in reverse order.
Be careful not to over-tighten the screws.
Fig. 3.d
Fig. 3.e
3.2.2 Fastening to the wall Drill the wall according to the drilling template supplied; then secure Elite Steam firmly to the wall by the screws and anchors supplied.
Fig. 3.f 10
3. 3 Plumbing
3.3.1 Water supply The Elite Steam must be supplied with COLD potable water
(not softened or demineralized) having the following characteristics:
Instant flow rate: Connection: Temperature limits: Pressure limits: Hardness limits: Conductivity:
0.12 gpm / 0.45 L/min 1/4″ O.D. Compression 34 to 104°F / 1 to 40 °C 15 to 116
psi / 1 to 8 bar <= 400 ppm CaCO3 125 to 1250 µ S/cm (micromhos)
Tab. 3.d
Fig. 3.g
The water feed line should be 1/2″ copper, PVC or poly tubing run to within 3
feet of the humidifier, then bushed down to 1/4″ O.D. poly to make the final
connection to the 1/4″ O.D. compression fitting supplied with the unit.
WARNING: WE RECOMMEND TO USE A SOFT POLY HOSE TO ABSORB THE WATER HAMMERING IN
ORDER TO AVOID DAMAGE TO THE FILL VALVE. The water line may be routed through
the back or through the bottom of the unit. With poly tubing, an insert should
be used to support the tubing and prevent leaks. The fitting then threads onto
the fill valve inlet located on the bottom of the humidifier. Note that there
is a strainer built into the fill valve fitting underneath the unit, which
will require periodic cleaning, so be sure to allow clearance for access.
NOTE: softened water should NOT be used as it is generally corrosive to the
electrode plating.
3.3.2 Water drain The Elite Steam also requires connection to a drain. The
drain line may be routed out the back of the unit or the bottom of the unit
using the included angle fitting. The drain water characteristics are:
Drain rate per hour: Instant drain rate: Connection: Typical temperature:
0.7 gph / 2.6 L/h 1.3 gpm / 5 L/min 1-1/4″ / 33 mm nominal diameter 140°F / 60 °C
Fig. 3.h
The drain line can be 1-1/4″ schedule 40 PVC or CPVC, 1-1/4″ copper, or 1-1/4″
Polypropylene. In all cases, the drain tube is slipped over the drain outlet
on the bottom of the humidifier. It is not glued or otherwise attached to the
humidifier, so it must be supported by itself. If 1-1/4″ schedule 40 PVC or
CPVC is used, then a coupling should be used between the drain line and unit
drain. The Elite Steam includes a drain tempering valve that opens whenever
the drain valve opens and flushes cool feed water into the drain line to
insure that the drain water temperature never exceeds 140 °F / 60 °C.
NOTE: Drain line must be trapped under the unit to prevent flash steam from
condensing in the unit cabinet.
11
3. 4 Steam distribution
3.4.1 Duct steam injection The maximum allowed duct static pressure is 2 in
WC.
The Elite Steam duct injection models include a plastic duct injection nozzle:
A
1.24″ (31.5 mm)
B
1.96″ (50 mm)
C
2.20″ (56 mm)
D
2.26″ (57.5 mm)
E
3.93″ (100 mm)
F
0.31″ dia. (8 mm)
G
0.86″ dia. (22 mm)
H
1.18″ dia. (30 mm)
I 0.47 or 0.87″ (12 or 22 mm)
Or a stainless steel duct distributor:
Fig. 3.i
Fig. 3.l
To install the distributor pipes: 1. Cut a round hole in the side of the duct
to match the steam pipe and condensate return. 2. Apply silicone sealant to
the mounting plate and insert the pipe through the hole and secure it with 4
sheet metal screws. 3. Connect the steam and condensate hoses using the hose
clamps supplied. (Note: end support bracket supplied only with 36″ and longer
distributors.)
IMPORTANT: allow 2 feet of straight duct downstream of the distributor pipes
for evaporation of the steam. Always allow 2 feet upstream. Turbulent air flow
may require longer lengths.
3.4.2 Return Condensate Connection The return condensate from the distribution
manifold or the Thru-wall blower unit shall be returned through the knockout
on top of the humidifier and be inserted into the hole located on the top of
the fill cup. See Fig. 3.k
.
Fig. 3.k
12
3.4.3 Steam Hoses NINETY PERCENT (90%) OF ALL OPERATION PROBLEMS ARE CREATED
BY IMPROPER STEAM PIPING FROM THE HUMIDIFIER UNIT TO THE DUCT DISTRIBUTOR
PIPES. To avoid these problems, remember one simple fact when running the
steam hose: steam naturally flows up hill, and condensate naturally flows down
hill. Run the steam hose or piping to avoid any kinks, sharp elbows, or low
spots that could collect or restrict the flow of steam to the distributor
pipe, or the flow of condensate back to the humidifier. Support the hose
adequately to avoid sags. The following diagrams are to provide you with some
guidelines. If you have a situation you are unsure of, please contact the
factory for instructions.
Fig. 3.m IMPORTANT: Maximum length of rubber steam hose is 10 feet. Insulated
copper tubing may be up to 20 feet. In all cases, minimize sharp bends and
elbows use 2-45° elbows instead of 90°s. Hose size = 7/8″ (22 mm). Hose size
= 1-1/4″ (30 mm).
13
3. 5 Power wiring
Check that the power supply voltage to be connected matches the value
indicated on the rating plate inside the electrical panel.
Insert the power and ground connection cables into the electrical panel
compartment using the strain reliefs supplied, and connect to the terminals.
An external fused disconnect must be installed.
All wiring must be in accordance with local, state and national electric
codes.
NOTE: to avoid unwanted interference, the power cables should be kept separate
from any control wiring.
All wiring must be in accordance with local, state and national electric
codes.
Fig. 3.n
Power supply Steam Output Steam Output POWER CURRENT EXTERNAL POWER WIRES EXTERNAL FUSE (A)
Model Code (single phase) (lbs/hr)
(kg/h)
(kW)
(A)
DS15 110Vac 50/60Hz
5.5
2.5
1.86 16.88
AWG10
25
RS15 110Vac 50/60Hz
5.5
2.5
1.86 16.88
AWG10
25
DS20A 230Vac 50/60Hz
7
3.2
2.36 10.27
AWG12
20
RS20A 230Vac 50/60Hz
7
3.2
2.36 10.27
AWG12
20
DS35 230Vac 50/60Hz
12
5.4
4.05 17.61
AWG10
25
RS35 230Vac 50/60Hz
12
5.4
4.05 17.61
AWG10
25
NOTE: Tolerance allowed on main voltage = -15% to +10%
Connect power wires to the power terminal block located at the bottom left of the control module. .
Fig. 3.o Connect the wiring ground wire to the unit’s chassis ground, located
just behind the power wiring terminal block.
14
Fig.3.p
3. 6 Control wiring
Elite Steam allows connection of any simple or automatic humidistat, and
safety devices such as high-limit humidistat, air flow proving switch, and
remote on/off.
3.6.1 Select Signal Type REMARK: Select the proper type of control signal by the keyboard before connecting the control wiring.
Proceed as follows: 1. Switch Elite Steam off. 2. Keep pressed both buttons, “reset/sel” and “drain”, and switch Elite Steam back on until the display shows
00 and the spanner
blinks; then release the 2 buttons.
Keep pressed “reset/sel” until the display shows 02. WARNING: do NOT confirm any value higher than 04. In
case, press “reset/sel” until the display goes back to the normal operating mode and restart from step 1.
3. Press “drain” (min. 1 second) to confirm: the display shows “P1” for 1 second and then P1’s current value;
se t will be displayed beside.
4. By pressing “reset/sel” the value of P1 will loop between 0 and 1: 0 = humidistat; 1 = external 0-10 Vdc
modulating signal
5. Press “drain” (min. 1 second) when done to confirm the new value of P1 and exit to the normal operating
mode.
6. Switch Elite Steam off: you can now proceed with connecting the control wiring.
Fig. 3.q
Thread the control wiring through the bottom of the unit, and the strain relief (see photo at top of previous page), and then up the side of the control module to the top right wiring terminal blocks. Connect the control wiring to the control wiring terminal blocks found at the top right side of the control module.
3.6.2 Connect the E2 Humidistat for On/Off Operation: 1. Remove the humidistat from the base, squeeze the louvered base at the top and bottom.To remove the humidistat from the wall, lift up on the humidistat and pivot top away from wall 2. Before wall mounting, please remove the gasket. 3. Before return air duct mounting, please remove the breakout piece. 4. If return air duct mounting, route wires between humidistat and base 5. Mount the sensor outside the house. Do not mount on South side of the house or in direct sunlight. Place at least 4 feet away from any exhaust vent. If in air intake, place 1 foot or closer to outside wall. Place at least 6″ higher than possible snow. Do not route sensor wire near high voltage wires. 6. Connect the GND-IN terminals on the humidifier to the HUM terminals on the E2 Humidistat. Connect the GND-24V terminals to the ACL-CAN terminals on the E2 humidistat.
Fig. 3.r
15
3.6.3 Modulating Operation: Connect an external 0-10 Vdc modulating input
between terminals IN-GND. Connect any Safety Switches (high-limit, air flow
switch, remote on/off) in series to terminals AB-AB. If no safety switches are
used, then a jumper must be installed between AB-AB. DO NOT apply any voltage
to AB-AB.
3.6.4 Safety and High Limit Switches Remove the jumper between terminals AB-AB
and connect any simple high-limits, air flow switch, and remote contacts in
series to terminals AB-AB; otherwise, if no such dry contacts are available,
the jumper must remain in place between terminals AB-AB. DO NOT apply any
voltage to AB-AB.
3. 7 Wiring Connections:
Terminals N1-GND-N2 AB-AB IN-GND NC-C-NO NO-C 24-GND
Input/Output Type NTC 24 V Bridge 24 V Bridge Dry contact Dry contact 24 VAC
Description NTC air proving sensor Remote On/Off, Safety Switches Humidistat Alarm relay External fan relay Power for external humidistat
3.7.1 Wiring diagram of controller
Fig. 3.s 16
4. Start-Up
IMPORTANT WARNINGS: 1. Before starting, check that the humidifier is in
perfect condition, that there are no water leaks and that the electrical parts
are dry; 2. Do not connect power if the humidifier is damaged or even
partially wet!
When installation is completed, flush the supply pipe for around 10 minutes by
piping water directly into the drain, without sending it into the humidifier;
this will eliminate any scale or residues that may cause foam when boiling.
4. 1 Startup Checklist
Before starting the humidifier, the following should be checked:
Water is connected, the line has been flushed, and external valves are open.
Drain is connected, run to an open drain, and has a trap under the unit.
Electricity is connected in accordance with instructions, local codes and data
labels in the unit. The power fuses are installed and intact. All control
wiring is done and tested. Airflow switch is wired to open on air flow loss.
Hi-limit humidistat is wired to open on humidity rise above set point. Unit
wires have been checked to make sure they and all connectors are tight from
shipping. The steam hose(s) are run correctly with no sags or kinks and sloped
properly according to the manual. Condensate hoses are run correctly with no
sags or kinks and sloped properly according to the manual.
4. 2 The Elite Steam Controller
The Elite Steam controller features a comprehensive information display that
shows the operation of the system at a glance:
Display is % of nominal capacity
Maintenance required
Display is amperage (default)
Steam is being produced
Cylinder filling
Foaming
Cylinder full
1
2
3
14
4
5
Cylinder draining
6
LEDs indicate: power (yellow), operation (green) and alarms (red)
7
10. Drain button for manual draining of cylinder and confirming parameter values
13
8
11. ON/OFF button
12. Reset button to reset alarms and access parameters
13. Level of output: 33%, 66%, 100%
9
14. Fan relay is activated
12
10
11
Fig. 4.a 17
4. 3 Starting Elite Steam
· Insure that the external power is turned on. · Push the top part of the
On/Off button so that the I part is in. The yellow Power LED will be lit. The
Elite Steam is now ready to operate. · When there is a call for humidity,
Elite Steam will close its power relays and send power to the electrodes in
the plastic steam generator. The green
Operation LED will light, indicating that operation has begun.
4. 4 Starting with a new cylinder
When starting with a new cylinder, you should activate the cylinder cleaning
function as follows: 1. Switch Elite Steam off.
2. Keep pressed both buttons, “reset/sel” and “drain”, and switch Elite Steam back on until the display shows 00 and the spanner
blinks; then release the
two buttons.
3. Keep pressed “reset/sel” until the display shows 04.
WARNING: do NOT confirm any value higher than 04. In case, press “reset/sel” until the display goes back to the normal operating mode and restart from step
4. Press “drain” (min. 1 second): the cleaning starts.
During the cleaning, the electrodes are powered and water is filled in until it touches the high-level sensor OR the phase current equals 20 A, whichever occurs first. After either of the events is detected, the boiler is fully discharged with the electrodes un-powered (the drain valve and the drain tempering valve are activated for 3 minutes). Warming the filling water helps washing out any mould release or dirt.
When starting the unit with a new or empty cylinder, it may take a significant amount of time (hours) for the unit to build up enough mineral concentration to reach rated capacity. This time can be shortened by the addition of Alka- Seltzer or salt (teaspoon) through the steam outlet on top of the cylinder.
5. Operating Elit e St eam
5. 1 3. 1 Displaying Information
By pressing the “reset/sel” button for 2 seconds, the display will loop from
amperage to production in % of the maximum production to the hour counter and
back to amperage:
%
A
A
1. Amperage: it is the value of the current that flows through the water
making it boiling off (default display) 2. Production %: it is the current
production expressed as a percentage of the nominal production 3. Hour
counter: it is expressed in tens; for instance, when the display shows 13 the
real hour value will be between 130 and 139 hours. Note that the hour
counter increment rate is proportional to the steam flow: e.g., in case the
steam flow is 40% of the nominal value, the hour counter increment rate will
be 40% and after 100 hours of production the hour counter will show 4 which
stands for 40 hours.
5. 2 Changing The Maximum Production
The maximum production can be adjusted between 20% to 100% of the nominal
production in steps of 5% in order to suit the environment characteristics:
1. Switch Elite Steam off.
2. Keep pressed both buttons “reset/sel” and “drain” and switch Elite Steam back on: the display shows 00 and the spanner
blinks; then release the two
buttons.
3. Keep pressed “reset/sel” until the display shows 01. WARNING: do NOT confirm any value higher than 04. In case, press “reset/sel” until the display goes
back to the normal operating mode and restart from step 1.
4. Press “drain” (min. 1 second) to confirm: the display shows “P0” for 1 second and then P0’s current value; se t will be displayed beside.
5. By pressing “reset/sel” the value of P0 will loop from 20% to 100% in steps of 5%
6. Press “drain” (min. 1 second) when done to confirm the new value of P0 and exit to the normal operating mode.
5. 3 Activating Manual Drain
Press and hold the “drain” button on the front of the unit until the cylinder
is drained.
5. 4 Resetting the hour counter
The hour counter should be reset every time the cylinder is changed in order
to reset and restart the ineternal maintenance timer:
1. Switch Elite Steam off.
18
2. Keep pressed both buttons “reset/sel” and “drain” and switch Elite Steam back on: the display shows 00 and the spanner
blinks; then release the two
buttons.
3. Keep pressed “reset/sel” until the display shows 03. WARNING: do NOT confirm any value higher than 04. In case, press “reset/sel” until the display goes
back to the normal operating mode and restart from step 1.
4. Press “drain” (min. 1 second) to confirm: the hour counter will be reset at once and Elite Steam will go back to the normal operating mode.
5. 5 Using the E2 Humidistat
Press to select OFF, MANUAL or AUTO mode (if outdoor sensor is connected). OFF mode: The humidifier is turned off.
MANUAL mode: The E2 will work to maintain the single humidity selected. You can set your desired humidity level by pressing or
. The humidifier will turn ON or OFF according to your manual setting. (The humidifier will operate when the measured relative
humidity falls more than 2% below the set point.) Humidity will have to be lowered when weather is colder or if condensation is
suspected.
Suggested Setting Outdoor Temperatures
15%
-20°F -29°C
20%
-10°F -23°C
25%
0°F -18°C
30%
+10°F -12°C
35%
+20°F – 7°C
40%
+30°F – 1°C
AUTO mode: The E2 will automatically raise the humidity as the outdoor
temperature increases. This provides the highest possible humidity. The E2
will automatically lower the humidity as temperatures drop. This minimizes the
risk of condensation on cold surfaces like windows. You can adjust the Auto
Humidity Index Set Point from 0 (low) to 10 (high) by pressing or . The
Humidity Index is based on the outdoor temperature and indoor humidity. The
humidifier will switch ON/OFF according to the calculated auto humidity index
set point. Lower Index settings are for older homes with less insulation and
vapor barriers. Higher Index settings are for newer homes with complete vapor
barriers, triple pane windows and high R-value insulation. If condensation
occurs reduce Index setting by 2 points until condensation stops.
NOTE If the outdoor temperature sensor fails, flashes and the unit will
default to MANUAL mode.
· To toggle between indoor / outdoor temperature and indoor humidity: Press .
· To change the temperature unit: Press °C / °F.
· To set the temperature / humidity offset in MANUAL or AUTO mode:
1. Simultaneously press and when viewing the temperature or humidity reading.
2. Use or to change the setting (-3 to 3).
3. Press and simultaneously or wait 5 seconds to confirm and move onto the next setting.
· Lo or Hi will flash on the display when:
MEASURE LO
HI
MENT
Indoor temp.
Below 0oC (32oF)
Above 99oF(37oC)
Outdoor temp.
Below 40oC (40oF)
Above 50oC (122oF)
Humidity
Below
Above
10%
90%
· If power is lost, current settings are retained.
WARNING:
Do not allow excess humidification. Excess humidity can cause condensation and enable mold and mildew growth.
19
5. 6 Alarms
In the event of an alarm, the red alarm LED will flash, the alarm relay will
close, and the alarm code will flash in the display. Multiple alarms will
flash in sequence, alternating with the main display. Pressing the sel button
for 2 seconds will reset the alarms, although still active alarms will
continue to display.
Display E0 E1
E2
E3
E4
E5 E6 E7 E8 E9
Description Control board configuration not valid High current alarm
Low production, low supply water conductivity or excessive foam/limescale in
the cylinder Cylinder lifetime expired (1200 hours)
Fill alarm, unable or slow fill (current does not increase within timeout)
Drain alarm, unable to drain (current does not decrease within timeout)
Cylinder exhausted (critical performance detected) Foam detected
Cylinder lifetime expired (2000 hours) High controller temperature (above 176
°F / 80 °C)
Unit disabled Unit disabled
Action
Unit disabled. Press “reset/sel” key for 1 seconds to reset.
Press “reset/sel” key for 1 seconds to reset. The warning will be displayed 50
hrs later until the hour counter is reset and the cylinder replaced. Press
“reset/sel” key for 1 seconds to reset, otherwise the warning will be reset
automatically every 10 minutes until the supply water is available again.
Press “reset/sel” key for 1 seconds to reset
The warning is automatically reset if Elite Steam can produce the demand,
otherwise turn off and then on. Press “reset/sel” key for 1 seconds to reset
Reset the hour counter (read chap. Resetting the hour counter”) The warning is
automatically reset if the temperature decreases below 176 °F / 80 °C.
Notes Turn off, check control board, reprogram Turn off, check connections,
check cylinder (no limescale bridges between electrodes, no electrodes short-
circuited) Check supply water conductivity (too low?), replace the cylinder.
Change cylinder (not urgent)
Check water supply and fill valve; check drain valve for leakage
Check drain valve and drain connection
Change cylinder (urgent)
If it continues, do some cleaning cycles (read chap. “Starting with a new
cylinder”) Change the cylinder. Check the ambient temperature, replace the
controller.
20
6. Trouble-Shooting
problem The humidifier does not turn on
causes
1. no electrical power 2. on/off switch of the humidifier in position 0
(open) 3. control connectors improperly connected 4. blown fuses 5.
transformer failure
solutions
1. check the safety devices upstream from the humidifier and the presence of
power 2. close the switch on the panel: position I 3. check that the
connectors are properly inserted in the terminal block 4. check the condition
of fuses 5. check that the proper voltage is connected and turned on
The humidifier does not start operation
1. remote ON/OFF contact open 2. the humidistat has not been connected correctly 3. humidistat failure 4. control signal not compatible with the type set 5. value measured by the sensor/s higher than the corresponding set point
1. close ON/OFF contacts 2. check the external connection 3. replace the humidistat
The humidifier fills with water without producing steam
The humidifier wets the duct
1. high steam back pressure 2. fill valve strainer clogged 3. mineral in the
fill cup 4. drain solenoid valve leaking
1. the distributor is not installed correctly (too near the top of the duct
or the condensate return is blocked) 2.system over-sized 3.humidifier active
when the fan in the duct is off
1. check that the steam hose is not kinked or sagging, trapping condensate 2.
clean the fill valve strainer 3. clean the fill cup 4. check for voltage at
the drain solenoid valve and/or drain solenoid replacement
1. check that the steam distributor is installed correctly 2. decrease the
steam production set on the control 3. check the connection of the device
(flow switch or differential pressure switch) slaving the humidifier to the
ventilation in the duct
The humidifier wets the floor below
1. the humidifier drain is blocked 2. the supply water or overflow circuit has leaks 3. the condensate drain pipe does not bring the water back to the drain pan 4. the steam hose is not properly fastened to the cylinder
1. clean the drain assembly and pan 2. check the entire water circuit 3. check the correct position of the condensate drain hose in the drain pan 4. check the fastening of the hose clamps on the steam outlet
problem
causes
solutions
Water in the cylinder turns black
1. minerals in the cylinder have overconcentrated and 1. Check for sags & kinks that could trap condensate in the steam
are deteriorating the electrodes.
hoses that could cause a back pressure on the cylinder.
2. Check the duct static pressure.
3. Check the fill valve and inlet strainer.
4. Check the drain valve operation.
5. Correct installation problems and replace cylinder.
Heavy arcing occurs within hours of startup 1. The feed water contains large amounts of Iron, 1. Contact the factory for an optional drain timer to force additional
Copper or other conductive contaminants.
drains to control the minerals.
2. If you are using a softener, check the salt being used. If it contains
any additives, discontinue use, flush all lines and convert to pure salt
or unsoftened water.
3. Check the electrodes in the cylinder to be sure they were not
damaged in shipping.
Humidifier continuously fills and drains without 1. Mineral has bridged between the electrodes.
1. Clean or replace the cylinder.
producing steam
2. There is back pressure from the steam hoses or duct. 2. Check the steam hoses for kinks or gullies that might be trapping
3. The flow regulator in the fill valve is broken or out condensate.
of place.
3. Replace the fill valve.
4. Water conductivity is very high.
4. Consider using a mix of demineralized water with raw water.
5. Water is foaming excessively.
5. Check cylinder – replace if exhausted. If feed water contains silica
or nitrates, install a 1 micron water filter.
21
7. Maintenance
7. 1 Periodic checks
· After one hour of operation: Check that there are no significant water
leaks. · Every fifteen days or no more than 300 operating hours: Check
operation, that there are no significant water leaks and the general condition
of the
cylinder. Check that during operation there is no arcing between the
electrodes. · Every three months or no more than 1000 operating hours: Check
operation, that there are no significant water leaks and, if necessary,
replace the
cylinder. Check that there are no blackened parts of the cylinder. If there
are blackened parts of the cylinder, check the condition of the electrodes,
and if necessary replace the cylinder. · Annually or no more than 2500
operating hours: Replace the cylinder.
CAUTION: ALWAYS DISCONNECT THE MAIN POWER BEFORE DOING MAINTENANCE! CAUTION:
always disconnect the main power before touching the cylinder in the event of
leaks, as current may flow through the water.
7. 2 Cylinder maintenance
The life of the cylinder depends on a number of factors, including: the amount
and type of mineral in the water, the correct use and sizing of the
humidifier, and the output, as well as careful and regular maintenance.
IMPORTANT WARNINGS The humidifier and its cylinder contain live electrical
components and hot surfaces, and therefore all service and/or maintenance
operations must be performed by expert and qualified personnel, who are aware
of the necessary precautions. Before performing any operations on the
cylinder, check that the humidifier is disconnected from the power supply.
Remove the cylinder from the humidifier only after having drained it
completely using the manual “drain” button or procedure. Check that the model
and the power supply voltage of the new cylinder correspond to the data on the
rating label.
7.2.1 Replacing the cylinder IMPORTANT WARNING: the cylinder may be hot. Allow
it to cool before touching it or use protective gloves.
To replace the cylinder: · completely drain the cylinder by pressing and
holding the “drain” button until the cylinder is empty; · turn the humidifier
off and disconnect the main power; · remove the cover; · duct version:
o remove the steam hose from the cylinder; o flip up the cylinder holding
bracket and lift the cylinder out of the unit; · room version: o undo the 2
bolts of the embedded fan; o flip up the cylinder holding bracket; o
disconnect the distributor from the cylinder and lift the cylinder out of the
unit; · disconnect the electrical connections from the top of the cylinder; ·
install the new cylinder in the humidifier by performing the previous
operations in reverse.
WARNING: Electrical connections to the cylinder must be tight or possible fire
hazard may result. Threaded nuts on power wires must be connected with 22 to
29 inch-pounds of torque (2.5 to 3.3 Nm).
Fig. 7.a
7.2.2 Maintenance of the other plumbing components
IMPORTANT WARNINGS: · External power must always be disconnected when
performing any maintenance on the humidifier. · When cleaning the plastic
components do not use detergents or solvents; · Scale can be removed using a
solution of Lime-A-Way ®, CLR®, or 5% phosphoric acid, then rinse with water.
Cleaning the fill valve: After having disconnected the cables and the hoses,
remove the valve and check the condition of the inlet filter; clean if
necessary using the same cleaning solution as for the steam cylinder and a
soft brush. Cleaning the drain valve: Remove the valve body, clean if
necessary using the same cleaning solution as for the steam cylinder and a
soft brush. Cleaning the drain pan: Clean the pan of any mineral deposits and
check that the water flows freely from the pan to the drain at the drain
valve. Cleaning the supply, fill, overflow pipes: Check that these are clear
and clean or replace if necessary. IMPORTANT WARNING: after having replaced or
checked the plumbing, check that components have been reconnected correctly
with the proper seals. Re-start the humidifier and perform a number of
cleaning cycles (from 2 to 4, read chap. “Starting with a new cylinder”), then
check for any water leaks.
22
7. 3 Replacement Parts
Item
Part No.
Description
1 See the table below Steam generator cylinder
2
7532
15-1 Control module 110 VAC 1-phase
7533
35-1 Control module 230 VAC 1-phase
7549
35-17 Internal cables kit
3
7551
35-18 On/off switch
4
7534
15-2 Room blower assembly 110 VAC 1-phase
7535
35-2 Room blower assembly 230 VAC 1-phase
5
7544
35-19 Blower filter
6
7536
35-20 Internal steam distributor for room blower
7
7537
15-3 Fill/tempering valve 110 VAC 1-phase
7538
35-3 Fill/tempering valve 230 VAC 1-phase
8
7539
15-4 Drain valve 110 VAC 1-phase
7541
35-4 Drain valve 230 VAC 1-phase
9
7442
35-21Ninety-degree drain adapter
7548
35-22 Fill cup
7546
35-23 Internal hoses kit for room versions
7547
35-24 Internal hoses kit for duct versions
7553
35-25 Cover holding screws
Fig. 7.b
Cylinders (item 1)
7523
7508A 7524 7543
Rated steam flow
5.5 lbs/h 7 lbs/h 12 lbs/h 12 lbs/h
2.5 kg/h 3.2 kg/h 5.4 kg/h 5.4 kg/h
Vac 1-phase
110 230 230 230
7552
35-16 Internal filter and gasket valid for all cylinders
Supply water conductivity (µS/cm)
Low and Normal Normal Normal Low
125-1250 350-1250 350-1250 125-350
Description
15-14 Steam Cylinder 20-14A Steam Cylinder 35-14 Steam Cylinder 35-15 Steam
Cylinder Low Conductivity
23
8. Technical Specifications
Steam flows, VAC, kW
Steam pressure Dimensions (mm ) Weight empty/packaged/installed with water IP
class Electrode power cables Power relays Ground connection Input water type
Conductivity range Water fill connection Water fill – instant flow Drain
connection Drain water temp Drain flow Embedded fan flow
5.5 lbs/hr (2.5 kg/h): 110 VAC 1-phase 50-60 Hz, 1.86 kW 7 lbs/hr (3.2 kg/h):
230 VAC 1-phase 50-60 Hz, 2.36 kW 12 lbs/hr (5.4 kg/h): 230 VAC 1-phase 50-60
Hz, 4.05 kW
39.37 in WC / 980 Pa
24″ x 14″ x 8″ (600 x 341 x 204 mm)
18/22/26 lbs. (8/10/12 kg)
IP20
14 AWG
2 x 30 Amp
Faston
Potable water
125-1250 µS/cm
1/4″ O.D. Compression
0.09 0.12 gpm (0.35 0.45 l/min)
33 mm O.D.
< 140°F (< 60°C) Max 1.3 gpm (max 5 l/min) 71 cfm (120 m³/hr)
Notes For duct only (Height x Width x Depth)
on board no demin. or softened water Special cylinders for cond. < 350 Adapter
to ¾” FPS
Adjustable from horizontal to vertical. May be from back or bottom of unit.
drain tempering device
Direct Room Discharge Only
Limited Warranty
DS, RS and CS Humidifiers, if properly registered by the return of the
attached warranty registration to General Filters, Inc., are warranted to the
consumer against defects in materials and workmanship for a period of two
years from the date of installation, so long as the product has been installed
and operated in accordance with all appropriate manuals and wiring diagrams.
Replacement or routinely replaceable parts such as steam cylinders and
gaskets, are not covered by this limited warranty or any other warranties. Any
other defective parts will be repaired without charge except for removal,
reinstallation and transportation costs. To obtain repair service under this
limited warranty, the consumer must send the defective part to General
Filters, Inc.
THERE ARE NOT EXPRESS WARRANTIES COVERING THIS HUMIDIFIER OTHER THAN AS SET
FORTH ABOVE. THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A
PARTICULAR PURPOSE ARE LIMITED IN DURATION TO TWO YEARS. THE MANUFACTURER
ASSUMES NO LIABILITY IN CONNECTION WITH THE INSTALLATION OR USE OF THIS
PRODUCT, EXCEPT AS STATED IN THE LIMITED WARRANTY. THE MANUFACTURER WILL IN NO
EVENT BE LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES.
This limited warranty gives you specific legal rights, and you may also have
other rights which vary from state to state. Some states do not allow either
limitations on implied warranties, or exclusions from incidental or
consequential damages, so the above exclusion and limitation may not apply to
you.
Any questions pertaining to this limited warranty should be addressed to
General Filters, Inc. General Filters, Inc. has elected not to make available
the informal dispute settlement mechanism which is specified in the Magnuson-
Moss Warranty Act.