LG DHA4012DL Dehumidifier Instruction Manual

July 27, 2024
LG

LG DHA4012DL Dehumidifier

PREFACE
This Service Manual provides various service information, containing the mechanical and electrical parts etc. This dehumidifier was manufactured and assembled under the strict quality control system.
The refrigerant is charged at the factory. Be sure to read the safety precaution prior to servicing the unit.

SAFETY PRECAUTIONS

  • Disconnect power supply before servicing or replacing any electrical or non-electrical component.
  • Do not cut off the grounding prong or alter the plug in any manner at any circumstances.

FEATURES

  • Quiet
  • High efficiency
  • Adjustable humidistat
  • Automatic defrost
  • Automatic shut-off
  • Bucket-full indicator light
  • Easy roll casters
  • Removable & large capacity bucket.
  • Washable air filter
  • 2 fan speeds
  • Drain hose connection.

DIMENSIONS (mm/in)

SPECIFICATIONS

MODELS

ITEMS

| DH3010B (DHA3012D)| DH4010B (DHA4012D)| *DH5010B (DHA5012D)**
---|---|---|---
CAPACITY (Pint/Day)| 30| 40| 50
POWER SUPPLY (Phase, V, Hz)| 1ø, 115V, 60Hz
REFRIGERANT| R134a| R22
REFRIGERANT CHARGE, oz(g)| 4.76(135)| 5.11(145)| 7.05(200)
CONTROL, DEFROST| OPEN : 32°F(0°C + 2 )

– 3

CLOSE : 52.6°F(13°C + 3 )

– 3

| ****

| OPEN : 32°F(0°C + 2 )

– 3

CLOSE : 53.6°F(13°C + 3 )

– 3

THERMOSTAT| OPEN : 28.4°F(-2°C ±2)

CLOSE : 55.4°F(13°C ±2)

| OPEN : 26.6°F(-3°C ±2)

CLOSE : 55.4°F(13°C ±2)

| OPEN : 28.4°F(-2°C ±2)

CLOSE : 55.4°F(13°C ±2)

HUMIDISTAT| CONTROL RANGE : 20% ~ 80% RH

NORMAL SETTING : 42 ± 5% RH

COMPRESSOR MODEL NO.| LX86HACG| QA075CH| QA082CH



P.T.C. ASSEMBLY

| TYPE| P220MC| ****


TIME| WORKING TIME: 0.2 ~ 0.7 sec.

RETURN TIME: 60 sec.


MAXIMUM

| AMPERE| 7A
VOLTAGE| 300V


PROTECTOR

| •  OVERLOAD PROTECTOR FOR COMPRESSOR
•  INTERNAL PROTECTOR(FUSE) FOR MOTOR
CAPACITOR| –| 25µF, 270VAC
SWITCH, ROTARY| 6A/125VAC, 12A/250VAC
MOTOR ASSEMBLY, SINGLE| Shaded pole motor, 65W/1A↓, Thermal cutoff : 266°F/130°C
SWITCH ASSEMBLY, MICRO| 16A/125VAC, 8A/250VAC
OUTSIDE DIMENSIONS

W x H x D, mm(in)

| WITHOUT BUCKET| 320 x 530 x 340 (12 9/16 x 20 13/16 x 13 3/8)
WITH BUCKET| 320 x 530 x 445 (12 9/16 x 20 13/16 x 17 1/2)
NET WEIGHT, kg(lbs)| 21.5(47)| 17.2(38)| 17.7(39)

NOTE Specifications are subject to minor change without notice for further improvement.

CONTROL

HOW TO OPERATE DEHUMIDIFIER

HOW DOES THE DEHUMIDIFIER WORK?
Moist, humid air is drawn over a cold refrigerated dehumidifying coil. Moisture in the air condenses on this coil and drains into a bucket (or through the bucket into a hose and drain).
Dry, clean air is drawn over the condenser where it is actually heated several degrees and discharged out the front grille into the room.
It is normal for the surrounding air to become slightly warmer as the dehumidifier operates.
This warming effect further reduces the relative humidity of the surrounding air.

LOCATION FOR THE DEHUMIDIFIER
Allow at least 12 inches of space on all sides of the unit for good air circulation.

  • The dehumidifier must be operated in an enclosed area to be most effective.
  • Close all doors, windows and other outside openings to the room.

Place the dehumidifier in a location that does not restrict air flow into the rear coil or out the front grille.
A dehumidifier operating in a basement will have little or no effect in drying an adjacent enclosed storage area, such as a closet, unless there is adequate circulation of air in and out of the area.

MICRO SWITCH
The micro switch assembly, which is located on the barrier of inside unit, automatically shuts off the dehumidifier when the bucket is full (note, the Auto Shut Off lights, to indicate bucket must be emptied). The bucket replaces in its place, the unit again turns itself on.

AUTO DEFROST
When frost builds up on the cooling coils, the compressor will cycle off until the frost disappears. The fan continues to run.
NOTE: This unit is designed to be operated at temperatures above 65°F(18°C). If the dehumidifier is operated in low temperature conditions, the temperature and humidity conditions of room are low, some frost can be formed in its evaporator coil and the unit will be operated ON/OFF repeatedly. In this case, please check on your room temperature condition and stop the unit.

HUMIDISTAT
Humidistat controls constant relative humidity in the room automatically.
When the relative humidity in the room increases to the selected level, the dehumidifier starts automatically. And the relative humidity drops to the selected level, the dehumidifier stops automatically.
When the first using the dehumidifier, it is recommended, for the first three or four days, to operate the unit with the humidistat control set to MAX. At this setting, the unit will run continuously.
When the sweating has stopped and the dampness odors have gone, it is preferable to select the humidistat position that will best suit local conditions.
The relative humidity range it can control is from 20 % to 80%. (See Figure 3)

NOTE : The relative humidity at the number is the approximate value.

DRIER (For some models)
Dryer is used to prevent capillary blockage from moisture in the refrigerant system and H/E, condenser and evaporator. Also, dryer is used to remove corrosion of the components.
NOTE : When dryer is replaced, proper injection to capillary is needed. On opening the dryer, it should be welded instantly. The oxidization of dryer inside and all tubes inside after welding can be prevented.

CIRCUIT DIAGRAM

MODEL : DH3010B/DHA3012DL

LOCATION NO.| ****

DESCRIPTION

| PART NO.| Q’TY PER SET| RE- MARKS
---|---|---|---|---
DH3010B
1| POWER CORD ASSEMBLY| 6411A20001Q| 1| S, A
2| SWITCH, ROTARY| 6600A20001A| 1| S
3| MOTOR ASSEMBLY, SINGLE| 4681A20040A| 1| S
4| P.T.C. ASSEMBLY| 6748C-0003A| 1| S
5| COMPRESSOR| 2521C-A8605| 1| S
6| O.L.P.| 6750C-0002S| 1| S
7| LAMP, NEON| 6912A30001F| 1| S
8| CONTROL, DEFROST| 6614A30001H| 1| S
9| HUMIDISTAT| 5216A20001A| 1| S, A
10| SWITCH ASSEMBLY, MICRO| 6600A30003C| 1| S
11| TERMINAL BLOCK| 6640A40001A| 1| S

MODEL : DH4010B/DHA4012DL, DH5010B/DHA5012DL(DEFROST CONTROL TYPE)

LOCATION NO.| ****

DESCRIPTION

| PART NO.| Q’TY PER SET| RE- MARKS
---|---|---|---|---
DH4010B| DH5010B
1| POWER CORD ASSEMBLY| 6411A20001Q| 1| S, A
2| SWITCH, ROTARY| 6600A20001A| 1| S
3| MOTOR ASSEMBLY SINGLE| 4681A20040A| 1| S
4| CAPACITOR| 0CZZA20001Q| 1| S
5| COMPRESSOR (ROTARY)| 2520UABC2FA| 5416AR2179J| 1| S
6| O.L.P.| 6750U-L039A| 1| S
7| LAMP, NEON| 6912A30001F| 1| S
8| CONTROL, DEFROST| –| 6614A30001F| 1| S
9| HUMIDISTAT| 5216A20001A| 1| S, A
10| SWITCH ASSEMBLY, MICRO| 6600A30003C| 1| S

MODEL : DH4010B/DHA4012DL, DH5010B/DHA5012DL(THERMOSTAT CONTROL TYPE)

LOCATION NO.| ****

DESCRIPTION

| PART NO.| Q’TY PER SET| RE- MARKS
---|---|---|---|---
DH4010B| DH5010B
1| POWER CORD ASSEMBLY| 6411A20001Q| 1| S, A
2| SWITCH, ROTARY| 6600A20001A| 1| S
3| MOTOR ASSEMBLY SINGLE| 4681A20040A| 1| S
4| CAPACITOR| 0CZZA20001Q| 1| S
5| COMPRESSOR (ROTARY)| 2520UABC2FA| 5416AR2179J| 1| S
6| O.L.P.| 6750U-L039A| 1| S
7| LAMP, NEON| 6912A30001F| 1| S
8| THERMOSTAT| 2H01127K| 2H01127J| 1| S
9| HUMIDISTAT| 5216A20001A| 1| S, A
10| SWITCH ASSEMBLY, MICRO| 6600A30003C| 1| S

DISASSEMBLY INSTRUCTIONS

MECHANICAL PARTS
BUCKET AND AIR FILTER

  1. Disconnect the power supply.
  2. Turn the Humidity Control off.
  3. Remove the bucket. (See Figure 5)
  4. Flex the filter at the lower right corner and take it off. (See Figure 5)

FRONT GRILLE

  1. Remove 2 screws which fasten the front grille.
  2. By pushing the both sides of front grille, pull the front grille forward and upward. (See Figure 6)

CABINET AND CONTROL BOX

  1. Remove the Bucket, the Air filter and Front grille according to the procedure above.
  2. Remove 3 screws that fasten Control box. (See Figure 7)
  3. Remove 9 screws on all sides of the cabinet.
  4. Lift the Cabinet from the base. (See Figure 8)
  5. Remove a screw fasten the earth wire on the front of control box.
  6. Unhook control box from two hooks on the shroud. (See Figure 8)

CONTROL PARTS
ROTARY SWITCH, HUMIDISAT AND NEON LAMP

  1. Unfasten screws located in the bottom side of control box
    (see Figure 9) and fasten capacitor clamp. (DH5010B/DH4010B) And then unfold two sides of control box. (See Figure 9)

  2. Disconnect housing and all leads of rotary switch, humidistat and neon lamp.

  3. Remove 4 screws which fasten the rotary switch and humidistat.

  4. Pull the neon lamp out.

CAPACITOR

  1. Remove each screw that fastens capacitor after control box is stretched upper wand.(See Fig. 9)
  2. Disconnect all leads of capacitor then remove them from control box.

DEFROST CONTROL (Some Models)

  1. Disconnect all leads of the defrost control in the Control Box.
  2. Remove the defrost control from the suction tube.(See Figure 10)

THERMOSTAT CONTROL(Some Models)

  1. Disconnect all leads of the thermostat on the control box.
  2. Remove the capacitor in the control box.(some models)
  3. Remove two screws that fasten the thermostat from the control box. (See figure 11)

MICRO SWITCH ASSY

  1. Disconnect the housing with three leads connected in the Micro switch.
  2. Turn the nut left and take off the micro switch from the barrier. (See Figure 12)

POWER CORD ASSY

  1. After the control box opens, remove a screw that fastens the earth wire of the Power cord.
  2. Disconnect housing and all leads of power cord then remove it from the unit. (See Figure 13)

FAN AND MOTOR

  1. Turn the nut left and full out the Fan by hands carefully.
  2. Remove 2 screws that fasten Heat Exchange.
  3. Lift the H/E and open the H/E around 45 degree clockwise carefully. (See Figure 14)
  4. Unfasten 3 screws that secure the Motor and earth wire. (See Figure 15)
  5. Remove the Motor.

SHROUD AND BARRIER

  1. Discharge the refrigerant by using a refrigerant Recovery System.
  2. After purging the unit completely, unbrace the Discharge and the Suction tube connected compressor carefully.
  3. Remove 2 screws that fasten the H/E.
  4. Unfasten 3 screws that secure the shroud on back and sides and upward the shroud from Barrier.
  5. Unfasten 2 screws that secure the Barrier to base pan.
  6. Pull the Barrier backward then take it up from the base.

REFRIGERATING CYCLE

CONDENSER, EVAPORATOR AND CAPILLARY TUBE(HEAT EXCHANGE ASSEMBLY)

  1. Remove the insulation on the H/E assembly
  2. Pierce the pinch-off tube to discharge the refrigerant, using a FREONTM recovery system.
  3. After discharging the refrigerant completely, remove 2 screws between the shroud and H/E.(See Figure 17)
  4. Lift the H/E and open the H/E around 45 degree clockwise carefully.
  5. Unbrace two interconnecting tubes of the evaporator and condenser carefully.
  6. Remove the H/E assembly from the shroud. (See Figure 18)
  7. Unbrace the capillary tube at the connections of each condenser and evaporator. (See Figure 19)
  8. Remove 4 screws between condenser and evaporator. (See Figure 19)

P.T.C. OR OVERLOAD PROTECTOR (O.L.P.) FOR RECIPROCATING COMPRESSOR

  1. Remove the cabinet. (Refer to section 3.1.3)
  2. Remove a screw or a nut which fastens the terminal cover
  3. Disconnect the lead wire from the overload protector or P.T.C. assembly.
  4. Remove the overload protector(O.L.P) or P.T.C. assembly. (See Figure 20)

ROTARY COMPRESSOR

  1. Remove the cabinet. (Refer to section 3.1.3)
  2. Discharge the refrigerant by using a refrigerant Recovery System.
  3. After purging the unit completely, unbrace the suction and discharge tubes at the compressor connections.
  4. Remove the nuts and washers which fasten the compressor. (See Figure 21)
  5. Remove the compressor. (See Figure 21)

HOW TO REPLACE THE REFRIGERATION SYSTEM

  1. When replacing the refrigeration cycle, be sure to discharge the refrigerant system by using a refrigerant recovery system.

  2. After discharging the unit completely, remove the desired component, and unbrace the pinch-off tubes.

  3. Solder service valves into the pinch-off tube ports, leaving the valves open.

  4. Solder the pinch-off tubes with service valves.

  5. After doing the above procedures, the valve must be closed and left in place on the system for any subsequent procedures.

  6. Evacuate as follows.

  7. Connect the vacuum pump, as illustrated in Figure 22A.

  8. Start the vacuum pump, slowly open manifold valves A and B with two full turns counterclockwise and leave the valves closed. The vacuum pump is now pulling through valves A and B up to valve C by means of the manifold and entire system.
    CAUTION If high vacuum equipment is used, just crack valves A and B for a few minutes, then open slowly with the two full turns counterclockwise. This will keep oil from foaming and being drawn into the vacuum pump.

  9. Operate the vacuum pump for 20 to 30 minutes, until 600 microns of vacuum are obtained. Close valves A and B, and observe vacuum gauge for a few minutes. A rise in pressure would
    indicate a possible leak or moisture remaining in the system. With valves A and B closed, stop the vacuum pump.

  10. Remove the hose from the vacuum pump and place it on the charging cylinder. See Figure 22B. Open valve C.
    Discharge the line at the manifold connection.

  11. The system is now ready for final charging.

  12. Recharge as follows

  13. Refrigeration cycle systems are charged from the High-side. If the total charge cannot be put in the High-side, the balance will be put in the suction line through the access valve which you installed as the system was opened.

  14. Connect the charging cylinder as shown in Figure 22B.
    With valve C open, discharge the hose at the manifold connection.

  15. Open valve A and allow the proper charge to enter the system. Valve B is still closed.

  16. If more charge is required, the high-side will not take it. Close valve A.

  17. With the unit running, open valve B and add the balance of the charge.
    a. Do not add the liquid refrigerant to the Low-side.
    b. Watch the Low-side gauge; allow pressure to rise to 30 lbs.
    c. Turn off valve B and allow pressure to drop.
    d. Repeat steps B and C until the balance of the charge is in the system.

  18. When satisfied the unit is operating correctly, use the pinch-off tool with the unit still running and clamp on to the pinch-off tube. Using a tube cutter, cut the pinch-off tube about 2 inches from the pinch-off tool. Use sil-fos solder and solder pinch-off tube closed. Turn off the unit, allow it to set for a while, and then test the leakage of the pinch-off connection.

NOTE : THE REFRIGERANT R134a IS USED SOME MODELS. CHECK THE SPECIFICATION LABEL ON THE CABINET.

When discharging refrigerant R134a, purging instrument should be used only for R134a, without mixing that of refrigerant R22.
When checking the leakage of refrigerant R134a, leakage test tool should be used only for R134a.
The pump for discharging should be high efficiency. Final discharging value must be managed below 0.5 Torr.
Maximum water should be less than quantity 150mg in the cycle-all tubes and H/E assembly-system.
If water quantity is over 150mg, it causes acid or corrosion in the cycle system and the capillary tube to be clogged by water and harmful materials.
The model charged the refrigerant R134a should be used dryer to prevent water from overflowing.

Equipment needed: Vacuum pump, charging cylinder, manifold gauge, brazing equipment. pinch-off tool capable of making a vapor-proof seal, leak detector, tubing cutter, hand tools to remove components, service valve.

TROUBLESHOOTING GUIDE

CONDITION CAUSE REMEDY

1. Dehumidifier does not start. (Both compressor and fan motor do not operate.)| No power| Check power supply at outlet. Correct if none.
Poor plug contact at outlet.| Install plug properly or replace it.
Bucket is full.| If Auto Shut Off lights, empty the bucket and replace properly.
Humidity control is at Off position| Turn the humidity control switch toward Max.
Wire disconnect or loose| Connect wire. Refer to wiring diagram for terminal identification. Repair or replace loose terminal.
Capacitor.

(Discharge capacitor before testing.)

| Test capacitor.

Replace if not within ±10% of manufacturer’s rating. Replace if shorted, open, or damaged.

2. Motor runs but compressor does not run.| Voltage (115V ± 10%)| It must be between 103.5V and 126.5V. If not within limits, call an electrician
Wiring| Check the wire connections; If loose, repair or replace the terminal. If the wires are disconnected, refer to wiring diagram for identification, and replace the wires. Check the wire connections; If not according to the wiring diagram, correct the connections.
Rotary switch| Check for continuity, refer to the wiring diagram for terminal identification. Replace the switch if the circuit is open.
Defrost control| The Defrost Control senses frost build-up on the evaporator coil and automatically shuts off the compressor. The fan continues to run, drawing air across the coil, and melting the frost. When the coil is defrosted, the compressor automatically restarts, and dehumidifying resumes.
Capacitor

(Discharge capacitor before servicing.)

| Check the capacitor.

Replace if not within ±10% of manufacturer’s rating. Replace if shorted, open, or damaged.

Compressor| Check the compressor for open circuit or ground. If open or grounded, replace the compressor.
Overload protector (O.L.P.)| Check the compressor O.L.P. if externally mounted. Replace if open. (If the compressor temperature is high, remove O.L.P., cool, and retest.)
3. Does not defrost control.| Defrost control is defective.| Check defrost control, replace it.
4. Insufficient dehumidification| Low relative humidity| Turn dehumidifier off.
Poor air circulation| Move dehumidifier to obtain free and unobstructed air circulation.
H/E clogged with dust and dirt| Clean evaporator and/or condenser assembly
Air filter is dirty.| Clean it.
Motor is not operating.| Check Motor, repair or replace it.
CONDITION| CAUSE| REMEDY
---|---|---
5. Noisy operating| Fan| If cracked, out of balance, or partially missing, replace it
Some material plunged and rattle.| Remove it.
Tube hits frame.| Adjust tubing routine carefully.
Fan blade hits frame| Check Motor Mount. If loose, tighten it.
Internal compressor noise.| Replace compressor.
Loose set screws| Tighten them.
Worn bearings of Motor Assembly| If knocking sounds continue when running or loose, replace the motor. If the motor hums or noise appears to be internal while running, replace motor assembly.
6. Water drips| The bucket is not installed properly.| The bucket should be properly positioned on the hangers of the drain pan.
Connection may be loose.| Check connection and repair.
Leak in bucket| Replace bucket.
Water drips when bucket removed for emptying.| Before removing bucket, the unit should be turned off.
Bucket overflows.| Check micro switch and float.
7. Compressor cycles on overload protector. (O.L.P.)| High or low line voltage. (115V ± 10%)| Check line voltage. It must be between 103.5V and 126.5V volts.

If intermittent, provide new supply.

Poor air circulation.| Move dehumidifier for free and unobstructed air flow.
Heat Exchange clogged with dust or dirt.| Clean dust or dirt on the Heat Exchange.
Motor| If not running, determine the cause. Replace if required.
Bad P.T.C. assembly (if assembled)| Check P.T.C., Repair.
Short circuit or ground in electrical circuit| Check electrical circuit. Repair.
Unit pressures not equalized| Allow 2 or 3 minutes for pressure to equalize before starting compressor.
Capacitor| Test the capacitor.
Wiring| Check the terminals. If loose, repair or replace.
Refrigeration system| Check the system for a restriction.
Stuck compressor| Check compressor, replace compressor
Overload protector (O.L.P.)| Check O.L.P., if externally mounted. Replace if open. (If the compressor temperature is high, remove the O.L.P., cool, and retest.)

EXPLODED VIEW – INTRODUCTION

MODEL: DH3010B/DHA3012DL

MODEL: DH4010B/DHA4012DL, DH5010B/DHA5012DL(DEFROST CONTROL TYPE)

MODEL: DH4010B/DHA4012DL, DH5010B/DHA5012DL(THERMOSTAT CONTROL

REPLACEMENT PARTS LIST

MODEL: DH3010B, DHA3012DL

LOCATION NO. DESCRIPTION PART NO. REMARK

DH3010B/DHA3012DL
130411| BASE ASSY, WELD(SINGLE)| 3041AD2007B|
130900| CABINET| 3090A10001J|
135312| GILLE ASSY, FRONT| 3531A20012B|
147910| BARRIER ASSY| 4791A10002B|
148380| TANK, BUCKET| 4838A20005A|
149410| KNOB ASSY| 4941A30002A|
152302| FILTER(MECH), AIR| 5230AD3005A|
249950| CONTROL BOX ASSY| 4995A20085F|
W6640| TERMINAL BLOCK| 6640A40001A|
264110| POWER CORD ASSY| 6411A20001Q| ALT) 6411A20001R
266003| SWITCH, ROTARY| 6600A20001A|
252160| HUMIDISTAT| 5216A20001A| ALT) 5216A20001B
266011| SWITCH ASSY, MICRO| 6600A30003C|
266140| CONTROL DEFROST| 6614A30001H|
269120| LAMP, NEON| 6912A30001F|
346811| MOTOR ASSY, SINGLE| 4681A20040A|
35211A| TUBE ASSY, SUCTION SINGLE| 5211A30373B|
352113| TUBE ASSY, DISCHARGE SINGLE| 5211A30367A|
354211| EVAPORATOR ASSY| 5421A10009B|
549990| SHROUD ASSY| 4999A10001A|
550140| ISOLATOR| 5040AR4195A|
552111| TUBE ASSY, CAPILLARY| 5211A10085C|
554030| CONDENSER ASSY| 5403A10008B|
554160| COMPRESSOR ASSY, FINAL| 2521C-A8605|
359012| FAN, TURBO| 5900A20007A|
567502| O.L.P| 6750C-0002S|
349600| MOUNT, MOTOR| 4960A20009A|
667482| P.T.C| 6748C-0003A|

MODEL: DH4010B/DHA4012DL, DH5010B/DHA5012DL(DEFROST CONTROL TYPE)

LOCATION NO. DESCRIPTION PART NO. REMARK
DH4010B/DHA4012DL DH5010B/DHA5012DL
130411 BASE ASSY, WELD(SINGLE) 3041AD2007C
130900 CABINET 3090A10001J
135312 GILLE ASSY, FRONT 3531A20012B
147910 BARRIER ASSY 4791A10002A ALT)4791A10002B
148380 TANK, BUCKET 4838A20005A
149410 KNOB ASSY 4941A30002A
152302 FILTER(MECH), AIR 5230AD3005A
W0CZZ CAPACITOR 0CZZA20001Q
249950 CONTROL BOX ASSY 4995A20085E
264110 POWER CORD ASSY 6411A20001Q ALT) 6411A20001R
266003 SWITCH, ROTARY 6600A20001A
252160 HUMIDISTAT 5216A20001A ALT) 5216A20001B
266011 SWITCH ASSY, MICRO 6600A30003C
266140 CONTROL DEFROST 6614A30001F
269120 LAMP, NEON 6912A30001F
346811 MOTOR ASSY, SINGLE 4681A20040A
35211A TUBE ASSY, SUCTION SINGLE 5211A10071B 5211A10071A
352113 TUBE ASSY, DISCHARGE SINGLE 5211A10070C 5211A10070A
354211 EVAPORATOR ASSY 5421A10009D 5421A10009A
549990 SHROUD ASSY 4999A10001A
550140 BUSHING 4830A30005A
552111 TUBE ASSY, CAPILLARY 5211A10085D 5211A10085A
554030 CONDENSER ASSY 5403A10008C 5403A10008A
554160 COMPRESSOR ASSY, FINAL 2520UABC2FA 5416AR2179J
359012 FAN, TURBO 5900A20007A
567502 O.L.P 6750U-L039A
349600 MOUNT, MOTOR 4960A20009A

MODEL: DH4010B/DHA4012DL, DH5010B/DHA5012DL(THERMOSTAT CONTROL TYPE)

LOCATION NO. DESCRIPTION PART NO. REMARK
DH4010B/DHA4012DL DH5010B/DHA5012DL
130411 BASE ASSY, WELD(SINGLE) 3041AD2007C
130900 CABINET 3090A10001J
135312 GILLE ASSY, FRONT 3531A20012B
147910 BARRIER ASSY 4791A10002A ALT)4791A10002B
148380 TANK, BUCKET 4838A20005A
149410 KNOB ASSY 4941A30002A
152302 FILTER(MECH), AIR 5230AD3005A
W0CZZ CAPACITOR 0CZZA20001Q
249950 CONTROL BOX ASSY 4995A20085J 4995A20085G
264110 POWER CORD ASSY 6411A20001Q ALT) 6411A20001R
266003 SWITCH, ROTARY 6600A20001A
252160 HUMIDISTAT 5216A20001A ALT) 5216A20001B
266011 SWITCH ASSY, MICRO 6600A30003C
269310 THERMOSTAT 2H01127K 2H01127J
269120 LAMP, NEON 6912A30001F
346811 MOTOR ASSY, SINGLE 4681A20040A
35211A TUBE ASSY, SUCTION SINGLE 5211A10071B 5211A10071A
352113 TUBE ASSY, DISCHARGE SINGLE 5211A10070C 5211A10070A
354211 EVAPORATOR ASSY 5421A10009D 5421A10009A
549990 SHROUD ASSY 4999A10001A
550140 BUSHING 4830A30005A
552111 TUBE ASSY, CAPILLARY 5211A10085D 5211A10085A
554030 CONDENSER ASSY 5403A10008C 5403A10008A
554160 COMPRESSOR ASSY, FINAL 2520UABC2FA 5416AR2179J
359012 FAN, TURBO 5900A20007A
567502 O.L.P 6750U-L039A
349600 MOUNT, MOTOR 4960A20009A

References