LG L1404R Room Air Conditioner Instruction Manual

July 29, 2024
LG

LG L1404R Room Air Conditioner

CAUTION

  • BEFORE SERVICING THE UNIT, READ THE SAFETY PRECAUTIONS IN THIS MANUAL.
  • ONLY FOR AUTHORIZED SERVICE PERSONNEL.

Safety Precautions

To prevent injury to the user or other people and property damage, the following instructions must be followed.

  • Incorrect operation due to ignoring instructions will cause harm or damage. The seriousness is classified by the following indications.
    • WARNING This symbol indicates the possibility of death or serious injury.
    • CAUTION This symbol indicates the possibility of injury or damage to properties only.
  • Meanings of symbols used in this manual are as shown below.
  • Be sure not to do.
  • Be sure to follow the instructions.

Installation

Do not use damaged power cord plugs, or a loose socket.

  • There is risk of fire or electric shock.

Always use the power plug and socket with the ground terminal.

  • There is risk of electric shock.
  • Do not modify or extend the power cord.
  • There is risk or fire or electrics hock.
  • Be cautious when unpacking and installing the product.
  • Sharp edges could cause injury. Be especially careful of the case edges and the fins on the condenser and evaporator.
  • Be sure the installation area does not deteriorate with age.
  • If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury.
  • Do not install, remove, or re-install the unit by yourself(customer).
  • There is risk of fire, electric shock, explosion, or injury.
  • Do not store or use flammable gas or combustibles near the air conditioner.
  • There is risk of fire or failure of the product.

Dimensions

Symbols Used in this Manual

  • This symbol alerts you to the risk of electric shock.
  • This symbol alerts you to hazards that could cause harm to the air conditioner.
  • NOTICE This symbol indicates special notes.

Outside Dimensions

Model

Dimension

| ****

L1404R

---|---
W| mm(inch)| 660(25 31/32)
H| mm(inch)| 428(16 27/32)
D| mm(inch)| 680(26 27/32)

Product Specifications


ITEMS

| MODELS| ****

L1404R

---|---|---
POWER SUPPLY| 1ø, 115V, 60Hz



COOLING

| CAPACITY| (BTU/h)| 13,500
INPUT| (W)| 1,380
RUNNING CURRENT (A)| 12.0
E.E.R             (BTU/W.h)| 9.8



HEATING

| CAPACITY| (BTU/h)| –
INPUT| (W)| –
RUNNING CURRENT (A)| –
E.E.R             (BTU/W.h)| –
OPERATING

CONDITION

| INDOOR (°C)| 26.7(DB)*       19.4(WB)*
OUTDOOR (°C)| 35(DB)
         23.9(WB)**
REFRIGERANT (R-22) CHARGE| 670g(23.6 oz)
EVAPORATOR| 2 ROW 11 STACKS, LOUVER-FIN TYPE
CONDENSER| 2 ROW 19 STACKS, STRAIGHT TYPE
FAN, INDOOR| TURBO FAN
FAN, OUTDOOR| PROPELLER TYPE FAN WITH SLINGER RING
FAN SPEEDS, FAN/COOLING/HEATING| 3/3
FAN MOTOR| 6 POLES
OPERATION CONTROL| REMOTE CONTROLLER
ROOM TEMP. CONTROL| THERMISTOR


AIR DIRECTION CONTROL

| VERTICAL LOUVER (RIGHT & LEFT)
HORIZONTAL LOUVER (UP & DOWN)
CONSTRUCTION| SLIDE IN-OUT CHASSIS


PROTECTOR

| COMPRESSOR| OVERLOAD PROTECTOR
FAN MOTOR| INTERNAL THERMAL PROTECTOR


POWER CORD

| 3 WIRE WITH GROUDING
ATTACHMENT PLUG (CORD-CONNECTED TYPE)
DRAIN SYSTEM| DRAIN PIPE OR SPLASHED BY FAN SLINGER
NET WEIGHT| (lbs/kg)| 126/57
OUTSIDE DIMENSION

(W x H x D)

| (inch)| 25 31/32 x 16 27/32 x 26 27/32
(mm)| 660 x 428 x 680

  • DB : dry bulb
  • WB : wet bulb

Note: Please refer to Label Quality on the product Since this specification may be changed for improving performance.

Select the Best Location

  1. To avoid vibration and noise, make sure the unit is installed securely and firmly.
  2. Install the unit where the sunlight does not shine directly on the unit. If the unit receives direct sunlight, build an awning to shade the cabinet.
  3. There should be no obstacle, like a fence, within 20″ which might restrict heat radiation from the condenser.
  4. To prevent reducing performance, install the unit so that the louvers of the cabinet are not blocked.
  5. Install the unit a little obliquely outward not to leak the condensed water into the room (about 1/2″ or 1/4 bubble with level).
  6. Install the unit with its bottom portion 30~60″ above the floor level.
  7. Stuff the foam between the top of the unit and the wall to prevent air and insects from getting into the room.
  8. The power cord must be connected to an independent circuit. The green wire must be grounded.
  9. Connect the drain tube to the base pan hole in the rear side if you need to drain (consult a dealer). A plastic hose or equivalent may be connected to the drain tube.

Installation Check

The setting conditions must be checked prior to initial starting. The following items are especially important check points when the installation is finished.

  1. Grounding wire (Green or Green and Yellow) is provided in the power cord. The green wire must be grounded.
  2. Connect to a single-outlet 15A circuit. (or 20A circuit for Electric Heater Model)
  3. To avoid vibration or noise, make sure the air conditioner is installed securely.
  4. Avoid placing furniture or draperies in front of the air inlet and outlet.

How to Secure the Drain Pipe
In humid weather, excess water may cause the BASE PAN to overflow. To drain the water, remove the DRAIN CAP and secure the DRAIN PIPE to the rear hole of the BASE PAN. Press the drain pipe into the hole by pushing down and away from the fins to avoid injury.

Optional

  1. Install the drain pan over the corner of the cabinet where you removed the plug with 4 (or 2) screws.
  2. Connect the drain hose to the outlet located at the bottom of the drain pan. You can purchase the drain hose or tubing locally to satisfy your particular needs. (Drain hose is not supplied).
  3. Select the most appropriate connection from among the following figures (by considering the hole of the unit) to fit the drain pan to your unit.

How to Install

When Using Installation Kits

Window Requirements
This unit is designed for installation in standard double-hung windows with actual opening widths from 29″ to 41″. The top and bottom window sash must open sufficiently to allow a clear vertical opening of 16″ fromthe bottom of the upper sash to the window stool.

Installation Kits Contents

  • Top retainer bar is in the product package.
NO. NAME OF PARTS Q’TY
1 FRAME CURTAIN 2
2 SILL SUPPORT 2
3 BOLT 2
4 NUT 2
5 SCREW(TYPE A) (10mm(2/5″)) 16
6 SCREW(TYPE B) D5.1mm(0.2″)/16mm(0.63″) 3
7 SCREW(TYPE C) D4.1mm(0.17″)/16mm(0.63″) 5
8 FOAM-STRIP 1
9 FOAM-PE (600mm x 25mm x 2mm) 1
10 WINDOW LOCKING BRACKET 1
11 FOAM-PE (920mm x 30mm x 2mm) 1
12 DRAIN PIPE 1
13 FRAME GUIDE 2
  1. Open the window. Mark a line on the center of the window stool between the side window stop moldings. Loosely attach the sill bracket to the support bracket using the carriage bolt and the lock nut.
  2. Attach the sill bracket to the window sill using the screws (Type B). Carefully place the cabinet on the window stool and align the center mark on the bottom front with the center line marked window stool.
  3. Using the M-screw and the lock nut, attach the support bracket to the cabinet track hole. Use the first track hole after the sill bracket on the outer edge of the window sill. Tighten the carriage bolt and the lock nut. Be sure the cabi-net slants outward. CAUTION: Do not drill a hole in the bottom pan. The unit is designed to operate with approximately 1/2″ of water in the bottom pan.
  4. Pull the bottom window sash down behind the Top retainer bar until they meet.

NOTICE

  1. Do not pull the window sash down so tightly that the movement of the Frame curtain is restricted. Attach the cabinet to the window stool by driving the screws (Type B) through the cabinet into the window stool.

  2. The cabinet should be installed with a very slight tilt downward toward the outside.

  3. Pull each Frame curtain fully to each window sash track, and pull the bottom window sash down behind the Top retainer bar until it meets.

  4. Attach each Frame curtain the window sash by using screws (Type C). (See Fig. 7)

  5. Slide the unit into the cabinet. (See Fig. 8)
    CAUTION: For security purposes, reinstall screws (Type A) at the cabinet’s sides.

  6. Cut the foam strip to the proper length and insert it between the upper window sash and the lower window sash. (See Fig. 9)

  7. Attach the Window locking bracket with a screw (Type C). (See Fig. 10) 10.

  8. Attach the front grille to the cabinet by inserting the tabs on the grille into the tabs on the front of the cabinet. Push the grille in until it snaps into place. (See Fig.11)

  9. Lift the inlet grille and secure it with a screw (Type A) through the front grille. (See Fig. 11)

  10. Window installation of room air conditioner is now completed.

Operation

Function of Controls

  • Designed for COOLING ONLY.
  • Powerful and quiet cooling.
  • Slide-in and slide-out chassis for the simple installation and service. Low air intake, top cooled-air discharge.
  • Built-in adjustable Thermistor
  • Washable one-touch filter
  • Compact size
  • Equipped with reliable and efficient rotary compressor.

PRECAUTION: The Remote Control unit will not function properly if strong light strikes the sensor window of the air conditioner or if there are obstacles between the Remote Control unit and the air conditioner.

POWER BUTTON
To turn the air conditioner ON, push the button. To turn the air conditioner OFF, push the button again. This button takes priority over any other buttons.

ROOM TEMPERATURE SETTING BUTTON
This button can automatically control the temperature of the room. The temperature can be set within a range of 60°F to 86°F by 1°F. (16°C to 30°C by 1°C) Select the lower number for the lower temperature of the room.

OPERATION MODE SELECTION BUTTON
Every time you push this button, it will shift among COOL, ENERGY SAVER, FAN, and DRY.

  • Energy Saver: If Energy Save mode is selected, the fan stops when the compressor stops cooling. Approximately every 3 minutes the fan will turn on and check the room air to determine if cooling is needed.

FAN SPEED SELECTOR
Every time you push this button, it is set as follows. (Hi [F3] ➔ Low [F1] ➔ Med [F2] ➔ Hi [F3] ➔ Low [F1] ➔…)

ON/OFF TIMER BUTTON
You can set the time when the unit will turn on or turn off automatically by pressing the timer button. If the unit is operating, this button controls the time it will be turned off. If the unit is off-state, this button controls the time it will start. Every time you push this button, the remaining time will be set as follows.

  • Stopping operation (1Hour ➔ 2Hours ➔ 3Hours ➔ 4Hours ➔ 5Hours ➔ 6Hours ➔ 7Hours ➔ 8Hours ➔ 9Hours ➔ 10Hours ➔ 11Hours ➔ 12Hours ➔ 0Hour ➔ 1Hour ➔ 2Hours ➔… )
  • Starting operation (1Hour ➔ 2Hours ➔ 3Hours ➔ 4Hours ➔ 5Hours ➔ 6Hours ➔ 7Hours ➔ 8Hours ➔ 9Hours ➔ 10Hours ➔ 11Hours ➔ 12Hours ➔ off ➔ 1Hour ➔ 2Hours ➔ … )

Disassembly

  • Before the following disassembly, CONTROL BOX set to OFF and disconnect the power cord.

Mechanical Parts

Front Grille

  1. Open the inlet grille downward and remove the air filter.
  2. Remove the screw that fastens the front grille.(See Figure 13)
  3. Pull the front grille from the right side.
  4. Remove the front grille. (There are 4 hooks.)
  5. Re-install the components by referring to the removal procedure, above.

Cabinet

  1. After disassembling the FRONT GRILLE, remove the 2 screws that fasten the cabinet at both sides.
  2. Remove the 2 screws that fasten the cabinet at the back.
  3. Pull the base pan forward. (See Figure 14)
  4. Remove the cabinet.
  5. Re-install the components by referring to the removal procedure, above.

Control Box

  1. Remove the front grille. (Refer to section 1)
  2. Remove the cabinet. (Refer to section 2)
  3. Remove the 2 screws which fasten the power cord.
  4. Disconnect the grounding screw from the evaporator channel.
  5. Remove the 1 screw that fastens the control box cover.
  6. Remove the housing that connects the PCB and motor wire in the control box.
  7. Disconnect the housing that connects the Plazma Air Purifier. (Optional)
  8. Remove the screw at the left cover of the filter case and open the cover to remove the inner screw. (Optional)
  9. Remove the nut that fastens the terminal cover.
  10. Remove the terminal cover.
  11. Remove all the leads from the overload protector.
  12. Discharge the capacitor by placing a 20,000-ohm resistor across the capacitor terminals.
  13. Raise the control box upward completely. (See Figure 15)
  14. Re-install the components by referring to the removal procedure, above. (Refer to the wiring diagram found on page 22 in this manual and on the control box.)

Air Handling Parts

Air Guide and Turbo Fan

  1. Remove the front grille. (Refer to section 1)
  2. Remove the cabinet. (Refer to section 2)
  3. Remove the control box. (Refer to section 3)
  4. Remove the 4 screws that fasten the brace.
  5. Remove the brace.
  6. Remove the 2 screws that fasten the air guide upper.
  7. Remove the air guide upper.(See Figure 16)
  8. Remove the 2 screws that fasten the evaporator.
  9. Move the evaporator forward and pull it upward slightly. (See Figure 17)
  10. Pull out the hook of the orifice by pushing the tabs and removing it. (See Figure 18)
  11. Remove the clamp with a hand plier that secures the turbofan.
  12. Remove the turbofan.
  13. Remove the 2 screws that fasten the air guide from the base pan.
  14. Move the air guide backward, and pull out from the base pan.(Move the air guide lower carefully)
  15. Re-install the components by referring to the removal procedure, above.

FAN

  1. Remove the cabinet. (Refer to section 2)
  2. Remove the brace (Refer to section 4)
  3. Remove the 5 screws that fasten the condenser.
  4. Move the condenser to the left carefully.
  5. Remove the clamp that secures the fan.
  6. Remove the fan. (See Figure 19)
  7. Re-install by referring to the removal procedure.

Shroud

  1. Remove the fan. (Refer to section 5)
  2. Remove the shroud. (See Figure 20)
  3. Reinstall the components by referring to the removal procedure, above.

Electrical Parts

Overload Protector

  1. Remove the cabinet. (Refer to section 2)
  2. Remove the nut that fastens the terminal cover.
  3. Remove the terminal cover. (See Figure 21)
  4. Remove all the leads from the overload protector.
  5. Remove the overload protector.
  6. Re-install the components by referring to the removal procedure, above.

Compressor

  1. Remove the cabinet. (Refer to section 2)
  2. Discharge the refrigerant system using a FreonTM Recovery System. If there is no valve to attach to the recovery system, install one (such as a WATCO A-1) before venting the FreonTM. Leave the valve in place after servicing the system.
  3. Remove the overload protector. (Refer to section 7)
  4. After purging the unit completely, unbraze the suction and discharge tubes at the compressor connections.
  5. Remove the 3 nuts and the 3 washers which fasten the compressor.
  6. Remove the compressor. (See Figure 22)
  7. Re-install the components by referring to the removal procedure, above.

Capacitor

  1. Remove the control box. (Refer to section 3)
  2. Open the top cover from the control box. (See Figure 23)
  3. Pull out the capacitor from the control box.
  4. Disconnect all the leads of capacitor terminals.
  5. Re-install the components by referring to the removal procedure, above.

Power Cord

  1. Remove the control box. (Refer to section 3)
  2. Open the top cover from the control box. (Refer to section 9)
  3. Disconnect the front panel from the control box. (See Figure 24)
  4. Disconnect two leads from the capacitor and relay.
  5. Pull out the power cord.
  6. Re-install the component by referring to the above removal procedure, above. (Use only one ground-marked hole for ground connection.)
  7. If the supply cord of this appliance is damaged, it must be replaced by a special cord. (The special cord means the cord which has the same specification marked on the supply cord attached at the unit.)

Motor

  1. Remove the cabinet. (Refer to section 2)
  2. Remove the turbofan. (Refer to section 4)
  3. Remove the fan. (Refer to section 5)
  4. Remove the 4 screws that fasten the motor from the air guide. (See Figure 25)
  5. Remove the motor.
  6. Re-install the components by referring to the removal procedure, above.(See Figure 25)

Refrigerating Cycle

Condenser

CAUTION: Discharge the refrigerant system using a FreonTM Recovery System. If there is no valve to attach to the recovery system, install one (such as a WATCO A-1) before venting the FreonTM. Leave the valve in place after servicing the system.

  1. Remove the cabinet. (Refer to section 2)
  2. Remove the 4 screws that fasten the brace.(Refer to section 4)
  3. Remove the 5 screws that fasten the condenser and shroud.
  4. After discharging the refrigerant completely, unbraze the interconnecting tube at the condenser connections.
  5. Remove the condenser.
  6. Re-install the components by referring to notes. (See Figure 26)

Evaporator

  1. Remove the control box. (Refer to section 3)
  2. Remove the air guide upper. (Refer to section 4)
  3. Remove the 2 screws that fasten the evaporator.
  4. Move the evaporator sideways carefully. (Refer to section 4)
  5. After discharging the refrigerant completely, unbraze the interconnecting tube at the evaporator connections.
  6. Remove the evaporator.
  7. Re-install the components by referring to notes. (See Figure 27)

Capillary Tube

  1. Remove the cabinet. (Refer to section s2)
  2. After discharging the refrigerant completely, unbraze the interconnecting tube at the capillary tube. (See caution above)
  3. Remove the capillary tube.
  4. Reinstall the components by referring to notes.

NOTICE

  • Replacement of the refrigeration cycle.
  1. When replacing the refrigeration cycle, be sure to Discharge the refrigerant system using a FreonTM Recovery System. If there is no valve to attach to the recovery system, install one (such as a WATCO A-1) before venting the FreonTM. Leave the valve in place after servicing the system.

  2. After discharging the unit completely, remove the desired component, and unbraze the pinch-off tubes.

  3. Braze service valves into the pinch-off tube ports, leaving the valves open.

  4. Braze the pinch-off tubes with Service valves.

  5. Evacuate as follows.

  6. Connect the vacuum pump, as illustrated in Figure 28A.

  7. Start the vacuum pump, slowly open manifold valves A and B with two full turns counterclockwise, and leave the valves open. The vacuum pump is now pulling through valves A and B up to valve C using the manifold and the entire system.
    CAUTION: If high vacuum equipment is used, just crack valves A and B for a few minutes, then open slowly with the two full turns counterclockwise. This will keep oil from foaming and being drawn into the vacuum pump.

  8. Operate the vacuum pump vacuum for 20 to 30 minutes, until 600 microns of vacuum is obtained. Close valves A and B, and observe the vacuum gauge for a few minutes. A rise in pressure would indicate a possible leak or moisture remaining in the system. With valves A and B closed, stop the vacuum pump.

  9. Remove the hose from the vacuum pump and place it on the charging cylinder. See Figure 29B. Open valve C. Discharge the line at the manifold connection.

  10. The system is now ready for final charging.

  11. Recharge as follows :

  12. Refrigeration cycle systems are charged from the high side. If the total charge cannot be put in the high side, the balance will be put in the suction line through the access valve which you installed as the system was opened.

  13. Connect the charging cylinder as shown in Figure 28B. With valve C open, discharge the hose at the manifold connection.

  14. Open valve A and allow the proper charge to enter the system. Valve B is still closed.

  15. If more charge is required, the high side will not take it. Close valve A.

  16. With the unit running, open valve B and add the balance of the charge.

  * Do not add the liquid refrigerant to the low side.
  * Watch the Low-side gauge; allow pressure to rise to 30 lbs.
  * Turn off valve B and allow pressure to drop.
  * Repeat steps b. and c. until the balance of the charge is in the system.
10. When satisfied the unit is operating correctly, use the pinch-off tool with the unit still running and clamp on to the pinch-off tube. Using a tube cutter, cut the pinch-off tube about 2 inches from the pinch-off tool. Use sil-fos brazing and braze the pinch-off tube closed. Turn off the unit, allow it to set for a while, and then test the leakage of the pinch-off connection.

Equipment needed: Vacuum pump, Charging cylinder, Manifold gauge, Brazing equipment. Pin-off tool capable of making a vapor-proof seal, Leak detector, Tubing cutter, Hand Tools to remove components, Service valve.

Schematic Diagram

Electronic Control Device

Wiring Diagram

  • S: Service Parts
  • N: Non-Service Parts

LOCATION NO.

|

DESCRIPTION

|

Q’TY PER SET

|

REMARKS

---|---|---|---
1| MOTOR ASSY| 1| S
2| CAPACITOR| 1| S
3| COMPRESSOR| 1| S
4| OVERLOAD PROTECTOR| 1| S
5| DC PCB ASSEMBLY| 1| S
6| AC PCB ASSEMBLY| 1| S
7| THERMISTOR| 1| S
8| PLASMA FILTER ASSY| 1| S

Components Location

MAIN P.C.B ASSEMBLY

DISPLAY P.C.B. ASSEMBLY

Troubleshooting Guide

Piping System

Figure 29 is a brief description of the important components and their function in what is called the refrigeration system. This will help you to understand the refrigeration cycle and the flow of the refrigerant in the cooling cycle.

In general, possible trouble is classified in two kinds. The one is called Starting Failure which is caused by an electrical defect, and the other is ineffective Air Conditioning caused by a defect in the refrigeration circuit and improper application.

Unit runs but poor cooling.

COMPLAINT CAUSE REMEDY
Fan motor will not run. No power Check the voltage at the outlet. Correct if

none.
Power supply cord| Check the voltage to the Control Box. If none, check the power supply cord. Replace cord if the circuit is open.
Wire disconnected or con- nection loose| Connect wire. Refer to wiring diagram for terminal identification. Repair or replace loose terminal.
Capacitor (Discharge capacitor before testing.)| Test capacitor.

Replace if not within ±10% of manufacturer’s rating. Replace if shorted, open, or damaged.

Will not rotate| Fan blade hitting shroud or blower wheel hitting scroll. Realign assembly.

Units using slinger ring for condenser fan must have 1/4 to 5/16 inch clearance to the base. If it hits the base, shim up the bottom of the fan motor with mounting screw(s).

Check fan motor bearings; if motor shaft will not rotate, replace the motor.

Fan motor runs intermittently| Revolves on overload.| Check voltage. If not within limits, call an electrician.

Test capacitor.

Check bearings. Does the fan blade rotate freely? If not, replace fan motor.

Pay attention to any change from high speed to

low speed. If the speed does not change, replace the motor.

Fan motor noise.| Fan| If cracked, out of balance, or partially missing, replace it.
Turbo| If cracked, out of balance, or partially missing, replace it.
Loose clamper| Tighten it.
Worn bearings| If knocking sounds continue when running or loose, replace the motor. If the motor hums or noise appears to be internal while running, replace the motor.
The compressor will not run, but fan motor runs.| Voltage| Check voltage.

If not within limits, call an electrician.

Wiring| Check the wire connections, if loose, repair or replace the terminal. If wires are off, refer to the wiring diagram for identification, and replace. Check wire locations. If not per the wiring diagram, correct.
COMPLAINT| CAUSE| REMEDY
---|---|---
The compressor will not run, but fan motor runs.| Thermistor| Check the TEMP control. If not at the lowest number, set TEMP control to this setting and restart the unit. Check the continuity of the thermistor. Replace the thermistor if the circuit is open.
Capacitor (Discharge capacitor before servicing.)| Check the capacitor.

Replace if not within ±10% of the manufacturer’s rating. Replace if shorted, open, or damaged.

Compressor| Check the compressor for open circuit or ground. If open or grounded, replace the compressor.
Overload| Check the compressor overload, if externally mount- ed. Replace if open. (If the compressor temperature is high, remove the overload, cool it, and retest.)
Compressor cycles on overload.| Voltage| Check the voltage.

If not within limits, call an electrician.

Overload| Check overload, if externally mounted.

Replace if open. (If the compressor temperature is high, remove the overload, cool, and retest.)

Compressor cycles on overload.| Fan motor| If not running, determine the cause. Replace if required.
Condenser airflow restriction| Remove the cabinet. inspect the interior surface of the condenser; if restricted, clean carefully with a vacuum cleaner (do not damage fins) or brush. Clean the interior base before reassembling.
Condenser fins (damaged)| If condenser fins are closed over a large area on the coil surface, head pressures will increase, causing the compressor to overload. Straighten the fins or replace the coil.
Compressor cycles on overload.| Capacitor| Test capacitor.
Wiring| Check the terminals. If loose, repair or replace.
Refrigerating system| Check the system for a restriction.
Insufficient cooling or heating| Air filter| If restricted, clean of replace.
Exhaust damper door| Close if open.
Unit undersized| Determine if the unit is properly sized for the area to be cooled.
Excessive noise| Turbo or fan| Check the set screw or clamp. If loose or missing, correct. If the turbo or fan is hitting air guide, rearrange the air handling parts.
Copper tubing| Remove the cabinet carefully and rearrange tubing so as not to contact the cabinet, compressor, shroud, and barrier.

Exploded View

Replacement Parts List

LOCATION NO .| ****

DESCRIPTION

| PART NO.| ****

REMARK

---|---|---|---
L1404R
130410| BASE ASSEMBLY, WELD[SINGLE]| 3041A20023V| R
130910| CABINET ASSEMBLY, SINGLE| 3091AR6057J| R
135312| GRILLE ASSEMBLY, FRONT(SINGLE)| 3531A20095A| R
135303| GRILLE, INLET| 3530A10080A| R
135500| COVER| 3550A30122A| R
147581| LOUVER, HORIZONTAL| 4758A30022A| R
147582-1| LOUVER, VERTICAL| 4758A20042A| R
147582-2| LOUVER, VERTICAL| 4758A20042B| R
148000| BRACE| 4800A20001A| R
149980| SHROUD| 4998A10026A| R
152302| FILTER ASSEMBLY, AIR CLEANER| 5231A20008A| R
237200| PANEL, CONTROL| 3720A10112A| R
249950| CONTROL BOX ASSEMBLY, SINGLE| 4995A23001A| R
268712| PWB(PCB) ASSEMBLY, MAIN(AC)| 6871A20167E| R
238310| ESCUTCHEON| 3831A10021M| R
268714| PWB(PCB) ASSEMBLY, MAIN(DC)| 6871A20325A| R
263230| THERMISTOR ASSEMBLY| 6323A20004E| R
264110| POWER CORD ASSEMBLY| 6411A20011J| R
346811| MOTOR ASSEMBLY, SINGLE| 4681AR6033X| R
349001| VENTILATION DAMPER| 4900A20004A| R
349480| ORIFICE| 4948A30008A| R
349600| MOUNT, MOTOR| 4960AR1596A| R
352111| TUBE, CAPILLARY BEND| 5210A20492Q| R
352113| TUBE ASSEMBLY, DISCHARGE SINGLE| 5211A30066R| R
W52106-1| TUBE , FORMED| 5210A21099L| R
W52106-2| TUBE , FORMED| 5210A21099M| R
35211A| TUBE ASSEMBLY, SUCTION(OUTDOOR)| 5211A20441G| R
352390| AIR GUIDE ASSEMBLY| 5239A20002A| R
354210| EVAPORATOR ASSEMBLY, FIRST| 5421A20091E| R
550140| ISOLATOR, COMP| 4H00982C| R
554031| CONDENSER ASSEMBLY, FIRST| 5403A20112B| R
554160| COMPRESSOR SET| 2520UMTC2BA| R
559010| FAN ASSEMBLY, AXIAL| 5901A20010A| R
359012| FAN ASSEMBLY, TURBO| 5901A20009A| R
267110| REMOTE CONTROLLER ASSEMBLY| 6711A20034G| R
W48602| CLAMP, SPRING| 3H02932C| R
W0CZZ| CAPACITOR, DRAWING| 0CZZA20001L| R

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals