Room Air Conditioner

SVC MANUAL(Exploded View)
MODEL : LWM1836TAS, LWM1836QCG, LWN2131QAG, Y5USC24-6R,
WG2400R, LWN2432QAS, LWN2433TCS, WG1800R, M1804R,
Y5USC18-6R, LWM1836QAS, HBLG1800R, HBLG2400R,
M2403R, LWC243NSMM0, LWC243NSMM2, HBLG2350E

CAUTION
Before Servicing the unit, read the safety precautions in General SVC manual. Only for authorized service personnel.

PREFACE

This service manual provides various service information, including the mechanical and electrical parts, etc.
This room air conditioner was manufactured and assembled under a strict quality control system.
The refrigerant is charged at the factory. Be sure to read the safety precautions prior to servicing the unit.
1.1 SAFETY PRECAUTIONS

  1. When servicing, set the POWER of CONTROL BOARD to Off and unplug the power cord.

  2. Observe the original lead dress.
    If a short circuit is found, replace all parts which have been overheated or damaged by the short circuit.

  3. After servicing, make an insulation resistance test to prevent the customer’s exposure to shock hazards.

1.2 INSULATION RESISTANCE TEST

  1. Unplug the power cord and connect a jumper between 2 pins (black and white).
  2. The grounding conductor (green or green and yellow) is to be open.
  3. Measure the resistance value with an ohm meter between the jumpered lead and each exposed metallic part on the equipment at all Mode [except POWER OFF].
  4. The value should be over 1 MΩ.

1.3 SPECIFICATIONS

MODELS ITEMS| M1804R WG1800R HBLG1800R| LWM1836TASL WN1836QCG| LWM1863QAS Y5USC18-6R| LWN2131QAG| WG2400R HBLG2400R M2403R| LWN2432QAS Y5USC24-6R LWC243NSMM0| LWN2433TCS| LWC243NSMM2| HBLG2350E
---|---|---|---|---|---|---|---|---|---
POWER SUPPLY| 1Ø, 208/230V, 60Hz| 1Ø, 220V, 60Hz| 1Ø, 220V, 60Hz| 1Ø, 208/230V, 60Hz| 1Ø, 220V, 60Hz| 1Ø, 208/230V, 60Hz
COOLING CAPACITY (Btu/h)| 17,500/18,000| 17,500| 18,000| 21,000| 23,500/24,000| 24,000| 24,000| 23,000| 23,000/23.500
INPUT (W)| 1,800/1,850| 1,840| 1,050| 2,470| 2,760/2,820| 2,820| 2,420| 2,540| 2,450/2,500
RUNNING CURRENT (A)| 9.0/8.3| 8.5| 8.3| 10.3| 13.7/12.7| 12.7/12.9| 11.2| 11.5| 12.2/11.3
REFRIGERANT CHARGE (g)| 710(25.1 OZ)| 995(35.1 OZ)/980(34.6 OZ)| 880(31 OZ)| 985(34.7 OZ)
OPERATING

TEMPERATURE

| INDOOR (°C)| 26.7(DB) 19.4(WB)
OUTDOOR (°C)| 35(DB) 23.9(WB)
FAN, INDOOR| BLOWER| TURBO
FAN, OUTDOOR| PROPELLER TYPE FAN WITH SLINGER-RING
FAN SPEEDS, FAN/COOLING| 3/3
FAN MOTOR| 6 POLES
OPERATION CONTROL| TOUCH PANEL
ROOM TEMP. CONTROL| THERMISTOR
AIR DIRECTION CONTROL| VERTICAL LOUVER(RIGHT & LEFT)
HORIZONTAL LOUVER(UP & DOWN)
CONSTRUCTION| SLIDE IN-OUT CHASSIS
PROTECTOR| COMPRESSOR| INTERNAL OVERLOAD PROTECTOR
FAN MOTOR| INTERNAL THERMAL PROTECTOR
POWER CORD| 1.6m (3 WIRE WITH GROUNDING)
ATTACHMENT PLUG(CORD-CONNECTED TYPE)
DRAIN SYSTEM| DRAIN PIPE OR SPLASHED BY FAN SLINGER
NET WEIGHT (lbs/kg)| 120/54| 143/65
OUTSIDE DIMENSION

(W x H x D)

| (inch)| 26 x 1627/32 x 269/16| 26 x 1627/32 x 305/16
(mm)| 660 x 428 x 675| 660 x 428 x 770

  • DB:Dry Bulb WB:Wet Bulb
    NOTE : Specifications are subject to minor change without notice for further improvement.
    1.4 FEATURES**

    • Designed for cooling only.
    • Powerful and quiet cooling.
    • Slide-in and slide-out chassis for the simple installation and service.
    • Reversible inlet grille.

1.5 CONTROL LOCATIONS

  • VENTILATION
    The ventilation lever must be in the CLOSE position in order to maintain the best cooling conditions.
    When a fresh air is necessary in the room, set the ventilation lever to the OPEN position. The damper is opened and room air is exhausted.

NOTE: Before using the ventilation feature, make the lever, as shown. First, pull down part to horizontal line with part .
Precaution: The Remote Control unit will not function properly if strong light strikes the sensor window of the air conditioner or if there are obstacles between the Remote Control unit and the air conditioner.

  1. POWER BUTTON
    Operation starts, when this button is pressed and stops when you press the button again.

  2. OPERATION MODE SELECTION BUTTON
    Select Cooling, or Fan or Dehumidification(Dry) mode with button. (Dry mode is not to all models.)

  3. ON/OFF TIMER BUTTON
    Set the time of starting and stopping operation. The timer is set by 1 hour.

  4. FAN SPEED SELECTOR
    Select the fan speed in three steps.
    – High [F3] ➔ Low[F1] ➔ Med[F2]➔ High[F3]… .

  5. ROOM TEMPERATURE SETTING BUTTON
    Control the room temperature within a range of 60°F to 86°F by 1°F.

  6. ENERGY SAVER(Available In some models)
    The fan stops when the compressor stops cooling. Approximately every 3 minutes the fan will turn on and check the room air to determine if cooling is needed.

  7. AUTO SWING
    Control the horizontal air direction by air swing system.

AUTO RESTART
In case the power comes on again after a power failure, the unit runs as previous setting operation.(Available in some models)

  • Side air-intake, side cooled-air discharge.
  • Built in adjustable THERMISTOR.
  • Washable one-touch filter.
  • Compact size.

LG LWM1836TAS Room Air Conditioner - CONTROL

DISASSEMBLY INSTRUCTIONS

— Before the following disassembly, POWER SWITCH is set to OFF and disconnected the power cord.
2.1 MECHANICAL PARTS
2.1.1 FRONT GRILLE

  1. Open the inlet grille upward or downward.
  2. Remove the screw which fastens the front grille.
  3. Pull the front grille from the right side.
  4. Remove the front grille. (See Fig. 1)
  5. Re-install the component by referring to the removal procedure.
    NOTE: Mark ∆ of inlet grille means opening direction.

2.1.2 CABINET

  1. After disassembling the FRONT GRILLE, remove the screws which fasten the cabinet at both sides.
    Keep these for later use.

  2. Remove the two screws which fasten the cabinet at back. (See Fig. 2)

  3. Pull the base pan forward.

2.1.3 CONTROL BOX

  1. Remove the front grille. (Refer to section 2.1.1)
  2. Pull the base pan forward so that you can remove the 2 screws which fasten the cover control at the right side. (See Fig. 3)
  3. Remove the 3 screws which fasten the control box. (See Fig. 3)
  4. Discharge the capacitor by placing a 20,000 ohm resistor across the capacitor terminals.
  5. Disconnect two wire housings in the control box.
  6. Pull the control box forward completely.
  7. Re-install the components by referring to the removal procedure. (See Fig. 3)LG LWM1836TAS Room Air Conditioner - CONTROL BOX(Refer to the circuit diagram found on page 24 in this manual and on the control box.)

2.2 AIR HANDLING PARTS
2.2.1 COVER (AT THE TOP)

  1. Remove the front grille. (Refer to section 2.1.1)
  2. Remove the cabinet. (Refer to section 2.1.2)
  3. Remove 11 screws which fasten the brace and covers.
  4. Remove the covers and the brace. (See Fig. 4)
  5. Re-install the components by referring to the removal procedure, above.

2.2.2 BLOWER

  1. Remove the cover. (Refer to section 2.2.1)
  2. Remove the 3 screws which fasten the evaporator at the left side and the top side. (See Fig. 4)
  3. Move the evaporator sideward carefully.
  4. Remove the orifice from the air guide carefully.
  5. Remove the clamp spring which is clamped to the boss of blower by hand plier. (See Fig. 5)
  6. Pull the blower outward, without touching blades. (See Fig. 6)
  7. Re-install the components by referring to the removal procedure, above.

2.2.3 FAN

  1. Remove the cabinet. (Refer to section 2.1.2)
  2. Remove the brace and shroud cover. (Refer to section 2.2.1)
  3. Remove the 5 screws which fasten the condenser.
  4. Move the condenser sideways carefully.
  5. Remove the clamp which secures the fan.
  6. Remove the fan. (See Fig. 7)
  7. Re-install the components by referring to the  removal procedure, above.

2.2.4 SHROUD

  1. Remove the fan. (Refer to section 2.2.3)
  2. Remove the 2 screws which fasten the shroud.
  3. Remove the shroud. (See Fig. 8)LG LWM1836TAS Room Air Conditioner - SHROUD
  4. Re-install the component by referring to the removal procedure, above.

2.3 ELECTRICAL PARTS
2.3.1 MOTOR

  1. Remove the cabinet. (Refer to section 2.1.2)
  2. Remove the cover control and disconnect a wire housing in control box. (Refer to section 2.1.3)
  3. Remove the blower. (Refer to section 2.2.2)
  4. Remove the fan. (Refer to section 2.2.3)
  5. Remove the 4 screws which fasten the motor. (See Fig. 9)
  6. Remove the motor.
  7. Re-install the components by referring to the removal procedure, above.

2.3.2 COMPRESSOR

  1. Remove the cabinet. (Refer to section 2.1.2)
  2. Discharge the refrigerant by using a Refrigerant Recovery System.
  3. Disconnect the 3 leads from the compressor.
  4. After purging the unit completely, unbraze the suction and discharge tubes at the compressor connections.
  5. Remove the 3 nuts and the 3 washers which fasten the compressor. (See Fig. 10)
  6. Remove the compressor.
  7. Re-instill the components by referring to the removal procedure, above.

2.3.3 CAPACITOR

  1. Remove the control box. (Refer to section 2.1.3)
  2. Remove the screw which fasten the display panel.
  3. Disconnect the 2 leads from the rocker switch and remove the panel.
  4. Remove a screw and unfold the control box. (See Fig. 11)
  5. Remove the screw and the clamp which fastens the capacitor. (See Fig. 11)
  6. Disconnect all the leads of capacitor terminals.
  7. Re-install the components by referring to the removal procedure, above.

2.3.4 POWER CORD

  1. Remove the control box. (Refer to section 2.1.3)

  2. Unfold the control box. (Refer to section 2.3.3)

  3. Disconnect the grounding screw from the control box.

  4. Disconnect 2 receptacles.

  5. Remove a screw which fastens the clip cord.

  6. Pull the power cord. (See Fig. 12)

  7. Re-install the component by referring to the removal procedure, above.
    (Use only one ground-marked hole for ground connection.)

  8. If the supply cord of this appliance is damaged, it must be replaced by the special cord.
    (The special cord means the cord which has the same specification marked on the supply cord fitted to the unit.)

2.3.5 THERMISTOR

  1. Remove the control box. (Refer to section 2.1.3)
  2. Unfold the control box. (Refer to section 2.3.3)
  3. Disconnect the thermistor terminals from main P.W.B assembly.
  4. Remove the thermistor.
  5. Re-install the components by referring to the removal procedure above. (See Figure 13)LG LWM1836TAS Room Air Conditioner - THERMISTOR

2.3.6 SYNCHRONOUS MOTOR

  1. Remove the control box. (Refer to section 2.1.3)
  2. Unfold the control box. (Refer to section 2.3.3)
  3. Remove the crankshaft.
  4. Disconnect all the leads of the synchronous motor.
  5. Remove the 2 screws which fasten the synchronous motor. (See Fig. 14)
  6. Re-install the components by referring to the removal procedure, above.

2.4 REFRIGERATION CYCLE
CAUTION
Discharge the refrigerant system using Freon Recovery System.
If there is no valve to attach the recovery system, install one (such as a WATCO A-1) before venting the Freon. Leave the valve in place after servicing the system.
2.4.1 CONDENSER

  1. Remove the cabinet. (Refer to section 2.1.2)
  2. Remove the brace and the shroud cover. (Refer to section 2.2.1)
  3. Remove the 5 screws which fasten the condenser.
  4. After discharging the refrigerant completely, unbraze the interconnecting tube at the condenser connections.
  5. Remove the condenser.
  6. Re-install the components by referring to notes. (See Fig. 15)

2.4.2 EVAPORATOR

  1. Remove the cabinet. (Refer to section 2.1.2)
  2. Remove the top cover and the brace. (Refer to section 2.2.1)
  3. Discharge the refrigerant completely.
  4. Remove the 3 screws which fasten the evaporator at the left side and the top side.
  5. Move the evaporator sideward carefully and then unbraze the interconnecting tube at the evaporator connectors.
  6. Remove the evaporator.
  7. Re-install the components by referring to notes. (See Fig. 16)

2.4.3 CAPILLARY TUBE

  1. Remove the cabinet. (Refer to section 2.1.2)
  2. Remove the brace. (Refer to section 2.2.1)
  3. After discharging the refrigerant completely, unbraze the interconnecting tube at the capillary tube.
  4. Remove the capillary tube.
  5. Re-install the components by referring to notes.

LG LWM1836TAS Room Air Conditioner - CONDENSER 1

NOTES
— Replacement of the refrigeration cycle.

  1. When replacing the refrigeration cycle, be sure to discharge the refrigerant system using a Freon recovery System.
    If there is no valve to attach the recovery system, install one (such as a WATCO A-1) before venting the Freon . Leave the valve in place after servicing the system.

  2. After discharging the unit completely, remove the desired component, and unbrace the pinch-off tubes.

  3. Solder service valves into the pinch-off tube ports, leaving the valves open.

  4. Solder the pinch-off tubes with Service valves.

  5. Evacuate as follows.

  1. Connect the vacuum pump, as illustrated Fig. 17A.
  2. Start the vacuum pump, slowly open manifold valves A and B with two full turns counterclockwise and leave the valves closed.
    The vacuum pump is now pulling through valves A and B up to valve C by means of the manifold and entire system.
    CAUTION
    If high vacuum equipment is used, just crack valves A and B for a few minutes, then open slowly with the two full turns counterclockwise.
    This will keep oil from foaming and being drawn into the vacuum pump.
  3. Operate the vacuum pump for 20 to 30 minutes, until 600 microns of vacuum is obtained. Close valves A and B, and observe vacuum gauge for a few minutes. A rise in pressure would indicate a possible leak or moisture remaining in the system. With valves A and B closed, stop the vacuum pump.
    Remove the hose from the vacuum pump and place it on the charging cylinder. See Fig. 17B.
    Open valve C.
    Discharge the line at the manifold connection.
  4. The system is now ready for final charging.
  1. Recharge as follows :
  1. Refrigeration cycle systems are charged from the High-side. If the total charge cannot be put in the High-side, the balance will be put in the suction line through the access valve which you installed as the system was opened.
  2. Connect the charging cylinder as shown in Fig. 17B. With valve C open, discharge the hose at the manifold connection.
  3. Open valve A and allow the proper charge to enter the system. Valve B is still closed.
  4. If more charge is required, the high-side will not take it. Close valve A.
  5. With the unit running, open valve B and add the balance of the charge.
    a. Do not add the liquid refrigerant to the Lowside.
    b. Watch the Low-side gauge; allow pressure to rise to 30 lbs.
    c. Turn off valve B and allow pressure to drop.
    d. Repeat steps B and C until the balance of the charge is in the system.
  6. When satisfied the unit is operating correctly, use the pinch-off tool with the unit still running and clamp on to the pinch-off tube. Using a tube cutter, cut the pinch-off tube about 2 inches from the pinch-off tool. Use sil-fos solder and solder pinch-off tube closed. Turn off the unit, allow it to set for a while, and then test the leakage of the pinch-off connection.

Equipment needed: Vacuum pump, Charging cylinder, Manifold gauge, Brazing equipment. Pinch-off tool capable of making a vapor-proof seal, Leak detector, Tubing cutter, Hand Tools to remove components, Service valve.

LG LWM1836TAS Room Air Conditioner - Equipment needed

INSTALLATION

3.1 HOW TO INSTALL THE UNIT

  1. To avoid vibration and noise, make sure the unit is installed securely and firmly.

  2. Install the unit where the sunlight does not shine directly on the unit.
    If the unit receives direct sunlight, build an awning to shade the cabinet.

  3. There should be no obstacle, like a fence, within 20″ which might restrict heat radiation from the condenser.

  4. To prevent reducing performance, install the unit so that louvers of the cabinet are not blocked.

  5. Install the unit a little obliquely outward not to leak the condensed water into the room (about 1/2″ or 1/4″ bubble with level).

  6. Install the unit with its bottom portion 30~60″ above the floor level.

  7. Stuff the foam between the top of the unit and the wall to prevent air and insects from getting into the room.

  8. The power cord must be connected to an independent circuit. The green wire must be grounded.

  9. Connect the drain tube to the base pan hole in the rear side if you need to drain (consult a dealer). Plastic hose or equivalent may be connected to the drain tube.

3.2 HOW TO USE THE REVERSIBLE INLET GRILLE
The grille is designed to clean the filter both upward and downward.
A. BEFORE ATTACHING THE FRONT GRILLE TO THE CABINET, IF YOU WANT
TO PULL OUT THE FILTER UPWARD;

  1. Open the inlet grille slightly (a).
  2. Turn inside out the front grille (a).
  3. Disassemble the inlet grille from the front grille with separating the hinged part by inserting a straight type screw-driver tip (b).
  4. Then, rotate the inlet grille 180 degrees and insert the hooks into bottom holes of the front grille.
  5. Insert the filter and attach the front grille to the cabinet.
    B. IF YOU WANT TO PULL OUT THE FILTER DOWNWARD;
    The grille is already designed for that way.

LG LWM1836TAS Room Air Conditioner - GRILLE

3.3 WINDOW REQUIREMENTS
NOTE: All supporting parts should be secured to firm wood, masonry, or metal.
The models of the specific area don’t contain installation feit.
3.3.1 WINDOW REQUIREMENTS

  1. This unit is designed for installation in standard double hung windows with actual opening widths from 29″ to 41″.
    The top and bottom window sashes must open sufficiently to allow a clear vertical opening of 18″ from the bottom of the upper sash to the window stool.

  2. The stool offset (height between the stool and sill) must be less than 1 1 /4″.

3.4 INSTALLATION KITS CONTENTS

LG LWM1836TAS Room Air Conditioner - CONTENTS

3.5 SUGGESTED TOOL REQUIREMENTS
SCREWDRIVER(+, -), RULER, KNIFE, HAMMER, PENCIL, LEVEL

  1. Remove the screws which fasten the cabinet at both sides and at the back. Keep these two screws which fasten the cabinet at both sides for later use.
  2. Slide the unit out from the cabinet by gripping the base pan handle and pulling forward while bracing the cabinet.
  3. Cut the window sash seal to the proper length. Peel off the backing and attach the Foam-PE to the underside of the window sash.
  4. Remove the backing from Foam-PE with 3 holes and attach it to the bottom of the Top retainer bar.
  5. Attach the Top retainer bar onto the top of the cabinet with 3 screws (Type A).
  6. Insert the Frame guides into the bottom of the cabinet.LG LWM1836TAS Room Air Conditioner - Curtain
  7. Insert the Frame Curtain into the Top retainer bar and Frame guides.
  8. Fasten the curtains to the unit with 10 screws (Type A) at both sides.

LG LWM1836TAS Room Air Conditioner - Top retainer bar

3.6 CABINET INSTALLATION

  1. Open the window. Mark a line on the center of the window stool between the side window stop moldings.
    Loosely attach the sill bracket to the support bracket using the carriage bolt and the lock nut.LG LWM1836TAS Room Air Conditioner -
CABINET

  2. Attach the sill bracket to the window sill using the screws (Type B).
    Carefully place the cabinet on the window stool and align the center mark on the bottom front with the center line marked window stool.LG LWM1836TAS Room
Air Conditioner - window

  3. Using the M-screw and the lock nut, attach the support bracket to the cabinet track hole. Use the first track hole after the sill bracket on the outer edge of the window sill.
    Tighten the carriage bolt and the lock nut. Be sure the cabinet slants outward.
    CAUTION: Do not drill a hole in the bottom pan. The unit is designed to operate with approximately 1/2″ of water in bottom pan.LG LWM1836TAS Room
Air Conditioner - Front angle

  4. Pull the bottom window sash down behind the Top retainer bar until they meet.LG LWM1836TAS Room Air Conditioner - bottom pan
    NOTE:
    1. Do not pull the window sash down so tightly that the movement of Frame curtain is restricted. Attach the cabinet to the window stool by driving the screws (Type B) through the cabinet into window stool.
    2. The cabinet should be installed with a very slight tilt downward toward the outside.LG LWM1836TAS Room Air Conditioner -
slight

  5. Pull each Frame curtain fully to each window sash  track, and pull the bottom window sash down behind the Top retainer bar until it meets.

  6. Attach each Frame curtain the window sash by using  screws (Type C). (See Fig. 27)LG LWM1836TAS Room Air Conditioner - meets

  7. Slide the unit into the cabinet. (See Fig. 28)LG LWM1836TAS Room Air Conditioner - meets 1 CAUTION: For security purpose, reinstall screws (Type A) at cabinet’s sides.

  8. Cut the Foam-strip to the proper length and insert between the upper window sash and the lower window sash. (See Fig. 29)LG LWM1836TAS Room Air Conditioner - Foam

  9. Attach the Window locking bracket with a screw (Type C). (See Fig. 30)LG LWM1836TAS Room Air Conditioner - locking bracket

  10. Attach the front grille to the cabinet by inserting the tabs on the grille into the tabs on the front of the cabinet. Push the grille in until it snaps into place. (See Fig.31)LG LWM1836TAS Room Air Conditioner - tabs

  11. Lift the inlet grille and secure it with a screw (Type A) through the front grille. (See Fig. 31)

  12. Window installation of room air conditioner is now completed.LG LWM1836TAS Room Air Conditioner - tabs 1

TROUBLESHOOTING GUIDE

4.1 OUTSIDE DIMENSIONS

LG LWM1836TAS Room Air Conditioner - OUTSIDE
DIMENSIONS

4.2 PIPING SYSTEM

LG LWM1836TAS Room Air Conditioner - PIPING SYSTEM

Following is a brief description of the important components and their functions in the refrigeration system.
Refer to Fig. 33 to follow the refrigeration cycle and the flow of the refrigerant in the cooling cycle.

LG LWM1836TAS Room Air Conditioner - ROOM AIR
CONDITIONER

4.3 TROUBLESHOOTING GUIDE
In general, possible trouble is classified in two causes.
The one is called Starting Failure which is caused from an electrical defect, and the other is Ineffective Air
Conditioning caused by a defect in the refrigeration circuit and improper application.
Unit runs but poor cooling

LG LWM1836TAS Room Air Conditioner - poor cooling

LG LWM1836TAS Room Air Conditioner - poor cooling 1

ELECTRIC PARTS TROUBLESHOOTING GUIDE:
Possible Trouble 1

  • The unit does not operate.

LG LWM1836TAS Room Air Conditioner - Possible Trouble

Possible Trouble 2

  • The compressor does not operate.

LG LWM1836TAS Room Air Conditioner - Possible Trouble
3

Possible Trouble 5

  • The function of Energy Saver does not operate.

LG LWM1836TAS Room Air Conditioner - Possible Trouble
5

Possible Trouble 7

  • It displays abnormally on Display P.W.B Ass’y.

LG LWM1836TAS Room Air Conditioner - Possible Trouble
6

ROOM AIR CONDITIONER VOLTAGE LIMITS

NAME PLATE RATING MINIMUM MAXIMUM
208~230 ± 10% 187V 253V
COMPLAINT CAUSE REMEDY
--- --- ---
Fan motor will not run. No power Check voltage at outlet. Correct if none.
Power supply cord Check voltage to rotary switch. If none, check power supply

cord. Replace cord if circuit is open.
Rotary switch| Check switch continuity. Refer to wiring diagram for terminal identification. Replace switch if defective.
Wire disconnected or connection loose| Connect wire. Refer to wiring diagram for terminal identification. Repair or replace loose terminal.
Capacitor (Discharge capacitor before testing.)| Test capacitor. Replace if not within ±10% of manufacturer’s rating. Replace if shorted, open, or damaged.
Will not rotate| Fan blade hitting shroud or blower wheel hitting scroll. Re- align assembly.
Units using slinger ring condenser fans must have 0.22~0.25 inch clearance to the base. If necessary, shim up the bottom of the fan motor with mounting screw(s).
Check fan motor bearings; if motor shaft will not rotate, replace the motor.
Fan motor runs.| Revolves on overload| Check voltage. See limits on this page. If not within limits, call an electrician. Test capacitor. Check bearings. Does the fan blade rotate freely?
If not, replace fan motor. Pay attention to any change from high speed to low speed. If the speed does not change, replace the motor.
COMPLAINT| CAUSE| REMEDY
---|---|---
Fan motor noise.| Fan| If cracked, out of balance, or partially missing, replace it.
Blower| If cracked, out of balance, or partially missing, replace it.
Loose set screw| Tighten it.
Worn bearings| If knocking sounds continue when running or loose, replace the motor. If the motor hums or noise appears to be internal while running, replace motor.
Compressor will not run, fan motor runs.| Voltage| Check voltage. See the limits on the preceding page. If not within limits, call an electrician.
Wiring| Check the wire connections; if loose, repair or replace the terminal. If the wires are disconnected, refer to wiring diagram for identification, and replace the wires. Check the wire connections; If not according to the wiring diagram, correct the connections.
Rotary| Check for continuity, refer to the wiring diagram for terminal identification. Replace the switch if the circuit is open.
Thermistor| Check the TEMP control. If not at the lowest number, set TEMP control to this setting and restart the unit. Check the continuity of the thermistor. Replace the thermistor if the circuit is open.
Capacitor (discharge capacitor before servicing.)| Check the capacitor. Replace if not within ±10% of manufacturer’s rating, replace if shorted, open, or damaged.
Compressor| Check the compressor for open circuit or ground. If open or grounded, replace the compressor.
Overload| Check the compressor overload if externally mounted. Replace if open. (If the compressor temperature is high, remove the overload, cool, and retest.)
Compressor cycles on overload.| Voltage| Check the voltage. See the limits on the preceding page. If voltage is not within these limits, call an electrician.
Overload| Check overload, if externally mounted. Replace if open. (If the compressor temperature is high, remove the overload, cool, and retest.)
COMPLAINT| CAUSE| REMEDY
---|---|---
Compressor cycles on overload.| Fan motor| If not running, determine the cause. Replace if required.
Condenser air flow restriction| Remove the cabinet, inspect the interior surface of the condenser. If restricted, clean carefully with a vacuum cleaner (do not damage fins) or brush. Clean the interior base before re-assembling.
Condenser fins (damaged)| If the condenser fins are closed over a large area on the coil surface, head pressures will increase, causing the compressor to cycle. Straighten the fins or replace the coil.
Capacitor| Test the capacitor.
Wiring| Check the terminals. If loose, repair or replace.
Refrigeration system| Check the system for a restriction.
Insufficient cooling| Air filter| If restricted, clean or replace.
Exhaust damper door| Close if open.
Unit undersized| Determine if the unit is properly sized for the area to be cooled.
Excessive noise| Blower or fan| Check the set screw, or clamp. If loose or miss- ing, correct. If the blower or fan is hitting scroll or barrier, rearrange the air handling parts.
Copper tubing| Remove the cabinet and carefully rearrange the tubing not to contact the cabinet,
compressor, shroud, and barrier.
Auto air-swing fails.| Wiring| Check terminals. If loose, repair or replace.
Synchronous motor.| Check the synchronous motor for open circuit.

SCHEMATIC DIAGRAM

5.1 CIRCUIT DIAGRAM

LG LWM1836TAS Room Air Conditioner - DIAGRAM

NO. DESCRIPTION
1 POWER CORD
2 FAN MOTOR
3 CAPACITOR
4 COMPRESSOR
5 MAIN PWB ASSEMBLY
6 DISPLAY PWB ASSEMBLY
7 THERMISTOR ASSEMBLY
8 CONNECTOR
9 FUSE

5.2. ELECTOINC CONTROL DEVICE
NOTE

  1. The unit of undefined resistors is
  2. The unit of undefined capacitors is uF. ohm, 1/6W, 5%.
    LG LWM1836TAS Room Air Conditioner - DEVICE

5.3. COMPONENTS LOCATION (FOR MAIN P.C.B ASM)
LG LWM1836TAS Room Air Conditioner - . COMPONENTS

5.4. COMPONENTS LOCATION (FOR DISPLAY P.C.B ASM)

LG LWM1836TAS Room Air Conditioner - . COMPONENTS 1

EXPLODED VIEW

LG LWM1836TAS Room Air Conditioner - EXPLODED VIEW

P/NO : 3828A20095H
FEBRUARY, 2008
Copyright ©2007 LG Electronics. Inc.
All right reserved.
Only for training and service purposes

Documents / Resources