SPV340
6LE007485Ab / 1226675-01
PV Surge Protective Device
Installation
Connection
DIN VDE 0100-534IEC 60364-5-53 | A | b | ≤ 0,5 m |
---|---|---|---|
B | a + b | ≤ 0,5 m |
Indoor use only
|
---|---
For use in photovoltaic systems IEC 60364-7-712 (DIN VDE 0100 Part 712)
| |
---|---|---
min.| 1,5 mm²
max.| 25 mm²| 35 mm²
SPV040
Safety instructions
The device may only be connected and installed by an electrically skilled
person. National standards and safety regulations must be observed (see IEC
603647-712:.. (VDE 0100 Part 712:…)).
The device must be checked for external damage prior to installation. If any
damage or other defects are detected in this check, the device must not be
installed. Its use is only permitted within the limits shown and stated in the
installation instructions. The device and the equipment connected to can be
destroyed by loads exceeding the values stated. Opening or otherwise tampering
with the device invalidates the warranty.
Note:
The constructor’s standard IEC 60364-7-712 (DIN VDE 0100 Part 712) recommends
applying protection level II as a protective measure against indirect contact
on the dc side. In this case SPV325 has to be installed in a corresponding
insulating enclosure and connected by connecting cables with double or
reinforced insulation.
Hager Electro S.A.S., Boulevard d’Europe, B.P. 3, 67215 OBERNAI CEDEX, France
– www.hager.com
Hager 05.22
OCOM 144906
6LE007485Ab