FLEX MULTI SPLIT INSTALLATION INSTRUCTIONS

IMPORTANT!
Please read this instruction sheet completely before installing the product. This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.

WARNING

  • Installation or repairs made by unqualified persons can result in hazards to you and others.
    Installation MUST comply with local building codes or, in the absence of local codes, with the National Electrical Code NFPA 70/ANSI C1-1993 or current edition and Canadian Electrical Code Part1 CSA C.22.1.

  • The information contained in this manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.

  • Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, property damage, personal injury and/or death.

CAUTION: Improper installation, adjustment, alteration, service or maintenance can void the warranty. The weight of the condensing unit requires caution and proper handling procedures when lifting or moving to avoid personal injury. Use care to avoid contact with sharp or pointed edges.

Safety Precautions
Always wear safety glasses and work gloves when installing equipment.

  • Never assume electrical power is disconnected. Check with meter and equipment.
  • Keep hands out of fan areas when power is connected to equipment.
  • R-410A causes frostbite burns.
  • R-410A is toxic when burned.

NOTE TO INSTALLING DEALER: The Owners Instructions and Warranty are to be given to the owner or prominently displayed near the indoor Air Handler Unit.

Special warnings

When wiring:
Electrical shock can cause severe personal injury or death. Only a qualified, experienced electrician should attempt to wire this system.

  • Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked. Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death.
  • Ground the unit following local electrical codes.
  • Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.

When transporting:
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.
When installing…

………. in a wall: Make sure the wall is strong enough to hold the unit’s weight.
It may be necessary to construct a strong wood or metal frame to provide added support.
………. in a room: Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to wall and floors.
………. in moist or uneven locations: Use a raised concrete pad or concrete blocks provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration.
………. in an area with high winds: Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
………. in a snowy area(for Heat Pump Model): Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.

When connecting refrigerant tubing

  • Keep all tubing runs as short as possible.
  • Use the flare method for connecting tubing.
  • Check carefully for leaks before starting the test run.

When servicing

  • Turn the power OFF at the main power box(mains) before opening the unit to check or repair electrical parts and wiring.
  • Keep your fingers and clothing away from any moving parts.
  • Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.

P/No: MFL39817310

Required Tools

❏ Level gauge
❏ Screw driver
❏ Electric drill
❏ Hole core drill (ø50mm)

❏ Flaring tool set
❏ Specified torque wrenches 1.8kg.m, 4.2kg.m, 5.5kg.m, 6.6kg.m (different depending on model No.)
❏ Adjustable wrench

❏ A glass of water
❏ Screw driver

❏ Hexagonal wrench(4mm)
❏ Refrigerant Gas Leak Detector
❏ Vacuum pump
❏ Gauge manifold

❏ Owner’s manual
❏ Thermometer
❏ Remote Control Holder

Installation Parts Provided

[Standard /Artcool Mirror Type]

Type 1 Type 2
Installation plate Installation plate
Type “B” screw Type “B” screw
Type “A” screw (6 EA) Type “A” screw (8 EA)
Remote control holder Remote control holder

[Cealing Concealed Duct Type]

Name| Clamp metal| Insulation for fitting| Screws for duct flanges| Clamp| Conduit Bracket
---|---|---|---|---|---
Quantity| 1 EA| 1 set| 1 set| 8 EA| 1 EA
Shape| | | | |

[Cealing Cassette Type]

Name| Drain hose| Clamp metal| Washer for hanging backet| Clamp| Conduit Bracket| Insulation for fitting| Remote control holder
---|---|---|---|---|---|---|---
Quantity| 1 EA| 1 EA| 8 EA| 8 EA| 1 EA| 1 SET| 1 EA
Shape| | | | | | |

Product Introduction

Here is a brief introduction of the indoor and outdoor units. Please see the information specific to your indoor unit type.

Indoor Unit

LG LMU185HV Multi Air Conditioner - Indoor Unit

Outdoor Unit

LG LMU185HV Multi Air Conditioner - Outdoor Unit

Safety Precautions

To prevent the injury of the user or other people and property damage, the following instructions must be followed.
■ Be sure to read before installing the air conditioner.
■ Be sure to observe the cautions specified here as they include important items related to safety.
■ Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications.

WARNING This symbol indicates the possibility of death or serious injury.
CAUTION This symbol indicates the possibility of injury or damage to properties only.

■ The meanings of the symbols used in this manual are as shown below.

| Be sure not to do.
---|---
| Be sure to follow the instruction.

WARNING

■ Installation

Always perform grounding.| Don’t use a power cord, a plug or a loose socket which is damaged.| For installation of the product, always contact the service center or a professional installation agency.
---|---|---
• Otherwise, it may cause electrical shock.| • Otherwise, it may cause a fire or electrical shock.| • Otherwise, it may cause a fire, electrical shock, explosion or injury.
Securely attach the electrical part cover to the indoor unit and the service panel to the
outdoor unit.| Always install an air leakage breaker and a dedicated switching board.| Do not keep or use flammable gases or combustibles near the air conditioner.
• If the electrical part cover of the indoor unit and the service panel of the outdoor unit are not attached securely, it could result
in a fire or electric shock due to dust, water, etc.| • No installation may cause a fire and electrical shock.| • Otherwise, it may cause a fire or the failure of product.
Ensure that an installation frame of the outdoor unit is not damaged due to use for a long time.| Do not disassemble or repair the product randomly.
---|---
• It may cause injury or an accident.| • It will cause a fire or electrical shock.
Do not install the product at a place that there is concern of falling down.| Use caution when unpacking and installing.
---|---
• Otherwise, it may result in personal injury.| • Sharp edges may cause injury.

■ Operation

Do not share the outlet with other appliances.| Do not use the damaged power cord.| Do not modify or extend the power cord randomly.
---|---|---
• It will cause an electric shock or a fire due to heat
generation.| • Otherwise, it may cause a fire or electrical shock.| • Otherwise, it may cause a fire or electrical shock.
Take care so that the power cord may not be pulled during operation.| Unplug the unit if strange sounds, smell, or smoke comes from it.| Keep the flames away.
• Otherwise, it may cause a fire or electrical shock.| • Otherwise, it may cause electrical shock or a fire.| • Otherwise, it may cause a fire.
Take the power plug out if necessary, holding the head of the plug and do not touch it with wet hands.| Do not use the power cord near the heating tools.| Do not open the suction inlet of the indoor/outdoor
unit during operation.
• Otherwise, it may cause a fire or electrical shock.| • Otherwise, it may cause a fire and electrical shock.| • Otherwise, it may electrical shock and failure.
Do not allow water to run into electrical parts.| Hold the plug by the head when taking it out.| Never touch the metal parts of the unit when removing
the filter.
• Otherwise, it may cause the failure of machine or electrical shock.| • It may cause electric shock and damage.| • They are sharp and may cause injury.
Do not step on the indoor/outdoor unit and do not put anything on it.| Do not place a heavy object on the power cord.
---|---
• It may cause an injury through dropping of the unit or falling down.| • Otherwise, it may cause a fire or electrical shock.
When the product is submerged into water, always contact the service center.| Take care so that children may not step on the outdoor unit.
• Otherwise, it may cause a fire or electrical shock.| • Otherwise, children may be seriously injured due to falling down.

CAUTION

■ Installation

Install the drain hose to ensure that drain can be securely done.| Install the product so that the noise or hot wind from the outdoor unit may not cause any damage to the neighbors.
---|---
• Otherwise, it may cause water leakage.| • Otherwise, it may cause dispute with the neighbors.
Always inspect gas leakage after the installation and repair of product.| Keep level parallel in installing the product.
• Otherwise, it may cause the failure of product.| • Otherwise, it may cause vibration or water leakage.

■ Operation

Avoid excessive cooling and perform ventilation sometimes.| Use a soft cloth to clean. Do not use wax, thinner, or a strong detergent.
---|---
• Otherwise, it may do harm to your health.| • The appearance of the air conditioner may deteriorate, change color, or develop surface flaws.
Do not use an appliance for special purposes such as preserving animals vegetables, precision machine, or art articles.| Do not place obstacles around the flow inlet or outlet.
• Otherwise, it may damage your properties.| • Otherwise, it may cause the failure of appliance or an accident.

Installation of Indoor, Outdoor Unit

Read completely, then follow step by step.

Select the best location
Indoor unit

  1. Do not have any heat or steam near the unit.
  2. Select a place where there are no obstacles in front of the unit.
  3. Make sure that condensation drainage can be conveniently routed away.
  4. Do not install near a doorway.
  5. Ensure the unit is unobstructed, allow proper space on all sides according to the arrows and distance measurements in the figures.
  6. Use a Metal Detector or Metal Scanner to locate studs to prevent unnecessary damage to the wall.

LG LMU185HV Multi Air Conditioner - Artcool Mirror
TypeLG LMU185HV Multi Air Conditioner -
Cealing Concealed Duct Type

Capacity(Btu/h class) AB B
9/12k 600(23 5/8) 900(35 15/32)
18k 600(23 5/8) 1100(43 5/16)

[Cealing Cassette Type]LG LMU185HV Multi Air Conditioner - Cealing
Cassette Type

Outdoor unit

  1. If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radiation from the condenser is not restricted.
  2. Ensure the unit is unobstructed, allow proper space on all sides according to the arrows and distance measurements in the figures.
  3. Do not place animals and plants in the path of the warm air.
  4. Take the air conditioner weight into account and select a place where noise and vibration are minimum.
  5. Select a place so that the warm air and sound from the air conditioner does not disturb neighbors.

LG LMU185HV Multi Air Conditioner - Outdoor unit 2

Rooftop Installations:
If the outdoor unit is installed on a roof structure, be sure to level the unit. Ensure the roof structure and anchoring method are adequate for the unit location. Consult local codes regarding rooftop mounting.

Seaside Applications and Installation

CAUTION

  1. Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas, are produced.
  2. Do not install the product where it could be exposed to sea wind (salty wind) directly. It can result corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient performance.
  3. If outdoor unit is installed close to the seaside, it should avoid direct exposure to the sea wind.

1. Selecting the location(Outdoor Unit)

  1. If the outdoor unit is to be installed close to the seaside, direct exposure to the sea wind should be avoided. Install the outdoor unit on the opposite side of the sea wind direction.LG LMU185HV Multi Air Conditioner - Selecting the location

  2. In case, to install the outdoor unit on the seaside, set up a windbreaker/barrier, to lessen the unit’s exposure to sea airLG LMU185HV Multi Air Conditioner - outdoor unit on the seaside• It should be strong enough (like concrete) to obstruct the wind from the sea.
    • The height and width should be more than 150% of the outdoor unit.
    • A minimum of 70cm (27 1/16 inches) of space between outdoor unit and the windbreak for easy air flow.

  3. Select a well-drained place.

Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat exchanger using water is recommended.

Piping length and elevation

Multi Piping Type
Unit : m(ft)

Outdoor Unit Capacity
(Btu/h class)| Max total length of all pipes(A+B)/(A+B+C) / (A+B+C+D)| Max length of each pipe (A/B/C/D)| Min length of each pipe (A/B/C/D)| Max Elevation between each indoor unit and outdoor unit (h1)| Max elevation between indoor units (h2)| Max.Combination of Indoor unit
(Btu/h class)
---|---|---|---|---|---|---
18k| 50(164)| 25(82)| 3(10)| 15(49)| 7.5(25)| 24k
24k| 75(246)| 25(82)| 3(10)| 15(49)| 7.5(25)| 33k
36k| 75(246)| 25(82)| 3(10)| 15(49)| 7.5(25)| 48k
Indoor unit Capacity
(Btu/h class)| Pipe Diameter
Unit : mm(inch)| Standard Pipe Length
Unit: m(ft)| Additional Refrigerant
Unit: g/m(oz/ft)
---|---|---|---
Gas| Liquid
9k| 9.52(3/8)| 6.35(1/4)| 7.5(25)| 20(0.22)
12k| 9.52(3/8)| 6.35(1/4)| 7.5(25)| 20(0.22)
18k| 12.7(1/2)| 6.35(1/4)| 7.5(25)| 20(0.22)

LG LMU185HV Multi Air Conditioner - Multi Piping Type

CAUTION: Capacity is based on standard length and maximum allowance length is on the basis of reliability.

Installation

[Standard /Artcool Mirror Type]
Connecting the piping

  1. Prepare the indoor unit’s piping and drain hose for installation through the wall.

  2. Remove the plastic tubing retainer(see the illustration on the right) and pull the tubing and drain hose away from chassis.

  3. Route the indoor tubing and the drain hose to the required piping hole position.

  4. Insert the piping, drain hose, and the connecting cable into the piping hole.

  5. Insert the connecting cable into the indoor unit.
    • Don’t connect the cable to the indoor unit.
    • Make a small loop with the cable for easy connection later.

  6. Tape the drain hose and the connecting cables.LG LMU185HV Multi Air Conditioner - Connecting the piping

  7. Indoor unit installation
    • Hang the indoor unit from the hooks at the top of the installation plate.
    • Insert the spacer etc. between the indoor unit and the installation plate and separate the bottom of the indoor unit from the wall.LG LMU185HV Multi
Air Conditioner - Indoor unit installation

  8. Connecting the piping to the indoor unit and drain hose to drain pipe.LG LMU185HV Multi Air Conditioner - Connecting the piping 21) Align the center of the pipes and sufficiently tighten the flare nut by hand.

  1. Tighten the flare nut with a wrench.Outside diameter Torque
    mm inch
    Ø6.35 1/4
    Ø9.52 3/8
    Ø12.7 1/2
  2. Next, extend the indoor unit’s drain hose. Then attach the drain pipe.
    CAUTION:
    Installation Information. For left piping. Follow the instruction below.
    Good case
    • Press on the upper side of clamp and unfold the tubing to slowly downward.LG LMU185HV Multi Air Conditioner - Good case Bad case
    • Bending the pipe from right to left may cause damage to the tubing.LG
LMU185HV Multi Air Conditioner - Bad case

  1. Wrap the insulation material around the connecting portion.
  1. Overlap the connection pipe insulation and the indoor unit pipe heat insulation material. Bind them together with vinyl tape so that there is no gap.
  2. Wrap the area which accommodates the rear piping housing section with vinyl tape.LG LMU185HV Multi Air Conditioner - connecting
portion3) Bundle the piping and drain hose together by wrapping them with vinyl tape over the range within which they fit into the rear piping housing section.LG LMU185HV Multi Air Conditioner -
piping and drain hose
  1. Reroute the pipings and the drain hose across the back of the chassis.LG LMU185HV Multi Air Conditioner - Reroute the pipings and the drain
  2. Indoor unit installation
    LG LMU185HV Multi Air Conditioner - Indoor unit installation
21) Remove the spacer.
  1. Ensure that the hooks are properly seated on the installation plate by moving it left and right.
  2. Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots (clicking sound).

How To Fix
The wall you select should be strong and solid enough to prevent vibration

  1. Mount the installation plate on the wall with type “A” screws. If mounting the unit on a concrete wall, use anchor bolts.
    • Mount the installation plate horizontally by aligning the centerline using a level.

  2. Measure the wall and mark the centerline. It is also important to use caution concerning the location of the installation plate-routing of the wiring to power outlets is through the walls typically. Drilling the hole through the wall for piping connections must be done safely.

LG LMU185HV Multi Air Conditioner - How To Fix

Wiring Connection

  1. Connect the wires to the terminals on the control board individually according to the outdoor unit connection.
    • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively.LG LMU185HV Multi Air
Conditioner - Connected to Outdoor Unit

  2. Attach the Grille onto the cabinet.
    • Grasp the lower left and right side of the Grille and engage four tabs on the top inside edge of the chassis.
    • Press the Grille toward the chassis until it goes back into place.

LG LMU185HV Multi Air Conditioner - Wiring Connection

Conduit connection

  1. Set the connecting cable into the terminal block of indoor unit, and tighten set screw to lock the conduit bracket to the indoor unit.
  2. Join the conduit and the conduit bracket together.

LG LMU185HV Multi Air Conditioner - Conduit connection

[Cealing Concealed Duct Type]
Ceiling dimension and hanging bolt location

Installation of Unit
Install the unit above the ceiling correctly.

CASE 1
POSITION OF SUSPENSION BOLT

  • Apply a joint-canvas between the unit and duct to absorb unnecessary vibration.
  • Apply a filter Accessory at air return hole.

Unit:mm(inch)

Dimension
Capacity Btu/h class| A| B| C| D| E| F| G| H| I
---|---|---|---|---|---|---|---|---|---
9/12k| 850
(33 15/32)| 900
(35 15/32)| 383
(15 3/32)| 570
(22 7/16)| 93.5
(3 11/16)| 190
(7 1/2)| 20.6
(13/16)| 795
(31 5/16)| 163
(6 13/32)
18k| 1130
(44 1/2)| 1180
(46 1/2)| 383
(15 3/32)| 570
(22 7/16)| 93.5
(3 11/16)| 190
(7 1/2)| 20.6
(13/16)| 1065
(41 15/16)| 163
(6 13/32)

LG LMU185HV Multi Air Conditioner - Drainage hole

CASE 2

  • Install the unit leaning to a drainage hole side as a figure for easy water drainage.

POSITION OF CONSOLE BOLT

  • A place where the unit will be leveled and that can support the weight of the unit.
  • A place where the unit can withstand its vibration.
  • A place where service can be easily performed.

LG LMU185HV Multi Air Conditioner - POSITION OF CONSOLE
BOLT

How to Fix

  • Select and mark the position for fixing bolts.
  • Drill the hole for set anchor on the face of ceiling.

LG LMU185HV Multi Air Conditioner - set anchor

  • Insert the set anchor and washer onto the suspension bolts for locking the suspension bolts on the ceiling.
  • Mount the suspension bolts to the set anchor firmly.
  • Secure the installation plates onto the suspension bolts (adjust level roughly) using nuts, washers and spring washers.

LG LMU185HV Multi Air Conditioner - building

CAUTION : Tighten the nut and bolt to prevent unit falling.

Wiring Connection
Connect the wires to the terminals on the control board individually according to the outdoor unit connection.

  • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively.

B1/B2 Series

Conduit connection

  1. Remove the busing rubber product attached on the indoor unit.
  2. Set the connecting cable into the terminal block of indoor unit, and tighten set screw to lock the conduit bracket to the indoor unit.
  3. Join the conduit and the conduit bracket together.

LG LMU185HV Multi Air Conditioner - Conduit connection
2

CAUTION

  1. Install declination of the indoor unit is very important for the drain of the duct type air conditioner.
  2. Minimum thickness of the insulation for the connecting pipe shall be 19mm(1/32 inch).

Front of view

  • The unit must be horizontal or declined to the drain hose connected when finished installation.

LG LMU185HV Multi Air Conditioner - Front of view

INSULATION, OTHERS
Insulate the joint and tubes completely.

THERMAL INSULATION
All thermal insulation must comply with local requirement.

INDOOR UNIT

LG LMU185HV Multi Air Conditioner - INDOOR UNIT 2

TEST AND CHECK
■ After all workings are finished, check the working and operation.

  • Air distribution …………… Is the air circulation good?
  • Drain ……………………….. Is the drainage smoothly and no sweating?
  • Gas leakage …………….. Is the piping connection correctly?
  • Wiring ……………………… Is the wiring connection correctly?
  • Lock-bolt ………………….. Is the lock-bolt of compressor loosened?
  • Insulation………………….. Is the unit fully insulated?
  • Ground …………………….. Is the unit safely grounded?

Installation of wired Remote Controller

  1. Put the installation paper on the place and determine the position and height of the fixing screws of the wired remote controller.
    • Refer to the printed side of the installation paper.

  2. Plug the connecting cable into the indoor unit.
    • The product is being shipped with the cable connected only to the remote controller.
    Fix the connecting cable with the cable rack.LG LMU185HV Multi Air
Conditioner - connecting cable

  3. Remove the installation paper before installing the remote controller so that it can fit at the right place.LG LMU185HV Multi Air Conditioner - remote controller* Do not embed the remote controller into the wall. (It may cause the breakdown of the temperature sensor.)

  • If you want to install a number of remote controller at the same place in a vertical line, install them at regular intervals of 20mm(1/32 inch).
    (It may cause the breakdown of the temperature sensor.)
  • Do not install the cable with a distance of 50m(164ft) or longer.
    (This can cause communication error.)
  • When installing the cable, check whether the connector between the remote controller and the product is installed properly. The connector will not be connected when installed in opposite sides.

❏ Supply the power after connecting wired remote controller.
When you need to change wired remote controller, switch off the main power and change it.
If the wired remote controller is changed before switching off the main power, the option function of the indoor unit can’t be used. (option function like “slo” fan speed selection)

Wired remote controller switch informationLG LMU185HV Multi Air
Conditioner - Wired remote controller switch information

Group control switch

  1. For individual control/Master use
  2. For group control/Slave use

Ceiling height selection switch

  1. Low ceiling
  2. Standard ceiling
  3. High ceiling

Product selection switch

  1. Cooling Only product
  2. Heat Pump product

Indoor temperature sensor selection switch

  1. Use the temperature sensor on the remote controller.
  2. Use the temperature sensor on the product.
  3. Use the sensors on the product and remote controller.
  • When changing the product selection switch and group control switch, the power must be reconnected to reflect the changes.
  • The central control could operate inappropriately depends on indoor unit type, when the remote controller is set as slave.

■ Necessary functions before using
Trial Operation

The trial operation is to check the installation status of the product. The temperature will not be controlled during trial operation. Instead the product will operate in several modes such as cooling, strong wind, comp-on.LG
LMU185HV Multi Air Conditioner - Trial Operation

Celsius/Fahrenheit Switching

LG LMU185HV Multi Air Conditioner - Fahrenheit
Switching

Setting the Central-Control Address
Please set the address while using the central controller.
You don’t need to set address if you don’t use central controller.

LG LMU185HV Multi Air Conditioner - Central-Control
Address

  • If you connect the indoor unit to the central controller, you should set the network address of the indoor unit so that the central controller could recognize it.
  • The center-control address is composed of the group number and the indoor-unit number.

Note: The remote controller displays ‘HL’ if central controller has locked the remote controller .

ESP Function
E.S.P function is setting the volume of each fan speed. It is for the convenience of installation. It is recommended that you should not use this function while using the remote controller.

LG LMU185HV Multi Air Conditioner - ESP Function

❈ The E.S.P value is set at the proper value at the factory. So it is highly recommended that you should not change the E.S.P value at your discretion.

Static pressure(mmAq) 0 1 2 3 4
Model name Step(H/WL) Setting value

AMNWO9GB1A0
[LMDN095FIV]| 8.5 CMM(300cfm)| 75| 84| 94| 104| 114
7.5 CMM(265cfm)| 69| 77| 88| 99| 110
6.5 CMM(230cfm)| 62| 71| 83| 95| 106
AMNW12GB1A0
[LMDN125HV]| 9.5 CMM(336cfm)| 82| 90| 99| 109| 118
8.5 CMM(300cfm)| 75| 84| 94| 104| 114
7.5 CMM(265cfm)| 69| 77| 88| 99| 110
AMNW180132A0
[LMDN185HV]| 15 CMM(530cfm)| 90| 97| 105| 114| 122
13.5 CMM(477cfm)| 82| 90| 99| 109| 119
11.5 CMM(406cfm)| 75| 84| 93| 103| 114

[Cealing Cassette Type]
Ceiling dimension and hanging bolt location

  • The dimensions of the paper model for installation are the same as those of the ceiling opening dimensions.LG LMU185HV Multi Air Conditioner - Ceiling dimension CAUTION:
    • This air-conditioner uses a drain pump.
    • Install the unit horizontally using a level gauge.
    • During the installation, care should be taken not to damage electric wires.

  • Select and mark the position for fixing bolts and piping hole.

  • Decide the position for fixing bolts slightly tilted to the drain direction after considering the direction of drain hose.

  • Drill the hole for anchor bolt on the wall.

NOTICE

• Avoid the following installation location.

  1. Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated.
    These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function.
    In these cases, take the following actions;
    • Make sure that ventilation fan is enough to cover all noxious gases from this place.
    • Ensure enough distance from the cooking room to install the air conditioner in such a place where it may not suck oily steam.LG LMU185HV Multi Air
Conditioner - restaurants and kitchen

  2. Avoid installng air conditioner in such places where cooking oil or iron powder is generated.

  3. Avoid places where inflammable gas is generated.

  4. Avoid place where noxious gas is generated.

  5. Avoid places near high frequency generators.

How to Fix

LG LMU185HV Multi Air Conditioner - How to Fix 2

  • The following parts are local purchasing.
    ① Hanging Bolt – W 3/8 or M10
    ② Nut – W 3/8 or M10
    ③ Spring Washer – M10
    ④ Plate Washer – M10

CAUTION : Tighten the nut and bolt to prevent unit from falling off.

Wiring Connection

  • Open the control box cover and connect the remote control cord and indoor power wires.

TQ/TR series

Conduit connection

  • Remove the busing rubber product attached on the indoor unit.
  • Join the conduit and the conduit bracket together using nut.
  • Set the connecting cable into the terminal block of indoor unit, and tighten set screw to lock the conduit bracket to the indoor unit.

LG LMU185HV Multi Air Conditioner - Conduit connection
3

Installation of Wired Remote Controller(Optional)

  1. Connect the wired remote controller cable to the wired remote controller installation board as shown in the right picture.
    12V| Red wire
    ---|---
    SIG| Yellow wire
    GND| Black wire

LG LMU185HV Multi Air Conditioner - wired remote controller
cable❊ The wired remote controller cable is connected as factory default.

  1. After fixing the cable to the guide slot, attach the wired remote controller installation board at the desired location.
    • Before fixing the wired remote controller cable to the guide slot, remove any clogged part of the case in the direction to install before the installation.LG LMU185HV Multi Air Conditioner - controller cable is
connected

  2. After locating the wired remote controller installation board at the desired location, screw the unit firmly.
    (When there is a buried box, install the wired remote controller board to fit the buried box.)
    • Use the screw provided.LG LMU185HV Multi Air Conditioner - fixing the
cable to the guide slot

  3. After fixing the top part of the wired remote controller to the installation board as shown in beside picture, press the bottom part to assemble the controller to it’s board.LG LMU185HV Multi Air Conditioner - locating the wired remoteWhen disassemble the wired remote controller from the installation board, use the driver as shown in the right picture and insert it into the hole with the arrow. And when you pull the driver in the front direction, the wired remote controller will be separated.

  4. Use the connecting cable to connect the indoor unit and the wired remote controller.LG LMU185HV Multi Air Conditioner - connecting cable to connect

  5. When the distance between the wired remote controller and the indoor unit is 10m and above, use the extension cable.

CAUTION
When installing the wired remote controller, do not bury it in the wall.
(It can cause damage in the temperature sensor.)
Do not install the cable to be 50m or above.
(It can cause communication error.)

  • When installing the extension cable, check the connecting direction of the connector of the remote controller side and the product side for correct installation.
  • If you install the extension cable in the opposite direction, the connector will not be connected.
  • Specification of extension cable: 2547 1007 22# 2 core 3 shield 5 or above.

Installation of Decorative Panel

The decorative panel has its installation direction.
Before installing the decorative panel, always remove the paper template.

  1. Remove the packing and take out air inlet grille from front panel.LG LMU185HV Multi Air Conditioner - Front grille

  2. Remove the Corner covers of the panel.LG LMU185HV Multi Air Conditioner - Coner cover

  3. Fit the panel on the unit by inserting hooks as shown in picture.LG LMU185HV Multi Air Conditioner - Hook clip

  4. Insert two screws on diagonal corners of panel. Do not tighten the bolts completely.
    (The fixing screws are included in the indoor unit box.)
    Check the alignment of panel with the ceiling. Height can be adjusted using hanging bolts as shown in picture. Insert the other two screws and tighten all screws completely.LG LMU185HV Multi Air Conditioner - fixing screws are
included

  5. Fit the corner covers.

  6. Open two screws of control panel cover.

  7. Connect one display connector and two vane control connectors of front panel to indoor unit PCB.
    The position marking on PCB is as:
    Display connector : CN-DISPLAY
    Vane control connector: CN-VANE 1,2

  8. Close the cover for control box.

  9. Install the air inlet grille and Filter on the panel.

CAUTION: Install certainly the decorative panel.
Cool air leakage causes sweating. Water drops fall.

LG LMU185HV Multi Air Conditioner - leakage causes
sweating

HEAT INSULATION

  1. Use the heat insulation material for the refrigerant piping which has an excellent heatresistance [over 120°C(248°F)].
  2. Precautions in high humidity circumstance:
    This air conditioner has been tested according to the “KS Standard Conditions with Mist” and confirmed that there is not any default. However, if it is operated for a long time in high humid atmosphere [dew point temperature: more than 23°C(73.4°F)], water drops are liable to fall. In this case, add heat insulation material according to the following procedure:LG LMU185HV Multi
Air Conditioner - HEAT INSULATION• Heat insulation material to be prepared… Adiabatic glass wool with thickness 10 to 20mm.
    • Stick glass wool on all air conditioners that are located in ceiling atmosphere.

Drain Piping
[Standard /Artcool Mirror Type]

  1. The drain hose should point downward for optimum drainage.
  2. Incorrect Installation Examples:LG LMU185HV Multi Air Conditioner - Incorrect Installation Examples

[Cealing Concealed Duct/Cealing Cassette Type]

  • Drain piping must have down-slope (1/50 to 1/100): be sure not to provide up-and-down slope to prevent reversal flow.

  • During drain piping connection, be careful not to exert extra force on the drain port on the indoor unit.

  • The outside diameter of the drain connection on the indoor unit is 32mm(1 1/4 inch).
    Piping material: Polyvinyl chloride pipe inner diometes Ø 25mm(1 inch) and pipe fittings

  • Be sure to install heat insulation on the drain piping.
    Heat insulation material: Polyethylene foam with thickness more than 8mm(5/16 inch).

Drain test
The air conditioner uses a drain pump to drain water.
Use the following procedure to test the drain pump operation:

  • Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end.
  • Feed water to the flexible drain hose and check the piping for leakage.
  • Be sure to check the drain pump for normal operating and noise when electrical wiring is complete.
  • When the test is complete, connect the flexible drain hose to the drain port on the indoor unit.

LG LMU185HV Multi Air Conditioner - Drain test

CAUTION : The supplied flexible drain hose should not be curved, neither screwed. The curved or screwed hose may cause a leakage of water.

LG LMU185HV Multi Air Conditioner - neither screwed

Attention

  1. Possible drain-head height is up to 700mm(27 9/16 inch). So, it must be installed below 700mm(27 9/16 inch).LG LMU185HV Multi Air Conditioner - drain-head height

  2. Keep the drain hose downward up to 1/50~1/100 inclination.
    Prevent any upward flow or reverse flow in any part.

  3. 5mm(3/16 inch) or thicker formed thermal insulator is provided for the drain pipe.LG LMU185HV Multi Air Conditioner - thicker formed thermal

  4. Upward routing is not allowed.
    LG LMU185HV Multi Air Conditioner - check the drain
pump

  5. Be sure to check the drain pump for normal operation and abnormal noise when electrical wiring is complete.

Flaring Work and Connection of Piping

Flaring work
Main cause of gas leakage is defect in flaring work. Carry out correct flaring work in the following procedure.

  1. Cut the pipes and the cable.
    ■ Use the accessory piping kit or the pipes purchased locally.
    ■ Measure the distance between the indoor and the outdoor unit.
    ■ Cut the pipes a little longer than measured distance.
    ■ Cut the cable 1.5m(4.9ft) longer than the pipe length.LG LMU185HV Multi
Air Conditioner - Cut the pipes and the cable

  2. Burrs removal
    ■ Completely remove all burrs from the cut cross section of pipe/tube.
    ■ Put the end of the copper tube/pipe to downward direction as you remove burrs in order to avoid to let burrs drop in the tubing.

  3. Putting nut on
    ■ Remove flare nuts attached to indoor and outdoor units, than put them on pipe/tube having completed burr removal.
    (Not possible to put them on after flaring work)

  4. Flaring work
    ■ Carry out flaring work using flaring tool as shown below.Outside diameter| A
    ---|---
    mm| inch| mm| inch
    Ø6.35| 1/4| 1.1~1.3| 0.04~0.05
    Ø9.52| 3/8| 1.5~1.7| 0.06~0.07
    Ø12.7| 1/2| 1.6~1.8| 0.06~0.07

Firmly hold copper tube in a bar(or die) as indicated dimension in the table above.

  1. Check
    LG LMU185HV Multi Air Conditioner - Check ■ Compare the flared work with figure.
    ■ If flare is noted to be defective, cut off the flared section and do flaring work again.

Connection of piping – Outdoor

Align the center of the piping and sufficiently tighten the flare nut by hand.
Connecting pipe order

  1. A~D-UNIT gas side pipe
  2. A~D-UNIT liquid side pipe

LG LMU185HV Multi Air Conditioner - Connection of
piping

Finally, tighten the flare nut with torque wrench until the wrench clicks.

  • When tightening the flare nut with torque wrench ensure the direction for tightening follows the arrow on the wrench.
Outside diameter Torque
mm inch
Ø6.35 1/4
Ø9.52 3/8
Ø12.7 1/2

LG LMU185HV Multi Air Conditioner - tightening the
flare| LG LMU185HV Multi Air Conditioner -
Outdoor unit 3
---|---

Connecting the Cable between Indoor Unit and Outdoor Unit

Connect the cable to the Indoor unit.
Connect the cable to the indoor unit by connecting the wires to the terminals on the control board individually according to the outdoor unit connection. (Ensure that the color of the wires of the outdoor unit and the terminal No. are the same as those of the indoor unit.)
The ground wire should be longer than the common wires.
The circuit diagram is not subject to change without notice.
When installing, refer to the electrical diagram behind the front panel of Indoor Unit.
The wiring for the outdoor unit can be found on the inside of the Outdoor Unit control cover.

RECOMMENDATION:

  • The circuit diagram is subject to change without notice.
  • Be sure to connect wires according to the wiring diagram.
  • Connect the wires firmly, so that they can not be pulled out easily.
  • Connect the wires according to color codes by referring to the wiring diagram.

RECOMMENDATION: Provide a circuit breaker between power source and the outdoor unit as shown below.

Outdoor Unit Capacity (Btu/h class) Power source Fuse or breaker Capacity
18k 1ø,208/230V 15A
24k 1ø,208/230V 25A
36k 1ø,208/230V 25A

LG LMU185HV Multi Air Conditioner - Main power source

RECOMMENDATION: The power cord connected to the outdoor unit should be comply with the following specifications: ETL recognized and CSA certified.

LG LMU185HV Multi Air Conditioner - RECOMMENDATION

The power connecting cable connected to the indoor and outdoor unit should be comply with the following specifications: ETL recognized and CSA certified.

RECOMMENDATION: When using the separate wires as the power cord, please secure the separate wires into the control box panel using tie wraps to hold all wires together in place.

Connect the cable to the Outdoor unit.

  1. Remove the control cover from the unit by loosening the screw. Connect the wires to the terminals on the control board individually as the following.
  2. Secure the cable onto the control board with the holder (clamper).
  3. Re-attach the cover control to the original position using the screws.

LG LMU185HV Multi Air Conditioner - Outdoor unit 4

18kBtu/h class

LG LMU185HV Multi Air Conditioner - Connect the cable to the Outdoor
unit

24/36 kBtu/h class

LG LMU185HV Multi Air Conditioner - Connect the cable to the Outdoor unit
2

NOTICE :

  1. Separately wire the high and low voltage lines.
  2. Use heat resistant electrical wiring capable of withstanding temperatures up to 75°C(167°F).
  3. Use outdoor waterproof connection cable rated for at least 300V for the connection between indoor and outdoor unit. (For example, Type SJO-WA)

WARNING:

  • Be sure to comply with local and national codes while running the wire from the indoor unit to the outdoor unit(size of wire and wiring method, etc).
  • Every wire must be connected firmly.
  • No wire should be allowed to touch refrigerant tubing, the compressor or any moving parts.

Connection method of the connecting cable (Example)

  1. Remove two-caps on the conduit panel. (for low voltage line)
  2. Pull out connection cable through conduit.
  3. After conduit to the panel, fix nut to the opposite side of panel.
  4. Pass the connection cabel through the hole.
  5. Properly connect the cable on the terminal block.
  6. Fix the connection cable with cord clamp provided on the unit not to have strain at the terminal when the connection cable is pulled outside up to a 35 pound weight

LG LMU185HV Multi Air Conditioner - Connection method

WARNING: Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard may also exist. Therefore, be sure all wiring is tightly connected.

When connecting each power wire to the corresponding terminal, follow instructions “How to connect wiring to the terminals” and fasten the wire tightly with the fixing screw of the terminal plate.

How to connect wiring to the terminals
◼ For strand wiring

  1. Cut the wire end with a wire cutter or wire-cutting pliers, then strip the insulation to expose the strand wiring about 10 mm(3/8″).
  2. Using a screwdriver, remove the terminal screw(s) on the terminal plate.
  3. Using a round terminal fastener or pliers, securely clamp each stripped wire end with a round terminal.
  4. Position the round terminal wire, and replace and tighten the terminal screw using a screwdriver.

Power supply cableLG LMU185HV Multi Air Conditioner - Power supply
cable

Connecting Cable

LG LMU185HV Multi Air Conditioner - Connecting Cable 2

Checking the Drainage, Insulating the Pipe and Special Piping

Applications

Checking the drainage

  1. Remove the Air Filter.LG LMU185HV Multi Air Conditioner - Remove the Air Filter
  2. Check the drainage.
    • Spray one or two glasses of water upon the evaporator.
    • Ensure that water flows drain hose of indoor unit without any leakage.
    LG LMU185HV Multi Air Conditioner - Check the drainage❈ The figure can be changed according to model.

Insulating the Pipe and Special Piping Applications

Insulate the piping by wrapping the connecting portion of the indoor unit with insulation material and secure it with two kinds of vinyl tape.

  • If you want to connect an additional drain hose, the end of the drain outlet should be routed above the ground. Secure the drain hose appropriately.

LG LMU185HV Multi Air Conditioner - Pipe and Special
Piping

In cases where the outdoor unit is installed below the indoor unit perform the following:

  1. Tape the piping, drain hose and connecting cable from down to up.
  2. Secure the taped piping along the exterior wall using saddle or equivalent.

In cases where the Outdoor unit is installed above the Indoor unit perform the following.

  1. Tape the piping and connecting cable from down to up.
  2. Secure the taped piping along the exterior wall. Form a trap to prevent water entering the room.
  3. Secure the piping onto the wall using a saddle or equivalent.

LG LMU185HV Multi Air Conditioner - cases where the Outdoor
unit

Long Pipe Setting

  1. Open the top cover of outdoor unit.
  2. Select one of the two selectable modes as follows.
  3. Set the Zone as shown in Fig.
  4. Close the top cover and check whether the product works normally.

WARNING: Do not open the top cover or Set the pipe length when operating the product.LG LMU185HV Multi Air Conditioner - Long Pipe
Setting

Air Purging and Evacuation

Air and moisture remaining in the refrigerant system have undesirable effects as indicated below.

  1. Pressure in the system rises.
  2. Operating current rises.
  3. Cooling(or heating) efficiency drops.
  4. Moisture in the refrigerant circuit may freeze and block capillary tubing.
  5. Water may lead to corrosion of parts in the refrigeration system.
    Therefore, the indoor/outdoor unit and connecting tube must be checked for leaks, and vacuumed to remove incondensible gas and moisture in the system.

Leak Checking

Preparation

  • Check that each tube(both liquid and gas side tubes) between the indoor and outdoor units have been properly connected and all wiring for the test run has been completed. Remove the service valve caps from both the gas and the liquid sides on the outdoor unit. Check that both the liquid and the gas side service valves on the outdoor unit are kept closed at this stage.

Leakage test

  • Connect the manifold valve(with pressure gauges) and dry nitrogen gas cylinder to this service port with charge hoses.

CAUTION: Be sure to use a manifold valve for leak testing.
The high side manifold valve must always be kept closed.

  • Pressurize the system to no more than 150 P.S.I.G. with dry nitrogen gas and close the cylinder valve when the gauge reading reached 150 P.S.I.G. Next, test for leaks with liquid soap.

CAUTION: To avoid nitrogen entering the refrigerant system in a liquid state, the top of the cylinder must be higher than its bottom when you pressurize the system. Usually, the cylinder is used in a vertical standing position.

NOTICE : Leakage testing shoud be done for each indoor unit connection set, separately.

  1. Do a leakage test of all joints of the tubing(both indoor and outdoor) and both gas and liquid side service valves with soap bubbles.
    Bubbles indicate a leak. Be sure to wipe off the soap with a clean cloth.

  2. After the system is found to be free of leaks, relieve the nitrogen pressure by loosening the charge hose connector at the nitrogen cylinder. When the system pressure is reduced to normal, disconnect the hose from the cylinder.

LG LMU185HV Multi Air Conditioner - Leakage test

Evacuation

  1. Connect the charge hose end described in the preceding steps to the vacuum pump to evacuate the tubing and indoor unit.
    Confirm the “Lo” knob of the manifold valve is open. Then, run the vacuum pump.
    The operation time for evacuation varies with tubing length and capacity of the pump.
    [Each Room] The vacuum pump must be operated less than 0.8torr of the gage pressure.

  2. When the desired vacuum is reached, close the “Lo” knob of the manifold valve and stop the vacuum pump.

Finishing the job

  1. With a service valve wrench, turn the valve stem of liquid side valve counter-clockwise to fully open the valve.
  2. Turn the valve stem of gas side valve counter-clockwise to fully open the valve.
  3. Loosen the charge hose connected to the gas side service port slightly to release the pressure, then remove the hose.
  4. Replace the flare nut and its bonnet on the gas side service port and fasten the flare nut securely with an adjustable wrench. This process is very important to prevent leakage from the system.
  5. Replace the valve caps at both gas and liquid side service valves and fasten them tight.

This completes air purging with a vacuum pump.
The air conditioner is now ready for test running.

NOTICE : Repeat evacuation procedure for each indoor unit.

LG LMU185HV Multi Air Conditioner - Evacuation

Charging

■ Each outdoor unit is factory charged (see rating plate) for the evaporator as well as a 7.5m(25ft) line set for each indoor line.
Any time total line set is used either shorter or longer than the nominal 7.5ID No. m(25ID No. ft) line set length the refrigerant charge has to be adjusted.
■ Whether the line set is made shorter or longer you must adjust the charge based on how many ft of tubing are either added or removed based on 20g/m(0.22oz/ft) of R-410A per meter(foot).

Unit:m(ft)

Outdoor Unit
Capacity
(Btu/h class)| Max total length
of all pipes
(A+B)/(A+B+C)/
(A+B+C+D)| Max length of
each pipe
(A/B/C/D)| Min length of
each pipe
(A/B/C/D)| Max Elevation
between each
indoor unit and
outdoor unit (h1)| Max elevation
between indoor units (h2)| Additional
Refrigerant
Unit : g/m (oz/ft)| PipingLength
(no add’l refrigerant)
---|---|---|---|---|---|---|---
18k| 50(164)| 25(82)| 3(10)| 15(49)| 7.5(25)| 20(0.22)| 22.5(74)
24k| 75(246)| 25(82)| 3(10)| 15(49)| 7.5(25)| 20(0.22)| 37.5(128)
36k| 75(246)| 25(82)| 3(10)| 15(49)| 7.5(25)| 20(0.22)| 37.5(128)

Important:
If you are ever uncertain of the unit charge, reclaim, evacuate and weigh in the correct charge using the charge amount specified on the unit’s rating plate, adjusting for line sets longer or shorter than 7.5m(25ft) for each indoor unit.

Additional charge(g) = [(A Room Installation Length – Standard Length ) x 0.22 oz/ft
+ (B Room Installation Length – Standard Length ) x 0.22 oz/ft +.. ] – CF(Correction Factor) x 1.61 oz
❈ CF = Max. number of connectable indoor unit – Total number of connected indoor unit

LG LMU185HV Multi Air Conditioner - Max. number of connectable indoor
unit

❈ If the total additional charge value after calculation comes out to be negative, then do not consider additional charge.

Combination indoor units

The indoor units connectable to the outdoor unit are shown below

Type| Chassis Name| Indoor Unit Capacity (Btu/h class)| Outdoor Unit Capacity
(Btu/h class)
---|---|---|---
9k| 12k| 18k| 18 k| 24 k| 36 k
Model Name| Connectable Combination
Standard Type| SE| AMNWO9GDEA0
[LMN095HV]| AMNW12GDEA0
[LMN125HV]| | 0
0| 0|
S5| | | AMNW18GDELO
[LMN1851-IV]| | 0| 0
Artcool
Mirror
Type| SE| AMNWO9GDERO
[LMAN095HV]| [LMAN1251-1V]| AMNW12GDERO| 0| 0| 0
S8| | | AMNW18GDERO
[LMAN185HV]| | 0| 0
Ceiling
Concealed
Duct Type| B1| AMNWO9GB1A0
[LMDN095HV]| AMNW12GB1A0
[LMDN125HV]| | 0| 0| 0
B2| | | AMNW18GB2A0
[LMDN185HV]| | 0| 0
Ceiling
Cassette
Type| TR| | AMNW12GTRAO
[LMCN125HV]| | 0| 0| 0
TO| | | AMNW18GTQAO
[LMCN185HV]| | 0| 0

NOTICE:

  1. The total capacity(in Btu/h unit) of connected indoor unit models represents the total sum of the figures expressed in the indoor model name.
  2. Combinations in which the total capacity of the connected indoor units exceeds the capacity of the outdoor unit will reduce the capacity of each indoor unit below the rated capacity during simultaneous operation. Therefore, if circumstances allows, combine indoor units within the capacity of the outdoor unit