SEL-3350 Adapter Panel Instruction Manual
- July 17, 2024
- SEL
Table of Contents
SEL-3350 Adapter Panel
Specifications
- Product Name: SEL-2902 RJ45 to DB-9 Adapter Panel
- Manufacturer: Schweitzer Engineering Laboratories, Inc.
- Mounting Options: Rack-mount, Surface-mount, DIN-rail
- Depth Adjustment: 7 to 11 inches
- Connectors: 16 Built-In RJ45 Ports, 16 Built-In DB-9 Female Ports
Product Overview
The SEL-2902 Adapter Panel allows easy adaptation of SEL computer
platform’s RJ45 serial ports to DB-9 connectors. It features flexible mounting
options, secure transceiver mounting, and cable management solutions
Installation Instructions
- Unit Location and Placement: Follow guidelines for proper installation to ensure trouble-free operation.
- Grounding: Connect chassis grounding terminals to rack frame ground for safety and performance.
- Applications: Retrofit applications for SEL-2020, SEL-2030, SEL-2032, and SEL-3530.
- Secure Mounting of Transceivers: Mount the adapter panel securely using surface-mount or rack-mount options.
- Cable Connection: Use shielded Ethernet patch cables to connect RJ45 port to SEL-3350 or SEL-3355 ports.
FAQ
-
Q: Can the SEL-2902 Adapter Panel be used with other SEL products?
A: The adapter panel is primarily designed for use with SEL-2020, SEL-2030, SEL-2032, SEL-3530, SEL-3350, and SEL-3355 products. -
Q: What is the recommended wire size for grounding the chassis terminals?
A: Use 14 AWG (2 mm2) or larger wire, less than 3 m (10 ft) in length for proper grounding.
SEL-2902 RJ45 to DB-9 Adapter Panel
Easily adapt the SEL computer platform’s RJ45 serial ports to DB-9 connectors
Key Features and Benefits
- Retrofit Applications. Retain existing serial cables and transceiver installation when upgrading an SEL-3530 Real-Time Automation Controller (RTAC) or SEL-2020/SEL-2030/SEL-2032 Communications Processor to the SEL-3350 Automation and Computing Platform and SEL-3355 Automation and Computing Platform.
- Flexible Mounting Options. Use rack-mount, surface-mount, or DIN-rail mounting options to support several different types of installations.
- Secure Transceiver Mounting. Provide solid mounting for SEL serial transceivers when used with the SEL-3350 and SEL-3355.
- Cable Management. Use the included rack-mount brackets to allow the use of existing cable management solutions.
Product Overview
Table 1 SEL-2902 RJ45 to DB-9 Connector Pinout Diagram
SEL-3350 Series Signal (EIA-232)| RJ45 Connector| DB-9
Connector
---|---|---
–IRIG-B out (GND)| 1| 6
+5 Vdca| 2| 1
+IRIG-B out| 3| 4
Signal Ground (GND)| 4| 5
Receive Data (RXD)| 5| 2
Transmit Data (TXD)| 6| 3
Clear to Send (CTS)| 7| 8
Request to Send (RTS)| 8| 7
SHIELD| SHELL| SHELL
a Software-enabled on the SEL-3500 series.
Grounding
Connect all chassis grounding terminals labeled GND on the rear panel to a
rack frame ground or main station ground for proper safety and performance.
Use 14 AWG (2 mm2) or larger wire, less than 3 m (10 ft) in length, for this
connection. All ground terminals connect directly to the internal chassis
ground of the SEL-2902.
Applications
SEL-2020, SEL-2030, SEL-2032,
and SEL-3530 Retrofit Application
The adapter panel with the adjustable-depth rack-mount option can be
configured between 7 and 11 inches in depth to match an existing SEL-2020,
SEL-2030, SEL-2032, or SEL-3530 installation. Matching the device depth allows
existing communications cables with DB-9 connectors to be retained. Use an
SEL-CA605 cable or equivalent shielded Ethernet patch cable to con-nect the
adapter panel RJ45 port to the ports on an SEL-3350, as shown in Figure 4, or
an SEL-3355 that is using the optional SEL-3390S8 Serial Adapter Cards.
SEL-3350 and SEL-3355 and Secure
Mounting of Transceivers
Securely mount the adapter panel with the surface-mount ordering option to a
solid surface, a 19 in rack-mount panel, or DIN rail by using the optional
DIN-rail mounting kit (915900639). Connect serial transceivers with a DB-9
male connector to the DB-9 port. An SEL-CA605 or equivalent shielded Ethernet
patch cable can be used to connect the RJ45 port to the ports on the SEL-3350
or SEL-3355.
Installation
Unit Location and Placement
For trouble-free operation, use the following guidelines to properly install
the SEL-2902.
Mount the SEL-2902 with the SEL-3300 series device in a sheltered indoor
environment (a building or an enclosed cabinet) that does not exceed the
temperature and humidity ratings for the unit (see Specifications on page 10).
The unit is rated as Installation/Overvoltage Category II (at <5 km altitude)
and Pollution Degree 2. These ratings allow you to mount the unit indoors or
in an outdoor (extended) enclosure where the unit is protected from direct
sunlight, precipitation, and full wind pressure but temperature and humidity
are not controlled. To satisfy safety requirements, install the unit in a
suit-able fire/electrical/mechanical enclosure.
To ensure best EMI and EMC performance, the SEL-CA605 cable or equivalent
shielded Ethernet patch cable that connects the SEL-3300 series device to the
SEL-2902 RJ45 port should not exceed 2 meters
(6.6 feet) in length.
Mounting Bracket Adjustment
The adjustable-depth mounting option ships by default at 8 in, as shown in
Figure 5. Adjust the depth in 1 in incre-ments from a minimum depth of 7 in to
a maximum of 11 in, as shown in Figure 6.
To adjust the depth, remove four screws from the side and eight screws from
the bottom, as shown in Figure 7. Move the adapter panel to the desired depth,
as shown in Figure 8. Reinstall the screws, as shown in Figure 9. Torque the
screws to 12 in-lb.
Adjusting Rack-Mount Depth
Surface Mounting
To mount the adapter panel with the surface-mount option, use the dimensions shown in Figure 14 and drill holes no larger than 3/16 in (5 mm).
DIN-Rail Mounting
To use the optional DIN-rail mounting kit (915900639), snap the two DIN-rail
clips onto your DIN rail. Align the DIN-rail clips with the center of the
adapter panel mounting ears, as shown in Figure 11. Thread the included #8
plastic screw through the hole and into the DIN-rail clip. Torque the screw to
12 in-lb after it is fully seated.
Cable Management
Each SEL-2902 that is configured with the adjustable-depth bracket is shipped
with accessory mounting ears and hard-ware, as shown in Figure 12. The
mounting ears can only be installed (torque screws to 12 in-lb) after the
adapter panel has been installed. Use third-party cable management brackets
compatible with 2U, 19 in rack-mount holes.
Dimensions
Specifications
Compliance
Designed and manufactured under an ISO 9001 certified quality management
system 47 CFR 15B Class A
This equipment has been tested and found to comply with the limits for a Class
A digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference when
the equipment is operated in a commercial environment. This equipment
generates, uses, and can radiate radio frequency energy and, if not installed
and used in accordance with the instruction manual, may cause harmful
interference in which case the user will be required to correct the
interference at his own expense.
UL Listed to U.S. and Canadian safety standards
(File E220228; NRAQ)
CE Mark
RoHS Compliant
General
- Connectors: Female DB-9, Shielded
- RJ45 Jack, Shielded
- Power Requirements: None
- Dimensions: See Figure 13 and Figure 14.
- Relative Humidity: 5 to 95% non-condensing
- DB-9 Jack Screw Torque: 6 in-lb
- Operating Temperature
- Range: –40° to +85°C (–40° to +185°F)
- Ground Screw (#6 Crimp Ring Terminal Is Recommended)
- Warning: When using stranded wire, use crimp ferrules to safely capture all wire strands before assembling and attaching the plug or ground wire.
- Insulation Ratings: 300 V, 90°C (194°F), minimum
- Wire Material: Copper
- Size: 12–18 AWG (4.00–0.75 mm2)
- Length: <3.0 m (<9.8 ft)
- Tightening Torque Min/Max: 0.9–1.36 Nm (8–12 in-lb)
Mounting Brackets
- Tightening Torque Min/Max: 2–4 Nm (18–35 in-lb)
Type Tests
To ensure protection-level EMI and EMC performance, type tests were performed
using shielded serial cables with the shield grounded at both ends of the
cable.
- Electromagnetic Compatibility Immunity
- Conducted RF Immunity: IEC 60255-26:2013
- EN 60255-26:2013 § 7.2.7
- IEC 61850-3:2013
- EN 61850-3:2014
- EN 55011:2009+A1:2010
- EN 55022:2010+AC:2011
- EN 55032:2015 + A11:2020
- CISPR 11:2009+A1:2010
- CISPR 11:2015 + A1:2015 + A2:2019
- CISPR 22:2008
- Canada ICES-001 (A)/ NMB-001 (A)
- CISPR 32:2015 + A1:2019
- ANSI C63.4:2014
- CSA CISPR 11:19
- ICES-001, Issue 5
- 47 CFR Part 15.107
- 47 CFR Part 15.109
- Other type tests and standards are inherited from the SEL-3350 Automation and Computing Platform and can be found in Section 1: Introduction and
- Specifications in the SEL-3350 Instruction Manual.
Technical Support
We appreciate your interest in SEL products and services. If you have
questions or comments, please contact us at: Schweitzer Engineering
Laboratories, Inc.
2350 NE Hopkins Court
Pullman, WA 99163-5603 U.S.A.
Tel: +1.509.338.3838
Fax: +1.509.332.7990
Internet: selinc.com/support
Email: info@selinc.com
© 2024 by Schweitzer Engineering Laboratories, Inc. All rights reserved.
All brand or product names appearing in this document are the trademark or
registered trademark of their respective holders. No SEL trademarks may be
used without written permission. SEL products appearing in this document may
be covered by U.S. and Foreign patents.
Schweitzer Engineering Laboratories, Inc. reserves all rights and benefits
afforded under federal and international copyright and patent laws in its
products, including without limitation software, firmware, and documentation.
The information in this document is provided for informational use only and is
subject t o change without notice. Schweitzer Engineering Laboratories, Inc.
has approved only the English language document.
This product is covered by the standard SEL 10-year warranty. For warranty
details, visit selinc.com or contact your customer
service representative.