Comfortmaker FXM4X Series Fan Coil HVAC System User Manual
- July 13, 2024
- Comfortmaker
Table of Contents
Comfortmaker FXM4X Series Fan Coil HVAC System
Product Specifications
Model Numbers
- FXM4X2400AL: 2 tons, 600 CFM (283 L/s), Dimensions: 49-5/8 x 17-5/8 x 22-1/16 in. (1261 x 448 x 560), Filter Size: 16-3/8 x21-1/2 in. (416 x 546), Ship Wt: 122 lbs. (55 kg)
- FXM4X3600AL: 3 tons, 800 CFM (378 L/s), Dimensions: 49-5/8 x 17-5/8 x 22-1/16 in. (1261 x 448 x 560), Filter Size: 16-3/8 x 21-1/2 in. (416 x 546), Ship Wt: 122 lbs. (55 kg)
- FXM4X4800AL: 4 tons, 1000 CFM (472 L/s), Dimensions: 53-7/16 x 21-1/8 x 22-1/16 in. (1357 x 537 x 560), Filter Size: 19-7/8 x 21-1/2 in. (505 x 546), Ship Wt: 146 lbs. (66 kg)
- FXM4X6000AL: 5 tons, 1200 CFM (566 L/s), Dimensions: 49-5/8 x 21-1/8 x 22-1/16 in. (1261 x 537 x 560), Filter Size: 19-7/8 x 21-1/2 in. (505 x 546), Ship Wt: 157 lbs. (71 kg).
Troubleshooting
If you encounter any issues with the unit, refer to the troubleshooting
section of the manual or contact customer support for assistance.
FAQ (Frequently Asked Questions)
Q: What is the warranty coverage for the product?
A: With timely registration, the product comes with an additional 5-year parts
limited warranty for owner-occupied, residential applications only. Refer to
the warranty certificate for complete details and restrictions.
Product Specifications
NOTE: Read the entire instruction manual before starting the installation.
Use of the AHRI Certified TM Mark indicates a manufacturer’s participation in the program. For verification of certification for individual products, go to www.ahridirectory.org.
- 1-1/2 thru 5 tons
- Available for environmentally balanced R-410A systems
- TXV metering device factory installed
- ECM motor
- Sweat connections
- Primary and secondary drain fittings with brass inserts
- 3 amp automotive type fuse in wire harness
- Multiple electrical entry locations
- Time delay relay (TDR) programmed in motor
- Field installed heater packages from 5 kW – 30 kW available separately
- HUD approved for manufactured housing
- 208/230-1-60 supply voltage
- Assembled at the factory compliant with low leak requirements of less than 2% cabinet leakage rate at 0.5 inches W.C. and 1.4% cabinet leakage rate at 0.5 inches W.C. when tested in accordance with ASHRAE 193 standard.
- 1 inch thick insulation with R value of 4.2
- Multi-position installation – up flow or horizontal left standard, horizontal right with minor modification (field convertible to downflow with available accessory kit)
- No Heat (Plug) Kit factory installed
- Filter (washable) factory supplied
WARRANTY*
-
5 year No Hassle replacement limited warranty
5 year parts limited warranty -
With timely registration, an additional 5 year parts limited warranty
-
For owner occupied, residential applications only. See warranty certificate for complete details and restrictions, including warranty coverage for other applications.
Model Number
| Tons| Nom. CFM (L/s)| Dimensions H x W x D in. (mm)|
Filter Size in. (mm)| Ship Wt lbs. (kg)
---|---|---|---|---|---
FXM4X1800AL| 1½| 600 (283)| 49-5/8 x 17-5/8 x 22-1/16 (1261 x 448 x 560)|
16-3/8 x 21-1/2 (416 x 546)| 122 (55)
FXM4X2400AL| 2| 800 (378)| 49-5/8 x 17-5/8 x 22-1/16 (1261 x 448 x 560)|
16-3/8 x 21-1/2 (416 x 546)| 122 (55)
FXM4X3000AL| 2½| 1000 (472)| 53-7/16 x 21-1/8 x 22-1/16 (1357 x 537 x 560)|
19-7/8 x 21-1/2 (505 x 546)| 146 (66)
FXM4X3600AL| 3| 1200 (566)| 49-5/8 x 21-1/8 x 22-1/16 (1261 x 537 x 560)|
19-7/8 x 21-1/2 (505 x 546)| 157 (71)
FXM4X4200AL| 3½| 1400 (661)| 49-5/8 x 21-1/8 x 22-1/16 (1261 x 537 x 560)|
19-7/8 x 21-1/2 (505 x 546)| 157 (71)
FXM4X4800AL| 4| 1600 (755)| 53-1/16 x 24-11/16 x 22-1/16 (1357 x 627 x 576)|
23-5/16 x 21-1/2 (592 x 546)| 185 (84)
FXM4X6000AL| 5| 2000 (944)| 59-3/16 x 24-11/16 x 22-1/16 (1503 x 627 x 576)|
23-5/16 x 21-1/2 (592 x 546)| 201 (91)
FXM4X: Product Specifications
DIMENSIONAL DATA
Model
| Size (tons)| Dimensions Inches| Coil Type| Ship. Wt
(llb)
A| B| C| D| E| F| G| H| J|
Suct| Liquid
FXM4X1800| 1-1/2| 49-5/8| 17-5/8| 15-3/4| 15-5/8| 15-3/8| 23-1/8| 23-5/8| –|
17| 5/8| 3/8| Slope| 122
FXM4X2400| 2| 49-5/8| 17-5/8| 15-3/4| 15-5/8| 15-3/8| 23-1/8| 23-5/8| –| 17|
5/8| 3/8| Slope| 122
FXM4X3000| 2-1/2| 53-7/16| 21-1/8| 19-1/8| 19-1/8| 19-3/16| 26-15/16| 27-1/2|
–| 19| 3/4| 3/8| Slope| 146
FXM4X3600| 3| 49-5/8| 21-1/8| 19-1/8| 19-1/8| 15-11/16| 23-7/16| 23-1/8| –| –|
3/4| 3/8| “A”| 157
FXM4X4200| 3-1/2| 49-5/8| 21-1/8| 19-1/8| 19-1/8| 15-11/16| 23-7/16| 23-1/8|
–| –| 7/8| 3/8| “A”| 157
FXM4X4800| 4| 53-1/16| 24-11/16| 22-3/4| 22-11/16| 19-1/2| 27-1/4| 26-15/16|
28-5/16| –| 7/8| 3/8| “A”| 185
FXM4X6000| 5| 59-3/16| 24-11/16| 22-3/4| 22-11/16| 25-1/4| 32-15/16| 32-5/8|
34-1/16| —| 7/8| 3/8| “A”| 201
Model| Size (tons)| Dimensions MM| Coil Type| Ship. Wt
(lkg)
A| B| C| D| E| F| G| H| J|
Suct| Liquid
FXM4X1800| 1-1/2| 1261| 448| 400| 397| 391| 587| 600| –| 432| 16| 10| Slope|
55
FXM4X2400| 2| 1261| 448| 400| 397| 391| 587| 600| –| 432| 16| 10| Slope| 55
FXM4X3000| 2-1/2| 1357| 537| 489| 486| 487| 684| 699| –| 483| 19| 10| Slope|
66
FXM4X3600| 3| 1261| 537| 489| 486| 399| 595| 587| –| –| 19| 10| “A”| 71
FXM4X4200| 3-1/2| 1261| 537| 489| 486| 399| 595| 587| –| –| 22| 10| “A”| 71
FXM4X4800| 4| 1357| 627| 578| 576| 495| 692| 684| 719| –| 22| 10| “A”| 84
FXM4X6000| 5| 1503| 627| 578| 576| 641| 837| 829| 865| 587| 22| 10| “A”| 91
PHYSICAL DATA
| Model Size
1800| 2400| 3000| 3600| 4200| 4800| 6000
Blower Data
CFM nominal (L/s)| 600 (283)| 800 (378)| 1000 (472)| 1200 (566)| 1400 (661)|
1600 (755)| 2000 (944)
Motor Type| ECM
HP| 1/3| 1/3| 1/2| 1/2| 1/2| 3/4| 3/4
Filter Data (factory supplied, washable)
Filter Size in. (mm)| 16-3/8 x 21-1/2 (416 x 546)| 19-7/8 x 21-1/2 (505 x
546)| 23-5/16 x 21-1/2 (592 x 546)
Coil Data (all coils 14½ fins per inch, wavy lanced bare aluminum fin)
Face Area ft2 (m2)| 2.97 (0.28)| 2.97 (0.28)| 3.46 (0.32)| 4.45 (0.41)| 5.93
(0.55)| 7.42 (0.69)
Refrigerant Line Connections (sweat)
Liquid inch (mm)| 3/8 (10)| 3/8 (10)| 3/8 (10)| 3/8 (10)| 3/8 (10)| 3/8 (10)|
3/8 (10)
Suction inch (mm)| 5/8 (16)| 5/8 (16)| 3/4 (19)| 3/4 (19)| 7/8 (22)| 7/8 (22)|
7/8 (22)
**ELECTRICAL DATA, FAN COIL ONLY WITHOUT ELECTRIC HEAT ***
Model
| 208/230V, single phase, 60 Hz
Motor Full Load Amps (FLA)| Minimum Circuit Ampacity (MCA)|
Maximum Fuse/Ckt Bkr Amps (Max OverCurrent Protection – MOCP)
FXM4X1800| 2.8| 3.5| 15
FXM4X2400| 2.8| 3.5| 15
FXM4X3000| 4.1| 5.1| 15
FXM4X3600| 4.1| 5.1| 15
FXM4X4200| 4.1| 5.1| 15
FXM4X4800| 6.0| 7.5| 15
FXM4X6000| 6.0| 7.5| 15
*. SCCR (Short Circuit Current Rating) = 5kA rms, symmetrical, 230V
Manufacturer reserves the right to change, at any time, specifications and
designs without notice and without obligations. 7
AIRFLOW PERFORMANCE – CFM at a given Speed and Static reading
Model| Blower Speed| Measured Static Pressure, inlet to outlet
(inches water column)
0.10| 0.20| 0.30| 0.40| 0.50| 0.60
FXM4X1800| Tap 5| 776| 745| 696| 660| 609| 572
Tap 4| 683| 644| 589| 548| 494| 461
Tap 3| 683| 644| 589| 548| 494| 461
Tap 2| 631| 563| 500| 443| 409| 361
Tap 1| 625| 524| 457| 417| 367| 319
FXM4X2400| Tap 5| 956| 920| 891| 851| 816| 780
Tap 4| 825| 795| 757| 722| 674| 634
Tap 3| 825| 795| 757| 722| 674| 634
Tap 2| 726| 695| 635| 598| 543| 509
Tap 1| 631| 563| 500| 443| 409| 361
FXM4X3000| Tap 5| 1189| 1151| 1104| 1050| 1003| 959
Tap 4| 1041| 998| 944| 886| 837| 772
Tap 3| 1041| 998| 944| 886| 837| 772
Tap 2| 924| 876| 817| 752| 704| 660
Tap 1| 779| 693| 628| 571| 526| 476
FXM4X3600| Tap 5| 1363| 1332| 1294| 1253| 1207| 1157
Tap 4| 1237| 1206| 1160| 1121| 1070| 1013
Tap 3| 1237| 1206| 1160| 1121| 1070| 1013
Tap 2| 1095| 1058| 1007| 951| 888| 824
Tap 1| 1014| 885| 773| 673| 609| 549
FXM4X4200| Tap 5| 1519| 1490| 1454| 1419| 1379| 1332
Tap 4| 1437| 1403| 1366| 1333| 1294| 1245
Tap 3| 1437| 1403| 1366| 1333| 1294| 1245
Tap 2| 1257| 1226| 1191| 1141| 1090| 1033
Tap 1| 1237| 1206| 1160| 1121| 1070| 1013
FXM4X4800| Tap 5| 1757| 1725| 1693| 1653| 1614| 1576
Tap 4| 1664| 1626| 1593| 1552| 1517| 1477
Tap 3| 1664| 1626| 1593| 1552| 1517| 1477
Tap 2| 1459| 1420| 1379| 1336| 1298| 1259
Tap 1| 1301| 1241| 1195| 1150| 1102| 1039
FXM4X6000| Tap 5| 2030| 1995| 1961| 1927| 1888| 1842
Tap 4| 1811| 1775| 1740| 1703| 1664| 1613
Tap 3| 1811| 1775| 1740| 1703| 1664| 1613
Tap 2| 1665| 1632| 1593| 1556| 1507| 1453
Tap 1| 1462| 1418| 1371| 1327| 1278| 1228
NOTES :
- Airflow based upon dry coil at 230v with factory approved filter and electric heater (2 element heater sizes 18 through 36, 3 element heater sizes 42 through 60).
- Airflow at 208 volts is approximately the same as 230 volts because the X13 motor is a constant torque motor. The torque doesn’t drop off at the speeds the motor operates.
- To avoid potential for condensate blowing out of drain pan prior to making drain trap: Return static pressure must be less than 0.40 in. wc. Horizontal applications of 042 – 060 sizes must have supply static greater than 0.20 in. wc.
- Airflow above 400 cfm/ton on 048 – 060 size could result in condensate blowing off coil or splashing out of drain pan.
- Shading – Airflow outside 450 cfm/ton.
Static Pressure Drop Across Filter (inches of water column)
Model Size| CFM
400| 600| 800| 1000| 1200| 1400| 1600|
1800| 2000
1800| .020| .044| .075| –| –| –| –| –| –
2400| –| .022| .048| .072| .100| –| –| –| –
3000| –| .022| .048| .072| .100| –| –| –| –
3600| –| –| –| .051| .070| .092| .120| .152| –
4200| –| –| –| .051| .070| .092| .120| .152| –
4800| –| –| –| .051| .070| .092| .120| .152| –
6000| –| –| –| –| –| –| .086| .105| .130
Static Pressure Correction from Dry to Wet Coil (inches of water column)
Airflow performance chart was developed using fan coils with DRY coils.
When taking a static reading across a WET coil, adjust the static pressure
numbers by adding the values in this table (for a given CFM, wet coil will
have greater static pressure drop than dry coil).
Model Size| CFM
500| 600| 700| 800| 900| 1000| 1100|
1200| 1300| 1400| 1500| 1600| 1700| 1800|
1900| 2000
1800| .034| .049| .063| –| –| –| –| –| –| –| –| –| –| –| –| –
2400| .016| .027| .038| .049| .059| –| –| –| –| –| –| –| –| –| –| –
3000| –| –| –| .049| .059| .070| .080| –| –| –| –| –| –| –| –| –
3600| –| –| –| –| –| .055| .064| .073| .081| –| –| –| –| –| –| –
4200| –| –| –| –| –| –| –| .049| .056| .063| .070| –| –| –| –| –
4800| –| –| –| –| –| –| –| –| –| .038| .043| .049| .054| .059| –| –
6000| –| –| –| –| –| –| –| –| –| –| –| .027| .031| .035| .039| .043
Static Pressure Correction for Electric Heaters (inches of water column)
Airflow performance chart was developed using fan coils with 10 kW electric
heater (2 elements) in the 1800 – 3600 model sizes, and 15 kW electric heaters
(3 elements) in the 4200 – 6000 model sizes.
When using a different number of heater elements, adjust the static pressure
numbers by adding or subtracting the values in this table (for a given CFM,
more electric heater elements create higher static pressure drop).
Model Size
| Heater kW
No Heater| 3 or 5| 8 or 10| 9 or 15| 20
Number of Heat Elements
0| 1| 2| 3| 4
1800| +0.02| +0.01| 0| -0.02| -0.04
2400| +0.02| +0.01| 0| -0.02| -0.04
3000| +0.02| +0.01| 0| -0.02| -0.04
3600| +0.02| +0.01| 0| -0.02| -0.04
4200| +0.04| –| +0.02| 0| -0.02
4800| +0.04| –| +0.02| 0| -0.02
6000| +0.04| –| +0.02| 0| -0.02
ESTIMATED SOUND POWER LEVEL (dBA)
Model Size| Conditions| **Octave Band Center Frequency*
CFM| Ext Static Pressure| 63| 125| 250| 500|
1000| 2000| 4000**
1800| 600| 0.25| 64.7| 60.7| 56.7| 53.7| 51.7| 49.7| 45.7
2400| 800| 0.25| 66.0| 62.0| 58.0| 55.0| 53.0| 51.0| 47.0
3000| 1000| 0.25| 67.0| 63.0| 59.0| 56.0| 54.0| 52.0| 48.0
3600| 1200| 0.25| 67.8| 63.8| 59.8| 56.8| 54.8| 52.8| 48.8
4200| 1400| 0.25| 68.4| 64.4| 60.4| 57.4| 55.4| 53.4| 49.4
4800| 1600| 0.25| 69.0| 65.0| 61.0| 58.0| 56.0| 54.0| 50.0
6000| 2000| 0.25| 70.0| 66.0| 62.0| 59.0| 57.0| 55.0| 51.0
- Estimated sound power levels have been derived using the method described in the 1987 ASHRAE HVAC Systems & Applications Handbook, Ch 52, pg 52.7.
ELECTRIC HEATER Electrical Data
Heater Model| Heater kW| PHASE| INTERNAL CIRCUIT
PROTECTION| HEATER AMPS 208/230V| BRANCH CIRCUIT
Min Ampacity k
208/230V| Min Wire Size (AWG) 208/230V 1| Min Gnd Wire Size
208/230V| Max Fuse/Ckt Brk Amps 208/230V| Max Wire Length 208/230V
(Ft) }}
Single Circuit| Dual Circuit| Single Circuit| Dual
Circuit| Single Circuit| Dual Circuit| Single Circuit|
Dual Circuit| Single Circuit| Dual Circuit| Single Circuit|
Dual Circuit
230V| 208V| L1,l2| L3,L4| L1,L2| L3,L4| L1,
L2| L3, L4| L1, L2| L3,L4| L1,L2| L3,L4|
L1,L2| L3,L4
EHK05AKN*| 5| 3.8| 1| None| 18.1/20.0| —| —| 26.0/28.4| —| —| 10/10| —|
—| 10/10| —| —| 30/30| —| —| 66/66| —| —
EHK05AKN**| 5| 3.8| 1| None| 18.1/20.0| —| —| 31.2/33.5| —| —| 8/8| —|
—| 10/10| —| —| 35/35| —| —| 85/88| —| —
EHK05AKB*| 5| 3.8| 1| Ckt Bkr| 18.1/20.0| —| —| 26.0/28.4| —| —| 10/10|
—| —| 10/10| —| —| 30/30| —| —| 66/66| —| —
EHK05AKB**| 5| 3.8| 1| Ckt Bkr| 18.1/20.0| —| —| 31.2/33.5| —| —| 8/8|
—| —| 10/10| —| —| 35/35| —| —| 85/88| —| —
EHK07AKN| 8| 6.0| 1| None| 28.9/32.0| —| —| 44.7/48.5| —| —| 8/8| —| —|
10/10| —| —| 45/50| —| —| 59/60| —| —
EHK07AKB| 8| 6.0| 1| Ckt Bkr| 28.9/32.0| —| —| 44.7/48.5| —| —| 8/8| —|
—| 10/10| —| —| 45/50| —| —| 59/60| —| —
EHK09AKCN {
| 9| 6.8| 1| None| 32.8/36.0| —| —| 49.5/53.5| —| —| 8/6| —| —| 10/10| —| —|
50/60| —| —| 54/87| —| —
9| 6.8| 3| None| 18.8/20.8| —| —| 32.0/34.5| —| —| 8/8| —| —| 10/10| —| —|
35/35| —| —| 83/85| —| —
EHK10AKN| 10| 7.5| 1| None| 36.2/40.0| —| —| 53.8/58.5| —| —| 6/6| —| —|
10/10| —| —| 60/60| —| —| 78/80| —| —
EHK10AKB| 10| 7.5| 1| Ckt Bkr| 36.2/40.0| —| —| 53.8/58.5| —| —| 6/6| —|
—| 10/10| —| —| 60/60| —| —| 78/80| —| —
EHK15AKF| 15| 11.3| 1| Fuse| 54.2/59.9| 36.2/40.0| 18.1/20.0| 76.3/83.4|
53.8/58.5| 22.7/25.0| 4/4| 6/6| 10/10| 8/8| 10/10| 10/10| 80/90| 60/60| 25/25|
88/89| 78/80| 75/76
EHK15AKB| 15| 11.3| 1| Ckt Bkr| —| 36.2/40.0| 18.1/20.0| —| 53.8/58.5|
22.7/25.0| —| 6/6| 10/10| —| 10/10| 10/10| —| 60/60| 25/25| —| 78/80| 75/76
EHK15AHN| 15| 11.3| 3| None| 31.3/34.6| —| —| 47.7/51.8| —| —| 8/6| —|
—| 10/10| —| —| 50/60| —| —| 56/90| —| —
EHK18AHN| 18| 13.5| 3| None| 37.6/41.5| —| —| 55.5/60.4| —| —| 6/6| —|
—| 10/8| —| —| 60/70| —| —| 76/77| —| —
EHK20AKF| 20| 15.0| 1| Fuse| 72.3/79.9| 36.2/40.0| 36.2/40.0|
98.9/108.4| 53.8/58.5| 45.3/50.0| 3/2| 6/6| 8/8| 8/6| 10/10| 10/10| 100/110|
60/60| 50/50| 85/109| 78/80| 59/59
EHK20AKB| 20| 15.0| 1| Ckt Bkr| —| 36.2/40.0| 36.2/40.0| —| 53.8/58.5|
45.3/50.0| —| 6/6| 8/8| —| 10/10| 10/10| —| 60/60| 50/50| —| 78/80| 59/59
EHK25AHCF }
| 24| 18.0| 3| Fuse| 50.1/55.4| —| —| 71.2/77.8| —| —| 4/4| —| —| 8/8| —| —|
80/80| —| —| 94/95| —| —
24| 18.0| 1| Fuse| 86.7/95.5| —| —| 116.9/127.9| —| —| 1/1| —| —| 6/6| —| —|
125/150| —| —| 115/116| —| —
EHK30AHCF }
| 30| 22.5| 3| Fuse| 62.6/69.2| —| —| 86.8/95.0| —| —| 3/3| —| —| 8/8| —| —|
90/100| —| —| 97/98| —| —
30| 22.5| 1| Fuse| 109.0/120.0| —| —| 144.8/158.5| —| —| 0/00| —| —| 6/6| —|
—| 150/175| —| —| 117/150| —| —
FIELD MULTIPOINT WIRING OR 24 AND 30 kW SINGLE PHASE|
---|---
Heater Model| Heater kW| P H A S E| Heater Amps 208/230V|
Minimum Circuit Ampacity 208/230V k| Minimum Wire Size (AWG)
208/230V }| Min Gnd Wire Size 208/230V| Max Fuse/Ckt Bkr Amps
208/230V| Max Wire Length 208/230V (FT) }}|
L1, L2| L3, L4| L5, L6| L1, L2| L3, L4| L5, L6|
L1, L2| L3, L4| L5, L6| L1, L2| L3, L4| L5, L6|
L1, L2| L3, L4| L5, L6|
230V| 208V|
EHK25AHCF }| 24| 18.0| 1| 28.9/32.0| 28.9/32.0| 28.9/32.0|
44.7/48.5| 36.2/40.0| 36.2/40.0| 8/8| 8/8| 8/8| 10/10| 45/50| 40/40| 40/40|
59/60| 73/73| 73/73|
EHK30AHCF }| 30| 22.5| 1| 36.2/40.0| 36.2/40.0| 36.2/40.0|
53.8/58.5| 45.3/50.0| 45.3/50.0| 6/6| 8/8| 8/8| 10/10| 60/60| 50/50| 50/50|
78/80| 59/59| 59/59|
Notes :
- Copper wire must be used. If other than uncoated (non-plated), 75°C ambient, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the National
Electric Code (ANSI/NFPA 70)
-
When used with Fan Coil model sizes 2400, 3600
** When used with Fan Coil model sizes 4200, 4800, 6000- k Includes blower motor amps of largest Fan Coil used with heater
- { Supplied as single phase, field convertible to 3-phase
- } Supplied as 3-phase, field convertible to single phase, single or multiple supply circuits
- }} Length shown is as measured one way along wire path between unit and service panel for a voltage drop not to exceed 2%\
ACCESSORIES
Part Number| Description| Use with model size
EBAC01DSC| Disconnect Kit| use with All single phase Heaters 5 kW thru 10 kW
EBAC02NCB| Downflow Base Kit| 1800, 2400
EBAC03NCB| 3000, 3600, 4200
EBAC04NCB| 4800, 6000
EBAC01DFS| Downflow Conversion Kit – Slope Coil| 1800, 2400, 3000
EBAC02DFA| Downflow Conversion Kit – “A” Coil| 3600, 4200, 4800, 6000
EBAC01SPK| Single Point Wiring Kit| only for use with 15 kW & 20 kW fused
heaters
Square Dr part #
QOU14100JBAF *
| Single Point Wiring Kit – Square Dr Jumper Bar Assembly|
Only for use with EHK15AKB and EHK20AKB breaker heaters
EBAC01FKM| Filter Kit (washable, box of 12) Factory Supplied| 1800, 2400|
Factory Supplied
EBAC01FKL| 3000, 3600, 4200
EBAC01FKX| 4800, 6000
NASA00201FR| Standard Filter Rack (16 x 20 x 1 filter required)| 1800, 2400
NASA00301FR| Standard Filter Rack (20 x 20 x 1 filter required)| 3000, 3600,
4200
NASA00401FR| Standard Filter Rack [quantity 2] (12 x 20 x 1 filter required)|
4800, 6000
EBAC01PLG| No Heat (Plug) Kit (box of 6)| Factory Installed
EBAC01CTK| PVC Condensate Trap Kit (box of 50)| ALL
EBAC01GSK| Horizontal Gasket Kit|
ALL (required for horizontal right and downflow)
NAEA20101TX| TXV Kit, R-22, Copper or Tin Coil Only| 1800, 2400, 3000, 3600,
4200
NAEA20201TX| 4800
NAEA20301TX| 6000
NAEB20101TX| TXV Kit, R-22, Aluminum Coil Only| 1800AL, 2400AL, 3000AL,
3600AL, 4200AL
NAEB20201TX| 4800AL
NAEB20301TX| 6000AL
1191140| Door Gasket Kit **| All
- Square D part number given for reference only. Check with local Square D supplier.
** This kit is for replacement of factory installed gaskets if they are damaged or removed from the fan coil.
ELECTRIC HEATERS
Part Number| Description| Use with Model Sizes
EHK05AKN| 5 kW, single phase, no internal circuit protection| ALL
EHK05AKB| 5 kW, single phase, with circuit breakers| ALL
EHK07AKN| 8 kW, single phase, no internal circuit protection| ALL
EHK07AKB| 8 kW, single phase, with circuit breakers| ALL
EHK09AKCN| 9 kW, supplied as single phase, field convertible to 3-phase, no
internal circuit protection| 3600, 4200, 4800, 6000
EHK10AKN| 10 kW, single phase, no internal circuit protection| ALL
EHK10AKB| 10 kW, single phase, with circuit breakers| ALL
EHK15AKF| 15 kW, single phase, with fuses| 2400, 3000, 3600, 4200, 4800, 6000
EHK15AKB| 15 kW, single phase, with circuit breakers| 2400, 3000, 3600, 4200,
4800, 6000
EHK15AHN| 15 kW, 3-phase, no internal circuit protection| 3600, 4200, 4800,
6000
EHK18AHN| 18 kW, 3-phase, no internal circuit protection| 4200, 4800, 6000
EHK20AKF| 20 kW, single phase, with fuses| 3000, 3600, 4200, 4800, 6000
EHK20AKB| 20 kW, single phase, with circuit breakers| 3000, 3600, 4200, 4800,
6000
EHK25AHCF| 24 kW, supplied as 3-phase, field convertible to single phase, with
fuses| 4800, 6000
EHK30AHCF| 30 kW, supplied as 3-phase, field convertible to single phase, with
fuses| 4800, 6000
2020 Carrier. All rights reserved.
A Carrier Company www.GoAirquest.com
Edition Date: 09/20 Catalog No: 496 51 5402 05
Replaces: 496 51 5402 04
FXM4X: Product Specifications
Manufacturer reserves the right to change, at any time, specifications and
designs without notice and without obligations.