LINDINVENT DCV-SPb Pressure Control Unit User Manual
- June 24, 2024
- LINDINVENT
Table of Contents
LINDINVENT DCV-SPb Pressure Control Unit
Product Information
Specifications
- Product Name: DCV-SPb Pressure Control Unit
- Model : SPLb version C04
- Manufacturer : Lindinvent
- Function : Pressure measurement and control for protective ventilation and climate control
- Compatibility : Cooperates with other control equipment via a local network (CAN loop)
Product Usage Instructions
Overview
The DCV-SPb Pressure Control Unit is designed for maintaining pressure in a
channel section for protective ventilation and climate control in workplaces.
Components
The unit consists of a damper, a damper motor, and a pressure controller.
The damper can be either circular or rectangular. Refer to the product
description for detailed technical specifications.
Installation
- Identify the appropriate location for installation based on ventilation needs.
- Connect the DCV-SPb to other control equipment using the local network (CAN loop).
- Ensure proper alignment of the damper and motor for efficient operation.
- Follow the wiring diagram provided in the manual for correct electrical connections.
Operation
The DCV-SPb maintains duct pressure by regulating the supply air via active
diffusers and extracting air via the corridor. It features two fixed extract
airflows for efficient ventilation control.
FAQ
-
Q: How do I adjust the pressure settings on the DCV-SPb?
- A: The pressure settings can be adjusted through the controller SPLb. Refer to the user manual for detailed instructions on setting pressure levels.
-
Q: Can the DCV-SPb be used in both circular and rectangular ducts?
- A: Yes, the DCV-SPb is versatile and can be installed in both circular and rectangular ducts. Ensure proper sizing and alignment during installation.
Product description
DCV-SPb PRESSURE CONTROL UNIT
Introduction
DCV-SPb is part of Lindinvent’s series of smart and installation-eff icient
dampers and measuring devices for protective ventilation and climate control
at workplaces.
FUNcTIONs
DCV-SPb consists of a damper, a damper motor and a pressure controller. The
unit cooperates with other control equipment via a local network (CAN loop) to
maintain pressure in a channel section.
Circular or rectangular
The circular version (Ø100-500 mm) is supplied as a complete module with
constituent parts connected and ready for assembly as a unit. DCV-SPb
Rectangular is supplied in parts to be assembled on site. DCV-SPb Circular is
available in database for MagiCad. DCV-SPb Rectangular is drawn as damper
JSPM.
See page 2 for a presentation of constituent parts.
Functional diagram: DCV-SPb maintains duct pressure. Supply air via active diff users and extract air via corridor. Two fixed extract airflows.
SPLb version C04
Pressure Measurement And Control
Pressure sensor in SPLb: Digital, integrerad Range: 5 to 500 Pa
Tolerance: ± 5 % or at least ± 3 Pa Performance: Change within 4s (95%
within 3s)
Parts With Specifications
The products below are included as parts of DCV-SPb. The damper is either circular or rectangular. See the product description for more complete technical specifications.
DCV-SPb and its constituent parts
Pressure controller – SPLb
- Included, mounted, in DCV-SPb Circular
- Supplied as part of DCV-SPb Rectangular
- Integrated digital pressure sensor
- CAN connection
- IP-class : IP53
- Operating temperature limits : 0°C to 40°C; <85% RH
- Temperature limit storage : – 20°C to 50°C; <90% RH
- Weight: 0.3 kg
- One of the following main features is to be selected at commissioning : Pressure control, Pressure control external measurement, Pressure measurement, or Slave control.
Damper actuator – DBA
- Included, mounted, in DCV-SPb Circular
- Supplied as part of DCV-SPb Rectangular
- Microprocessor controlled BLDC motor
- Indicator pin to show the damper opening angle
- IP-class : IP42 (mounted on the actuator holder)
- Operating temperature limits : 0°C to 40°C; <85% RH
- Temperature limit storage : – 20°C to 50°C; <90% RH
- Weight : 0.9 kg
Circular damper – SPM
- Included, mounted, in DCV-SPb Circular
- Throttle damper with a full damper blade
- Actuator shelf adapted for Lindinventʼs damper actuator
- Tightness class 3 according to VVS AMA
- Pressure class A according to VVS AMA
- Weight : After damper size (0.5 to 4.5 kg)
Rectangular damper – JSPM
- Supplied as part of DCV-SPb Rectangular
- Case of galvanized sheet steel (C3)
- Actuator shelf adapted for Lindinventʼs damper actuator
- Damper blades of aluminium (C4)
- Tightness class 2 according to VVS AMA
- Pressure class A according to VVS AMA
- Available with circular connection with size 700×700 or 800×800
- Weight: After damper size (3 to 40 kg)
Connection Diagram
Connections
- 2 x terminals for 24 VAC + CAN
- Terminal AIN1 and AOUT1 (0-10 VDC) used by the damper actuator
- Terminal AIN2 and AOUT2 (general 0-10 VDC)
- Relay (24 VAC or potential-free)
- Terminal AUX for Generic power supply (0, 5, 15 VDC)
- Terminal for I2C-bus
- Module for Bluetooth®
- Terminal for user panel (FLOCHECK P version B02)
VISUALIzation tool LINDINSPECT®
LINDINSPECT® is a powerful web-based tool which is part of the central unit
system soft ware. Everything from control units to supplementary systems for
comfort and sustainable energy use is made accessible for central
optimization, administration and visualization.
www.lindinvent.se | DCV-SPb_PB41_en
User interfaces
Look for details about a specific interface via its product name and product
description.
- Login localy directly to the controller via mobile phone with the LINDINSIDE app
- Via Gate way NCE and Lindinventʼs central unit running LINDINSPECT®
- Other parent system via Gateway NCE and Modbus-RTU or ModbusTCP
- Fixed panel FLOCHECK P, wired directly to SPLb
Troubleshooting and Alarm Notification
Systems with LINDINSPECT® log and set alarm flags in case of deviations. Alarms can also be indicated both acoustically and optically by connecting user panel FLOCHECK P to the controller.
Easy Commissioning
All of Lindinvent’s controllers are delivered factory-calibrated. Only a few
settings are required in connection with commissioning.
Functional chart
DCV-SPb on main duct for supply air:
Cell offices with supply air via active diffusers and extract air to a common
corridor. Two fixed extract airflows with supply air from the corridor.
Active diffusers
-
Controls the climate in each office according to setpoints
-
Notifies collaborating nodes of their current airflow
DCV-SPb -
Continuously measures the pressure in the duct section
-
Maintains the duct pressure according to setpoints via damper control
-
DCV-SPb is commissioned for pressure control
DCV-CFb -
Maintains a constant duct pressure to maintain the fixed set extract airflow
-
Measures and reports via CAN the fixed airflow
-
Note: DCV-CFb is always commissioned for pressure control and flow measurement
DCV-BLb -
Measures the extract airflow from the corridor
-
Reads the reported DCV-CFb airflow
-
Sums its own measured airflow with the measured flow from DCV-CFb
-
Maintains the desired balancing of the supply air-flow through damper control
DCV-BLb is commissioned for flow balancing.
Order Information
DCV-SPb Circular (Ø100-500 mm)
Pressure control unit, Lindinvent AB,
DCV-SPb-[Damper size][Material]-[Colour] Damper size SPM : 100, 125, 160,
200, 250, 315, 400, 500
Material
- Galvanized sheet steel (C3)
- Stainless acid-resistant sheet steel (C5)
- Epoxy-coated sheet steel (E)
- Powder-coated sheet steel (P)
Omitted material specification: Galvanized (C3)
Colour: RAL9003 (standard). To be stated for E and P. Other colours and
gloss levels can be ordered.
Example
- DCV-SPb-250C3 (DCV-SPb Circular galvanized)
- DCV-SPb-250P-RAL9003 (Powder-coated RAL9003)
DCV-SPb Circular (duct connection Ø630 mm)
- Pressure control unit, Lindinvent AB,
- DCV-SPb-630(700×700)[Material] or
- DCV-SPb-630(800×800)[Material]
- Size available : 700×700 or 800×800 mm
Material: Galvanized (C3)
Example: DCV-SPb-630(700×700)C3
DCV-SPb-630 is delivered as a construction kit. The rectangular damper JSPM
700×700 mm with circular connection 630, controller SPLb, and damper actuator
DBA are delivered separately to be installed on site.
DCV-SPb Rectangular
- Pressure control unit, Lindinvent AB,
- DCV-SPb-[WxH][Material]
- Standard sizes WxH: from 200×200 mm to 1600×1000 mm Width(W): from 200 to 1000 mm in intervals of 100 mm, then in intervals of 200 mm
- Height(H) : from 200 to 800 mm in intervals of 100 mm, then in intervals of 200 mm
- Contact Lindinvent if you need non-standard dimensions.
- Material: Galvanized (C3)
Example: DCV-SPb-600x300C3
DCV-SPb Rectangular is delivered as a construction kit where damper JSPM,
controller SPLb and damper actuator DBA are delivered separately to be
installed on site.
Dimensions in mm
Complementary Documentation
Document can be viewed on the product page at
www.lindinvent.com
Document | Comments |
---|---|
Installation instructions | Combined installation instructions for DCV- |
SPb and pressure controller SPLb (mounting + connection).
Operation instructions| Short presentation of LINDINSIDE and control
variables.
Maintenance instructions| Considered maintenance free.
External connection diagram| Shows how conductors from equipment
are connected to SPLb.
Environmental product declaration| For assessment at
Byggvarubedömningen.
Modbus list| Last entry in the modbus list for SPLb.
AMA-text| Available.
www.lindinvent.se | DCV-SPb_PB41_en
References
- Ventilation on demand - smart solutions, low life cycle cost
- Behovsstyrda fastigheter med fokus på människan | Lindinvent
Read User Manual Online (PDF format)