TopTech TT-UV24-15 TechPure Germicidal UV System Installation Guide
- June 8, 2024
- Toptech
Table of Contents
TT-UV24-15 TechPure Germicidal UV System
Installation Guide This manual covers the following model:
TechPure UV #TT-UV24-15
BEFORE INSTALLING
- Read all instructions carefully. Failure to do so could damage the equipment or cause harm to yourself or others.
- Acknowledge all warnings.
- Only qualified technicians should perform the installation.
INCLUDED INSIDE BOX
- Power Module
- Germicidal UV lamp
- Power cord
- Remote lamp cord
- Magnetic Mounting bracket
- Filter shield
- Self-drilling screws
- UV safety viewport
- UV safety label
- Installation & operation manual
- Installation hardware
SPECIFICATIONS
Dimensions:
Power Module: 5”L x 3.25”W x 2”H
Bracket: 3.5”L x 2.25”W x 3.5”H
Electrical: 24VAC (Expanded range ballast: 20V-32V), 50/60Hz, 1.4A. 3000V
surge protection. 3-ft power cord. 4-ft lamp cord
Lamp Length: 15”
Weight: 2lb
Humidity: Water resistant lamp.
Lamp Life: 18,000-hour. Ozone free.
Warranty: 5-year on power module. 2-year on lamp.
U.S. Patent Nos. 5,334,347, 5,817,276, 6,245,293, 6,267,924, 6,280,686,
6,313,470, 6,627,000, 6,539,727, 6,932,494, 6,550,257.
EPA Device Manufacturer Establishment No. 73316-TX-1
The product and technologies described are not medical devices, and are not
intended to diagnose, treat, cure, or prevent any disease or illness.
UV INSTALLATION NOTES
This device is meant only to be installed in the duct portion of the HVAC
system.
If the UV device is installed on the inlet side (return air side) of a coil,
make sure that the HVAC system is configured such that the blower is located
between the return air filter and the in-let of the coil, such as would be
found in a traditional up-flow, or horizontal furnace with the coil placed
after the heat exchanger.
If the UV device is installed near an air filter, check with filter
manufacturer for UV-C resistance properties. Optional lamp shield accessory is
available to protect air filter. Ask your local wholesaler.
If the desired UV installation location is intended to irradiate an air
filter, to neutralize the microbiological matter on the air filter surface,
such as would be found in the return air drop of a basement application or in
the return plenum of a horizontal system in an attic; take precautions as
described in note above, and make sure the UV fixture is placed on the return
side of the filter. DO NOT INSTALL THE UV FIXTURE ON EITHER SIDE OF THE FILTER
IN HALL / CLOSET RETURN AIR APPLICATIONS.
WARNING
UV Light Hazard.
Can cause serious eye and skin damage.
Do not look at UV-C light. Wear UV-C eye and skin protection.
W-COIL/ABOVE A-COIL INSTALLATION (Remote Lamp)
- Disconnect power to the air handler and open access panels.
- Magnetic Bracket Installation – Slit insulation on the back or side wall of air handler and attach magnetic bracket to the wall.
- Standard Bracket Installation – Install the lamp bracket at the desired location with two self-drilling screws (included).
- Secure the lamp to the lamp bracket with the provided knurled nuts.
- Connect remote mount lamp power cord.
A-COIL DELTA PLATE INSTALLATION (Remote Lamp)
- Drill a 7/8” hole into the delta plate and place gasket (included) around hole.
- Insert lamp directly into hole and secure the lamp to the delta plate with two self-drilling screws. (Screws and rubber washers Included.)
- Connect remote mount lamp power cord. Note: A-Coil delta plate installation does not use lamp bracket.
Fig. 3. Insert lamp into delta plate hole and secure with screws and washers. Connect remote lamp power cord.
NOTICE
Clean lamp prior to installation.
Use a cotton cloth to remove dirt and fingerprints. Failure to clean the lamp
could shorten the lamp’s lifespan.
WARNING
UV Light Hazard.
Can cause serious eye and skin damage.
Do not look at UV-C light. Wear UV-C eye and skin protection
A-COIL DELTA PLATE INSTALLATION (Direct Connect™)
- Drill a 7/8” hole in the outer sheet metal where the lamp will be centered on the return side of the coil. See diagram.
- Place gasket (included) around hole.
- Insert lamp into power module and secure with self-drilling screws. (Included.)
- Insert lamp/power module assembly directly into hole and secure with selfdrilling screws (Included.) Note: A-Coil delta plate installation does not use lamp bracket.
Fig. 4 Insert lamp into power module and secure with screws.
Fig. 4A Insert assembly into delta plate hole and secure with screws.
INSTALL POWER MODULE (Remote Lamp)
-
With the lamp cordage facing away from the mounting surface, use the long mounting screws and install the power module in a suitable location inside the control panel of the air handler using two self-drilling screws (included).
NOTE: DO NOT OVERTIGHTEN SCREWS. -
Connect the power module to constant 24V power.
-
Connect input 24V power cord. Align markers on power module with power cord connector.
Fig. 5A Flip power module over and secure with long screws. Do not overtighten.
INSTALL POWER MODULE (Direct Connect™)
- With the lamp directly connected to the power module, connect the power module to the mounting surface using the short, self drilling screws (included).
- Connect the power module to constant 24V power.
- Connect input 24V power cord. Align markers on power module with power cord connector.
The device must be installed in compliance with all national and local electrical and mechanical codes. Failure to do so will void warranty.
WARNING
Electric Shock Hazard.
Can cause injury or death.
Disconnect all electrical power supplies before servicing.
WARNING
For Use with 24V Only..
Do not exceed voltage rating.
Severe damage to device and/or fire could result. Verify proper voltage.
24V INSTALLATION NOTES
Installing the 24V UV fixture may require an upgrade to the 24V transformer in the furnace, or air handler, depending upon the capacity of the OE specified by the manufacturer of the AHU / furnace.
-
Verify the available volt amps prior to connecting the UV fixture to the 24V circuit.
Energize all 24V components so they reach their maximum amp load (Straight cool system – activate cooling. Heat pump – activate heating mode.) -
After obtaining the available volt amps, determine if the existing transformer can accommodate a 1.4 amp load:
-
After installing the UV fixture, energize all 24V components at their full amp draw, including the UV fixture, and ensure that all systems are operational and that fuses remain intact.
-
RECOMMEND CONNECTING TO A DEDICATED 40VA CLASS 2 TRANSFORMER IF EXISTING TRANSFORMER CANNOT ACCOMMODATE AMP LOAD RECOMMENDED ABOVE.
CONNECT LAMP
- Connect lamp connector to power module connector. Connectors are keyed for proper alignment. Be sure to fully seat the connectors for proper electrical connection and water resistance.
NOTICE
Fully Seat Lamp Connector.
Failure to properly seat lamp connector could result in improper lamp
operation and/or compromise water resistance.
INSTALL UV SAFETY VIEWPORT
- Adhere the provided UV safety label to the outside of the duct near the installation location and drill a 5/8” hole as indicated on the label. Press the UV safety viewport into hole.
- Close all access panels and reconnect power to the air handler.
- Verify that a blue glow can be seen through the UV safety viewport.
NOTICE
Replace Lamp Per Recommended Maintenace Schedule.
UV-C lamps expend their germicidal effectiveness over time. Replace the lamp
even if the lamp appears to be operating normally.
WARRANTY
TECHPURE 24V GERMICIDAL UV SYSTEM LIMITED WARRANTY
TopTech warrants this UV-C Light to be free from defects in materials and
workmanship under normal use and service, for a period of five (5) years from
the date of purchase. This warranty does not cover UV-C lamp(s), which carry
a two(2) year warranty from the date of installation.
This warranty does not cover cosmetic damage, damages due to acts of God,
damage as a result of handling or shipment, negligence, misuse, connection to
improper voltage, improper maintenance, or abuse. This warranty is void if
defect(s) result from failure to have this unit installed by a qualified,
properly licensed, heating and air conditioning contractor in compliance with
all local building and construction codes.
TopTech’s exclusive obligation under this warranty shall be to supply, without
charge, a replacement for any covered component of the UV-C Light which is
found to be defective within the parameters defined herein. TopTech reserves
the right to replace or repair the defective part or component.
TOPTECH SHALL NOT BE LIABLE FOR ANY LOSS OR DAMAGE OF ANY KIND, INCLUDING ANY
INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING, DIRECTLY OR INDIRECTLY, FROM
ANY BREACH OF WARRANTY, EXPRESS OR IMPLIED, OR ANY OTHER FAILURE OF THIS
PRODUCT. (Some states do not allow the exclusion or limitation of incidental
or consequential damages, so this limitation may not apply to you.) THE
WARRANTIES SET FORTH HEREIN ARE EXCLUSIVE AND TOPTECH EXPRESSLY DISCLAIMS ALL
OTHER WARRANTIES, WHETHER WRITTEN OR ORAL, IMPLIED OR STATUTORY, INCLUDING
BUT NOT LIMITED TO ANY WARRANTIES OF MERCHANTABILITY, WORKMANSHIP, OR FITNESS
FOR A PARTICULAR USE. If the limited warranty is void due to failure to use a
qualified contractor all disclaimers of implied warranties shall be effective
upon installation.
How to make a warranty claim or have questions answered:
Should you have a warranty claim or questions about the warranty policy,
contact the distributor or dealer from which you purchased the product.
Proof of original purchase and proof of identity that the original purchasing
party is filing the claim is required in order to initiate a warranty claim.
Defective parts must be returned no later than thirty (30) days after the
failure to the installing contractor together with the model number, serial
number, and date of installation. All service and removal must be performed
by a licensed HVAC contractor. You must pay shipping charges and all other
costs of warranty service. Warranty is only valid in the united States and
Canada. THIS WARRANTY SHALL NOT OBLIGATE THE MANUFACTURER FOR ANY LABOR COSTS
AND SHALL NOT APPLY TO DEFECTS IN WORKMANSHIP OR MATERIALS FURNISHED BY THE
INSTALLING CONTRACTOR AS CONTRASTED TO DEFECTS IN THE GERMICIDAL LIGHT ITSELF.
NOTE: Do not return any products or parts to the factory without a
factory issued Return Authorization number issued by the TopTech customer
service department. In the event you have any questions concerning the use
and care of this product or this warranty which have not been answered to your
satisfaction by the distributor or dealer, please call or write the factory.