resideo Aquastat Controllers Instruction Manual
- June 7, 2024
- resideo
Table of Contents
L4006,L4007 Aquastat Controllers
INSTALL ATION INSTRUCTIONS
APPLICATION
These boiler-mounted, immersion-type controllers operate in response to
temperature changes in hydronic heating systems.
L4006A, C; L4007 A breaks the circuit on a temperature rise to the control
setting. They are used tor high limit or low limit control. When used as a
controller or as a low limit, a separate high limit must be used.
L4006B, L4007Bmake the circuit on a temperature rise. They are used as a
circulator controller, delaying circulator operation if boiler water
temperature is below the control setting.
L4006E (horizontal well with vertical option) models include a trip-tree
manual reset switch. Whenever the temperature of the controlled medium reaches
the high limit setting, these models are designed to break the control
circuit. A reset button at the front of the case
must be pressed to re-establish the control circuit.
L4006G includes two switches that break simultaneously on temperature rise to
the control setting. This model is used tor high limit and circulator control.
Depending on the model, the Aquastat controllers may include:
- bulb compression sitting (L4006C only),
- immersion well tor mounting vertically, or
- immersion well for mounting horizontally.
INSTALLATION
When Installing this Product…
- Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
- Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
- The installer must be a trained, experienced service technician.
- After installation is complete, check out product operation as provided in these instructions.
CAUTION
Disconnect power supply before beginning installation to prevent electrical
shock or equipment damage. Mounting The boiler manufacturer generally provides
a tapping for insertion of the Aquastat controller’s sensing element. This
tapping is located in a representative point where the typical boiler water
temperature can be measured. Depending on the model, the element is either
inserted in an immersion well or through a bulb compression fitting.
It immersion well or bulb compression fitting must be ordered, refer to form
68-0040 “Wells and Fittings for Temperature Controllers,” for part numbers and
ordering information.
For Models Using an Immersion Well
The well of the Aquastat controller must always be exposed to average
temperature circulating water, and must never be located close to a hot or
cold inlet or steam coil. Where the tapping is on the side of the boiler, use
an Aquastat controller in which the well can be mounted horizontally. Where
the tapping is on top ot the boiler, use a model in which the well can be
mounted vertically. Some models include an adapter for vertical or horizontal
mounting. See Fig. 2.
IMPORTANT
The controller may be used with or without immersion well. Well, if used, must
fit sensing bulb snugly tor good thermal response. The bulb should be inserted
until it rests against the bottom of the well. then hold it there while
tightening the tubing clamp.
NOTE: Some models have an adjustable tubing length of 3 in. [716 mm]. In these models, extra tubing inside the case may be pulled out, if needed. Follow the mounting instructions furnished by the system manufacturer if available; otherwise. proceed as follows.
Installing the Immersion Well
On existing installations, shut off the power and remove the old control. If
the old immersion well appears suitable, and if the adapter clamp on the
Aquastat controller fits the old well spud, this well need not be replaced.
To install a new well:
- If the system is filled, drain the system to a point below the boiler tapping.
- Remove old well from boiler tapping.
- Install the immersion well. Both 1/2 and 3/4 inch x 14 NPT wells are available. Depending on size of boiler tapping and model ordered, a reducer fitting may be required.
- Fill the system. Make sure that the well is screwed in tightly enough to prevent leakage. Do NOT use the case as a handle to tighten well after the controller is secured to the well.
M38421
Fig. 1. Internal view showing L4006 (model with horizontal well).
- 1MODELS WITH FIXED DIFFERENTIALS DO NOT INCLUDE ADJUSTING WHEEL.
- A VERTICALLY MOUNTED IMMERSION WELL IS ATTACHED TO THE BOTTOM OF THE CASE.
- L4006G INCLUDES TWO SPST SWITCHES.
For Installation of Sensing Bulb in Immersion Well
- Loosen screw (at top of the case, above scale setting)and remove the cover. Loosen 2 screws that secure the adapter clamp. See Fig. 1.
- Insert the sensing element into the immersion well.
- Fasten the case of the Aquastat controller to the well with the adapter clamp. Make certain that the clamp is properly positioned over the groove of the good spud. Also, be sure the flange at the opening of the well fits snugly into the opening of the case.
The sensing bulb must bottom in the well for best temperature response.
Fig. 2. Mounting bracket placement for vertical or horizontal mounting.
Fig. 3. Direct Immersion model with bulb compression fitting partially removed.
Models Designed for Direct Immersion (without well)
For either horizontal or vertical placement of the mounting bracket, see Fig.
2. Some models, which provide for direct immersion of the sensing element into
the boiler, include a bulb compression fitting instead of an immersion well.
Install fitting in boiler tapping. Be sure the sealing washer is in place as
shown in Fig. 3. Make sure that the spud of the fitting is screwed in tightly
enough to prevent leaking. Insert sensing bulb through the fitting. Adjust the
adapter clamp so that it fits over the groove at the opening of the fitting.
Tighten adapter clamp screws so that the Aquastat controller is firmly
attached to the fitting.
WIRING
Disconnect power supply before connecting wiring to avoid electrical shock or
equipment damage.
All wiring must comply with local electrical codes and ordinances.
Refer to Fig. 4–9 for typical diagrams of Aquastat controllers used in heating
systems.
M1054C
Fig. 4. Typical hookup for oil-fired gravity system, using L4006A or L4007A.
- POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
M2855C
Fig. 5. Hookup for an oil-fired, summer-winter hydronic system with domestic hot water using L4006A or B, L4007 A or B. This Is typical where control for domestic hot water is added, or where each Aquastat controller is mounted in a separate location.
- POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
- USE L4006E FOR MANUAL RESET.
M2856D
Fig. 6. Typical hookup for a gas-fired system with domestic hot water, using L4006A,E, or L4007A.
- POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
- USE L4006E FOR MANUAL RESET.
M1154
Fig. 7. Typical wiring diagram for 24 V gas system using L4006C.
M1156C
Fig. 8. Typical Powerpile system wiring diagram, using L4006C.
M1155C
Fig. 9. Typical systems with 120 V electrical heal primaries, using L4006C.
- POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
OPERATION
For proper selection of settings, follow the boiler manufacturer’s recommendations.
-
High limit controller—shuts off the burner if water temperature exceeds high limit setting. Burner restarts when the temperature drops to high limit setting, less differential.
NOTE:
If L4006E, see Manual Reset below. -
Low limit controller—maintains minimum boiler temperature for domestic hot water. Turns on burner at temperature setting, minus differential.
-
Circulator controller—prevents circulation of water that is not hot enough. Breaks circulator circuit at temperature setting minus differential, remakes at setting.
ADJUSTING
Set the differential to correspond with the boiler manufacturer’s
recommendations. To adjust models with adjustable differential, rotate the
wheel on the back of the snap switch until the desired reading is aligned with
the “V” notch in the frame. The wheel provides an adjustment from 5 F to 30 F
(3 C to 1 7 C). Replace the cover on the Aquastat controller.
Adjust the control point to correspond with the boiler manufacturer’s
recommendations. To adjust insert a screwdriver in the slotted screw type head
located beneath the window in the cover. Turn the scale to the desired control
point.
Manual Reset
If the device includes a manual reset (model L4006E), be sure to press the red reset button on the front of the case to make sure that the controller is not locked out on safety. In checking out the system, adjust the limit setting low enough so that the temperature of the controlled medium reaches the high limit setting. When the limit setting is reached, the Aquastat controller locks out and the burner shuts down. When the temperature of the controlled medium drops to the high limit setting, minus differential, push the manual reset button and the system should again be operative. Reset control to the proper high limit setting.
CHECKOUT
Check to make certain the Aquastat controller has been installed and adjusted
properly. Put the system into operation and observe the action of the device
through several cycles to make certain that it provides proper control of the
system as described under OPERATION.
Further adjustments can be made to meet more exact comfort requirements.
Resideo Technologies, Inc.
1985 Douglas Drive North, Golden Valley, MN 55422
1-800-468-1502
95-6120B—05 M.S. Rev. 05-20 | Printed in the United States
© 2020 Resideo Technologies, Inc. All rights reserved.
This product is manufactured by Resideo Technologies, Inc. and its affiliates.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>