resideo V9406 Braukmann Verafix-Cool User Guide
- June 7, 2024
- resideo
Table of Contents
resideo V9406 Braukmann Verafix-Cool
APPLICATION
V9406 Verafix-Cool control and measuring valves are preferably installed in
the return of heat exchangers, for example fan coil units or chilled ceilings.
They regulate the room temperature by controlling the flow in connection with
an actuator.
With the V9406 Verafix-Cool the flow can either be preset according to the
diagram on page 6 or, in combination with a measuring instrument, by flow
measurement.
SPECIAL FEATURES
- Flow measuring and presetting on one valve at the same time
- Six functions in one valve: control, presetting, shut-off, measuring, draining and filling
- Compact design
- Suitable for operating pressures up to 16 bar
- Robust, low-noise and flow-efficient valve housing made of corrosion-resistant red bronze
Media
Medium:| Water or water-glycol mixture, quality to VDI 2035
pH-value:| 8 – 9.5
Connections/Sizes
Nominal size:| DN15
Pressure values
Max. operating pressure:| max. 16 bar (232 psi)
Operating temperatures
Water:| 2 – 130 °C (36 – 266 °F)
Water-glycol mixtures:| 2 – 110 °C (36 – 230 °F)
Specifications
kvs (cv)-values:| 2.5 (2.91)
Max. close-off pressure with
180N actuator:
| 1.0 bar (14.5 psi)
Leakage rate:| 0.02 % of kvs-value
Rangeability:| 50:1
Stroke:| 3 mm
Closing dimension:| 11.5 mm
Actuator connection:| M30 x 1.5
CONSTRUCTION
Overview | Components | Materials |
---|
| 1| Presentable
control insert with protection cap| White plastic
2| Valve housing PN16, DN15 with 3/4″ flat sealing external threads to
DIN/ISO 228.
Suitable pipe connections see ‘Accessories’| Red bronze
| Not depicted components:
| Measuring insert with cap| Brass with PTFE sealing ring
Union-nuts and sealings| Brass with EPDM sealing rings
Valve insert| Brass with EPDM O-rings and soft seals
METHOD OF OPERATION
The V9406 Verafix-Cool is installed in the return of a heat exchanger and
controlled by an actuator. The actuator acts onto the spindle of the control
insert and in this way regulates the flow through the valve. In a cooling
application the actuator closes the valve when the room temperature drops and
opens the valve when the room temperature rises. The V9406 Verafix-Cool can
also be used for heating applications, in this case operation is the other way
round.
Without mounted actuator the valve is normally open. The maximal flow rate can
be throttled by presetting the control insert. Presetting is either done
according to the flow diagram on page 6 or by flow measurement. A measuring
instrument can be connected to the valve by using the V9406 Verafix-MES
adapter (accessory). Presetting and flow measurement can be done at the same
time. The effect of a changed presetting is immediately displayed by the
measuring instrument.
The V9406 Verafix-Cool can optionally be installed in the supply. In that case
the draining function isn’t available for the connected heat exchanger as the
part of the system before the V9406 Verafix-Cool is drained.
Suitable Actuators
- M6410/M7410 with 180N
Marking
- MNG, DN15 and flow arrow on front
- MNG, PN16 and flow arrow on back
- White manual adjustment cap on top
- Brass nickel-plated protection cap with 19 mm hexagon on bottom
INSTALLATION GUIDELINES
Installation Example
Fig. 1 Regulation of chilled ceilings: a V9406 Verafix-Cool is fitted in
the return pipe of chilled ceiling systems.
Fig. 2 Due to the high kvs-value, a single V9406 Verafix-Cool can be used
to control several ceiling elements connected in parallel.
Shut-off
Use protection cap for longer-term shut-off
Presetting:|
5
| 8| 13| 16.0|
20 = open
---|---|---|---|---|---
kv-value:|
0.63
| 1.0| 1.6| 2.0|
2.5
cv-value:|
0.73
| 1.16| 1.86| 2.33|
2.91
Draining and Filling
Flow of water during draining
Presetting
Factory setting = 20
Turn back to required pre-setting
Measuring and Presetting
TECHNICAL CHARACTERISTICS
kvs-Values
Presetting:
| 5| 8| 13| 16|
20 = open
---|---|---|---|---|---
kv-value:| 0.63| 1.0| 1.6| 2.0| kvs = 2.5
cv-value:
| 0.73| 1.16| 1.86| 2.33|
2.91
Note: Flow data is only valid for water with a temperature of 5 – 30 °C (41 – 86 °F) When other temperatures or liquids are used the data may vary – see Reference Sheet ’Calculation of Flow Data’ (EN0H-0221GE25)
Flow Data
DIMENSIONS
Overview
1 for installation of actuator
2 for connection of draining adapter
*3 for connection of measuring adapter
Note: All dimensions in mm unless stated otherwise.
Note: Supplied with manual adjustment cap and union-nuts with sealings.
Actuator, draining adapter and measuring adapter have to be ordered separately
(see Accessories).
ORDERING INFORMATION
The following tables contain all the information you need to make an order of an item of your choice. When ordering, please always state the type, the ordering or the part number.
Options
Order text:
| DN:| Connection size:| k vs (c vs )-value:|
OS-No.:
---|---|---|---|---
V9406 Verafix-Cool control and measuring valve| 15| G3/4″A| 2.5 (2.91)|
V9406DX015
Accessories
|
Description
| Dimension|
Part No.
---|---|---|---
| VA3300|
Draining adapter
| | VA3300A001
| VA8300|
Special Verafix-key
| | VA8300A001
| VA3301|
Measuring adapter
| | VA3301A001
| VA5500|
Externally threaded brass tailpiece, flat sealing
to DIN 2999| R1/2″| VA5500A015
NPT thread!| NPT1/2| VA5501A015
| VM242A|
BasicMes-2 handheld measuring computer
Note: To connect the VM241 BasicMes to SafeConTM pressue test cocks please
order measuring adapter VA3600C001 separately.
| Computer is supplied with case and accessories| for all sizes| VM242A0101
| VA5930| Brass
soldering tailpiece, flat sealing
| 15 mm| VA5930A015
| 16 mm| VA5930A016
| VA5540| Steel
welding tailpiece, flat sealing
| 1/2″| VA5540A015
| VA5920|
Internally threaded nickel-plated brass tailpiece, flat sealing
| Rp1/2″| VA5920A015
Manufactured for and on behalf of Pittway Sàrl, Z.A., La Pièce 4, 1180 Rolle,
Switzerland by its authorised representative Ademco 1 GmbH
© 2020 Resideo Technologies, Inc. All rights reserved.
For more information
homecomfort.resideo.com/europe
Ademco 1 GmbH, Hardhofweg 40, 74821 MOSBACH, GERMANY
Phone: +49 6261 810
Fax: +49 6261 81309
Subject to change. EN0H-0198GE25 R0420
References
Read User Manual Online (PDF format)