resideo VR4304 Intermittent Pilot Combination Gas Control Installation Guide
- June 7, 2024
- resideo
Table of Contents
VR4304
Intermittent Pilot
Combination Gas Control
INSTALL ATION INSTRUCTIONS
APPLICATION
These intermittent pilot gas controls are used in gasfired appliances with
capacities up to 300 feet 3 /hour at 1-inch WC pressure drop [8.5 meters
3/hour at 0.25 kPa] for natural gas. They include a manual valve, two
automatic operators, a pressure regulator, pilot adjustment, and a conduit
cover.
The ambient temperature range for the standard opening model (VR4304M) is
-40° to +175°F [-40° to +79°C].
Body Pattern: Straight-through.
Inlet x Outlet Sizes Available: 1/2 x 3/4 inch and 3/4 x 3/4 inch.
This gas control comes with two 3/4 to 1/2 inch NPT bushings and one 1/2 to
3/8 inch NPT bushing.
Adapters: Adapters available for 1/2 and 3/4 inch straight and angle
connections. Refer to Table 2.
Electrical Ratings:
Voltage and Frequency: 120 Vac, 60 Hz.
Current Draw: 0.14A.
Capacity:
Size (Inlet x Outlet)| Capacity (at 1 inch we
pressure drop)a| Minimum Regulated
Capacity| Maximum Regulated
Capacity
---|---|---|---
1/2 x 1/2| 240 feet3/hour [6.8 meter3/hour]| 30 feet3/hour [0.8 meter3/hour]|
340 feet3/hour [9.6 meter3/hour]
1/2 x 3/4| 270 feet3/hour [7.6 meter3/hour]| 30 feet3/hour [0.8 meter3/hour]|
370 feet3/hour [10.5 meter3/hour]
3/4 x 3/4| 300 feet3/hour [8.5 meter3/hour]| 30 feet3/hour 0.8 meter3/hour]|
415 feet3/hour [11.8 meter3/hour]
Capacity based on 1000 Btu/feet³, 0.64 specific gravity natural gas at 1-inch WC pressure drop [37.3 MJ/meter³, 0.64 specific gravity natural gas at 0.25 kPa pressure drop].
Use conversion factors in Table 1 to convert capacities for other gases.
Table 1. Gas Capacity Conversion Factors.
Gas | Specific Gravity | Multiply Listed Capacity By |
---|---|---|
Manufactured | 0.60 | 0.516 |
Mixed | 0.70 | 0.765 |
Propane | 2. | 2. |
Table 2. Adapter (Flange) Part Numbers.
Inlet/Outlet
Pipe Size| Flange Type| Part Number
---|---|---
Without Hex
Wrench| With Hex
Wrench
1/2 inch NPT| Straight| 393690-6| 393690-16
Elbow| 393690-3| 393690-13
3/4 inch NPT| Straight| 393690-4| 393690-14
Elbow| 393690-5| 393690-15
Approvals:
American Gas Association design certificate: L2025007.
Canadian Gas Association design certificate: L2025007.
Australian Gas Association design certificate: Applied for.
Delta C.
INSTALLATION
WHEN INSTALLING THIS PRODUCT…
- Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
- Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
- The installer must be a trained, experienced service technician.
- After installation is complete, use these instructions to check out product operation.
WARNING
FIRE OR EXPLOSION HAZARDS CAN CAUSE
PROPERTY DAMAGE, SEVERE INJURY, OR DEATH
Follow these warnings exactly:
- Disconnect power supply before wiring to prevent electrical shock or equipment damage.
- To avoid the dangerous accumulation of fuel gas, turn off the gas supply at the appliance service valve before starting the installation, and perform Gas Leak Test after completion of installation.
- Do not bend pilot tubing at gas control or pilot burner after compression fitting has been tightened because gas leakage at the connection can result.
- Always install sediment trap in the gas supply line to prevent contamination of gas control.
- Do not force the gas control knob. Use only your hand to turn the gas control knob. Never use any tools. If the gas control knob will not operate by hand, call a qualified service technician to replace the gas control. Force or attempted repair can result in fire or explosion.
CAUTION
- Never apply a jumper across or short the valve coil terminals. This can burn out the heat anticipator in the thermostat or damage the electronic intermittent pilot (IP) module.
- When a gas control is installed external to the appliance, a conduit cover must be installed. See Fig. 1. Place the conduit cover over the flange, then rotate the conduit cover into position.
IMPORTANT
These gas controls are shipped with protective seals over inlet and outlet
tappings. Do not remove seals until ready to connect piping. Follow the
appliance manufacturer instructions if available; otherwise, use the following
instructions.
CONVERTING BETWEEN NATURAL AND LP GAS
WARNING
FIRE OR EXPLOSION HAZARDS CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY, OR
DEATH
Do not attempt to use a gas control set for natural gas on LP gas or a gas
control set for LP gas on natural gas.
Convert standard-opening gas controls from natural gas to LP gas with the
conversion kit included with this gas control. Part number 393691 will convert
from natural to LP gas. Part number 394588 will convert from LP to natural
gas.
INSTALL ADAPTERS TO GAS CONTROL
Install adapters to gas control as follows:
Flanges
- Choose the appropriate flange for your application.
- Remove seal over gas control inlet or outlet.
- Make sure the O-ring fits into the flange groove. If the O-ring is not attached or is missing, do not use the flange.
- With the O-ring facing the gas control, align the screw holes on the gas control with the holes in the flange. Insert and tighten the screws provided with the flange. See Fig. 1. Tighten the screws to 25 inch-pounds of torque to provide a gas-tight seal.
Bushings
- Remove seal over gas control inlet or outlet.
- Apply a moderate amount of good quality pipe compound to bushing, leaving two end threads bare. See Fig.
- On an LP installation, use compound resistant to LP gas. Do not use Teflon tape. 3. Insert bushing in gas control and carefully thread pipe into the bushing until tight.
USING ADAPTERS TO SOLVE SWING
RADIUS PROBLEMS
In some field service applications, space limitations make it difficult or
impossible to thread the gas control onto the gas supply pipe. This problem
can be resolved for many installations by using an adapter. Install the
adapter on the end of the supply pipe in place of the gas control by following
the same precautions and instructions that are used for installing the gas
control. after the adapter is installed, attach the gas control to the adapter
as outlined above.
NOTE: Using an adapter increases the overall length of the gas control.
LOCATION
Locate the combination gas control in the appliance vestibule on the gas
manifold. In replacement applications, locate the gas control in the same
location as the old control.
Do not locate the gas control where it can be affected by steam cleaning, high
humidity, dripping water, corrosive chemicals, dust or grease accumulation, or
excessive heat.
To safeguard proper operation, follow these guidelines:
- Locate gas control in a well-ventilated area.
- Mount gas control high enough above the cabinet bottom to avoid exposure to flooding or splashing water.
- Make sure the ambient temperature does not exceed the ambient temperature ratings for each component.
- Cover gas control when the appliance is cleaned with water, steam, or chemicals or to avoid dust and grease accumulation.
- Avoid locating gas control where exposure to corrosive chemical fumes or dripping water is possible.
Install Piping to Gas Control
All piping must comply with applicable codes and ordinances or with the
National Fuel Gas Code (ANSI Z223.1 NFPA No. 54), whichever applies. Tubing
installation must comply with approved standards and practices.
- Use new, properly reamed pipe free from chips. If tubing is used, make sure the ends are square, deburred, and clean. Make sure all tubing bends are smooth and without information.
- Run pipe or tubing to the gas control. If tubing is used, obtain a tube-to-pipe coupling to connect the tubing to the gas control.
- Install sediment trap in the supply line to the gas control. See Fig. 2.
Install Gas Control
-
This gas control can be mounted from 0 to 90 degrees in any direction from the vertical position of the gas control knob.
-
Mount the gas control so gas flow is in the direction of the arrow on the bottom of the gas control.
-
Thread pipe the amount shown in Table 3 for insertion into the gas control or flange. Do not thread pipe too far. Valve distortion or malfunction can result when the pipe is inserted too deeply into the gas control.
-
Apply a moderate amount of good quality pipe compound (do not use Teflon tape) to pipe only, leaving two end threads bare. On LP installations, use compound resistant to LP gas. Refer to Fig. 3.
-
Table 3. NPT pipe thread length in (in.). Pipe Size| Thread Pipe this Amount| The maximum Depth Pipe can be Inserted into the Control
---|---|---
3/8| 9/16| 3/8
1/2| 3/4| 1/2
3/4| 13/16| 3/4
- Remove seals over gas control inlet and outlet if necessary.
- Connect the pipe to the gas control inlet and outlet. Use a wrench on the square ends of the gas control. If a flange is used, place the wrench on the flange rather than on gas control. Refer to Figs. 4 and 5.
Connect Pilot Gas Tubing
-
cut tubing to the desired length and bend as necessary for routing to pilot burner. Do not make sharp bends or deform the tubing. Do not bend tubing at gas control or pilot burner after compression fitting has been tightened because this can result in a gas leakage at the connection.
-
Square off and remove burrs from the end of the tubing.
-
Use the compression fitting supplied with this gas control. Slip the fitting over the tubing and slide out of the way.
NOTE: When replacing a gas control, cut off the old compression fitting and replace it with the new compression fitting provided on the gas control. Never use the old compression fitting because it may not provide a gas-tight seal. -
Push tubing into the pilot gas tapping on the outlet end of the control until it bottoms. While holding tubing all the way in, slide compression fitting into place, engage threads and turn until finger tight. Then tighten one more turn with a wrench. Do not overtighten. Refer to Fig. 6.
-
Connect another end of the tubing to the pilot burner according to the pilot burner manufacturer’s instructions.
WIRING
Follow the wiring instructions furnished by the appliance manufacturer, if
available, or use the following general instructions are provided below. Where
these instructions differ from the appliance manufacturer, follow the
appliance manufacturer instructions.
All wiring including insulated quick-connect terminals must comply with
applicable electrical codes and ordinances.
Disconnect power supply before making wiring connections to prevent electrical
shock or equipment damage.
-
Check the power supply rating on the gas control and make sure it matches the available supply. Install the thermostat and other controls as required.
-
When the gas control is installed external to the appliance, install the conduit cover on the conduit fitting. Do not secure the conduit cover at this time.
-
Connect control circuit to gas control terminals. See Figs. 4 and 7.
NOTE: Use lead wires with insulated terminals. -
Make sure the conduit cover is in position and secured to the gas valve with the screw provided. See Fig. 1.
-
Adjust thermostat heat anticipator as instructed in the appliance manual (i.e., usually 0.1A).
STARTUP AND CHECKOUT
WARNING
FIRE OR EXPLOSION HAZARDS CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY, OR
DEATH
- Do not force the gas control knob. Use only your hand to turn the gas control knob. Never use any tools.
- If the gas control knob will not operate by hand, call a qualified service technician to replace the gas control.
GAS CONTROL KNOB SETTINGS
The gas control knob settings are as follows:
OFF: Prevents pilot and main burner gas flow.
ON: Permits gas to flow into the control body. Under control of the thermostat
and intermittent pilot module, gas can flow to the pilot and main burner.
NOTE: Gas controls are shipped with the gas control knob in the ON
position.
TURN ON SYSTEM
Rotate the gas control knob counterclockwise to ON.
TURN ON THE MAIN BURNER
Follow instructions provided by the appliance manufacturer or turn up the
thermostat to call for heat.
PERFORM GAS LEAK TEST
WARNING
FIRE OR EXPLOSION HAZARDS CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY, OR
DEATH
Check for gas leaks with a rich soap and water solution anytime work is done
on gas control.
GAS LEAK TEST
- Paint all pipe connections upstream of the gas control with a rich soap and water solution. Bubbles indicate a gas leak.
- If a gas leak is detected, tighten the pipe connection.
- Stand clear while lighting the main burner to prevent injury caused by hidden gas leaks that could cause flashbacks in the appliance vestibule. Light the main burner.
- With the main burner in operation, paint all pipe joints (including flanges) and gas control inlet and outlet with a rich soap and water solution.
- If another gas leak is detected, tighten flange screws, joints, and pipe connections.
- Replace the part of the gas leak can not be stopped.
ADJUST THE PILOT BURNER FLAME
The pilot flame should envelop 3/8 to 1/2 in. [10 to 13 mm] of the igniter-
sensor tip. Refer to Fig. 8. To adjust the pilot flame:
- Remove the pilot adjustment cover screw. Refer to Fig. 4.
- Turn the inner adjustment screw clockwise to decrease or counterclockwise to increase the pilot flame.
- To prevent gas leakage always replace the cover screw after adjustment.
CHECK AND ADJUST GAS INPUT TO THE MAIN BURNER
CAUTION
-
Do not exceed the input rating stamped on the appliance nameplate, or manufacturer-recommended burner orifice pressure for the sizing orifice(s) used. Make certain the primary air supply to the main burner is properly adjusted for complete combustion (refer to the appliance manufacturer instructions).
-
WHEN CHECKING GAS INPUT BY CLOCKING THE GAS METER:
• Make sure that the only gas flow through the meter is that of the appliance being checked.
• Make certain that other appliances are turned off with pilot burners extinguished (or deduct that gas consumption from the meter reading).
• Convert the flow rate to Btuh as described in Gas Controls Handbook, form 70-2602, and compare to the Btuh input rating on the appliance nameplate. -
WHEN CHECKING GAS INPUT WITH A MANOMETER (PRESSURE GAUGE):
• To connect the manometer, be sure the gas control knob is in the OFF position before removing the outlet pressure tap plug.
• When removing the manometer, turn the gas control knob back to OFF and replace the outlet pressure tap plug.
• Shut off the gas supply at the appliance service valve, or at the gas tank for LP gas, before removing the outlet pressure tap plug and before disconnecting the manometer and replacing the outlet pressure tap plug.
• Perform the Gas Leak Test at the outlet pressure tap plug.
Standard-Opening Pressure Regulator
- The gas control outlet pressure should match the manifold pressure listed on the appliance nameplate.
- With the main burner operating, check the gas control flow rate by using the meter clocking method or check the gas pressure using a manometer connected to the gas control outlet pressure tap. Refer to Fig.4.
- If necessary, adjust the pressure regulator to match the appliance rating. Refer to Table 4 or 5 for the factory set nominal outlet pressures and adjustment setting ranges.
a. Remove the pressure regulator adjustment cap screw.
b. Using a screwdriver, turn the inner adjustment screw clockwise to increase or counterclockwise to decrease the main burner gas pressure.
c. Always replace the cap screw and tighten firmly to safeguard proper operation. 4. If the desired outlet gas pressure or gas flow rate can not be achieved by adjusting the gas control, check the gas control inlet pressure by using a manometer at the inlet pressure tap. If the inlet pressure is in the normal range (refer to Table 4 or 5), replace the gas control. Otherwise, take the necessary steps to provide proper gas pressure to the gas control.
CHECK SAFETY SHUTDOWN PERFORMANCE
WARNING
FIRE OR EXPLOSION HAZARDS CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY, OR
DEATH
Perform the safety shutdown test anytime work is done on a gas system.
NOTE: Read steps 1 through 7 below before starting and compare to the
safety shutdown or safety lockout tests recommended for the intermittent pilot
(IP) module. Where they differ, use the procedure recommended for the module.
- Turn off the gas supply.
- Set the thermostat or controller above room temperature to call for heat.
- Watch for an ignition spark at the pilot burner either immediately or following pre-purge. See IP module specifications.
- If the module has timed ignition, time the length of the igniter operation. See IP module specifications.
- After the module locks out, open the gas control knob and make sure there is no gas flow to the pilot or main burner. With modules that continue to spark until pilot lights or system is shut down manually, the pilot should light when the gas control knob is opened.
- Set the thermostat below room temperature and wait one minute.
- Operate system through one complete cycle to make sure all controls operate properly.
Table 4. Pressure Regulator Specification Pressures in Inches WC.
Model| Type of Gas| Nominal Inlet
Pressure Range| Outlet Pressure
---|---|---|---
Nominal Factory Outlet Setting| Adjustment Setting Range
Full Rate| Full Rate
Standard-opening| Natural| 5.0 – 7.0| 4.| 3.0 – 5.0
LP| 12.0 – 14.0| 10.0| 8.0 – 12.0
Table 5. Pressure Regulator Specification Pressures in kPa.
Model| Type of Gas| Nominal Inlet
Pressure Range| Outlet Pressure
---|---|---|---
Nominal Factory Outlet Setting| Adjustment Setting Range
Full Rate| Full Rate
Standard-opening| Natural| 1 2 – 1.7| 0.9| 0.7 – 1.2
LP| 2.9 – 3.9| 3.| 2.0 – 3.0
MAINTENANCE
WARNING
FIRE OR EXPLOSION HAZARDS CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY, OR
DEATH
Improper cleaning or reassembly can cause gas leakage. When cleaning, be sure
that the control is reassembled properly and perform a gas leak test.
Regular preventive maintenance is important in applications such as commercial
cooking, agricultural and industrial operations that place a heavy load on
the system controls because:
- n many such applications, particularly commercial cooking, the equipment operates 100,000 to 200,000 cycles per year. Such heavy cycling can wear out the gas control in one to two years.
- Exposure to water, dirt, chemicals, and heat can damage the gas control and shut down the control system.
The maintenance program should include regular checkout of the gas control; see Startup and Checkout section. To check out the control system, see the appliance manufacturer literature. Maintenance frequency must be determined individually for each application. Some considerations are:
- Cycling frequency. Appliances that may cycle 100,000 times annually should be checked monthly.
- Intermittent use. Appliances that are used seasonally should be checked before shutdown and again before the next use.
- A consequence of unexpected shutdown. Where the cost of an unexpected shutdown would be high, the system should be checked more often.
- Dusty, wet, or corrosive environment. Since these environments can cause the gas control to deteriorate more rapidly, the system should be checked more often.
If the gas control will be exposed to high ammonia conditions, e.g., those used in greenhouses or animal barns, contact your Resideo sales representative to request a gas control with corrosion-resistant construction. The gas control should be replaced if:
- It does not perform properly during checkout or troubleshooting.
- The gas control knob is hard to turn or push down or it fails to pop back up when released.
- The gas control is likely to have operated for more than 200,000 cycles.
SERVICE
WARNING
FIRE OR EXPLOSION HAZARDS CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY, OR
DEATH
Do not disassemble the gas control; it contains no replaceable components.
Attempted disassembly or repair can damage the gas control.
CAUTION
Do not apply a jumper across or short the valve coil terminals. Doing so can
burn out the heat anticipator in the thermostat or damage the electronic
module.
IF THE MAIN BURNER WILL NOT COME ON WITH CALL FOR HEAT
-
Make sure the gas control knob is in the ON position.
-
Adjust the thermostat several degrees above room temperature.
-
Using an ac voltmeter, check for voltage at the gas control.
• If pilot lights, measure across MV/PV and MV.
• If the pilot does not light, measure across MV/PV and PV before safety lockout occurs. -
If voltage is not present, check the control circuit for proper operation.
-
If proper control circuit voltage is present, replace gas control.
INSTRUCTIONS TO THE HOMEOWNER (FOR YOUR SAFETY, READ BEFORE OPERATING)
WARNING
FIRE OR EXPLOSION HAZARDS CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY, OR
DEATH
Follow these warnings exactly:
-
The pilot flame is lit automatically. Do not light the pilot flame manually.
-
Before lighting the pilot burner flame, smell around the appliance for gas. Be sure to smell next to the floor because LP gas is heavier than air.
-
IF YOU SMELL GAS:
• Turn off the gas supply at the appliance service valve. On LP gas systems, turn off the gas supply at the gas tank.
• Do not light any appliances in the house.
• Do not touch electrical switches or use the phone.
• Leave the building and use a neighbor’s phone to call your gas supplier.
• If you can not reach your gas supplier, call the fire department. -
Do not force the gas control knob. Use only your hand to push down or turn the gas control knob. Never use any tools. If the gas control knob will not operate by hand, call a qualified service technician to replace the gas control. Force or attempted repair can result in a fire or explosion.
-
Call a qualified service technician to replace the gas control if it has been flooded with water.
-
Replace the gas control in the event of any physical damage, tampering, bent terminals, missing or broken parts, stripped threads, or evidence of exposure to heat.
IMPORTANT
Follow the operating instructions provided by the manufacturer of your heating
appliance. The information below will be of assistance in a typical gas
control application, but the specific controls used and the procedures
outlined by the manufacturer or your appliance may differ and require special
instructions.
TO TURN ON THE APPLIANCE
STOP: READ THE WARNINGS ABOVE.
The pilot flame is lit automatically. Do not attempt to manually light the
pilot. If the appliance does not turn on when the thermostat is set several
degrees above room temperature, follow these instructions:
- Set the thermostat to its lowest setting to reset the safety control.
- Disconnect all electric power to the appliance.
- Remove the gas control access panel.
- Push in the gas control knob slightly and turn clockwise to OFF.
- Wait five minutes to clear out any unburned gas. If you then smell gas, STOP! Follow step 3 in the Warning in the Instructions To The Homeowner section. If you do not smell gas, continue with the next step.
- Turn the gas control knob counterclockwise to ON.
- Replace the gas control access panel.
- Reconnect all electric power to the appliance.
- Set the thermostat to the desired setting.
- If the appliance does not turn on, set the gas control knob to OFF and contact a qualified service technician for assistance.
TURNING OFF THE APPLIANCE
VACATION SHUTDOWN—Set the thermostat to the desired room temperature while you
are away.
COMPLETE SHUTDOWN—Push in the gas control knob slightly and turn clockwise to
OFF. Do not force. The appliance will completely shut off. Follow the
Instructions to the Homeowner above to resume normal operation.
Resideo Technologies, Inc.
1985 Douglas Drive North, Golden Valley, MN 55422
1-800-468-1502
69-0838—01 M.S. 06-20 | Printed in the United States
www.resideo.com
© 2020 Resideo Technologies, Inc. All rights reserved.
This product is manufactured by Resideo Technologies, Inc. and its affiliates.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>