EMERSON 3485FCSD Vilter Vission 20/20 Software Instructions

June 7, 2024
Emerson

EMERSON LOGO Instructions for Important Product Safety Notice
Vilter Vission 20/20 Software Part Number 3485FCSD

EMERSON 2 Vission 20/20 ™ Version

Step 1: Checking program version to determine Safety Notice

Applicability

  1. Locate and press Help from any screen

  2. Click Help button
    EMERSON 3485FCSD Vilter Vission - FIG1

  3. In the Help screen, locate and press the Version button
    EMERSON 3485FCSD Vilter Vission - FIG2

  4. A pop-up dialog will appear with the Software Version

NOTE: Determine if the current revision of the software recall is listed here”
EMERSON 3485FCSD Vilter Vission - FIG3 IF LISTED: Continue on with the instructions below:

EMERSON 3485FCSD Vilter Vission - FIG4

Vission 20/20™ Program Disk

Before replacing the flashcard, Vilter recommends that you back up the setpoints on a USB drive. Otherwise, you will have to manually re-enter all values

Step 2: Backup/Restore Procedure

EMERSON 3485FCSD Vilter Vission - FIG5

The compressor must be off to backup or restore setpoints
Backup Procedure:

  1. Log on via the User Access screen

  2. Insert a USB drive into any of the USB ports located on the SBC

  3. Enter the “Data Backup” screen from the main menu

  4. The USB Drive should show up under the “Available
    Devices” window as /Media/usb0 or usb1 etc.

  5. Touch /Media/usb0 then touch the Filename window to add a backup file name to the end of /Media/usb0.

  6. Press the “Save” button on the bottom of the screen.

  7. Press “Unmount” to remove the USB drive

Restore Procedure:

  1. Repeat steps 1-4 from above
  2. Touch “Load” from the top left of the screen
  3. Touch the backup file from the “Select Folder/File” window
  4. Press the “load” button on the bottom right of the screen.
  5. A pop-up will inform you the program will restart, press “OK” to continue
  6. Other pop-ups will display asking you other questions, press “Ok” to continue.
  7. Once the program restarts you can remove the USB drive by pressing “Unmount” in the “Data Backup” screen

Vission 20/20T” Replacing & Returning Disk

Step 3: Replacing the Flashcard Disk

  1. Backup all parameters on the existing Program Disk to transfer to the new Disk (see Backup/Restore Procedure)
  2. Power down the Vission 20/20
  3. Carefully remove the existing Program Disk from the Vission 20/20 Single Board Computer (SBC)
  4. Carefully insert the new Program Disk into the Vission 20/20 SBC
  5. Restore all parameters to the new Program Disk using. (see Backup/Restore Procedure)

EMERSON 3485FCSD Vilter Vission - FIG6

Step 4: Return of Old Flashcard Disk

  • Please return the originally impacted flashcard to Vilter Manufacturing in the enclosed return envelope.
  • If you did not receive a return envelope, please return to:
    Vilter Manufacturing
    Attn: Sue Hancox
    5555 S Packard Ave
    Cudahy, WI 53110

Troubleshooting

You are unable to select any buttons on the Data Backup screen

  • The Save and Load function can only be used if you are logged in with an adequate security level and the compressor is stopped.

USB drive does not show up in the “Available Devices”

  • Not all USB drives are compatible, please try another drive.
  • If a drive was not Unmounted cleanly then it may prevent other mounts, Reboot the panel

You receive a message that the restore failed.

  • This is more likely to occur the further apart the versions of the old and new programs.
  • You can restore the factory setting from the “Migrate/Reset” tab in the Data backup screen.
  • Once the Program has been restored to the factory setting you will need to re-enter all the setpoints manually.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Emerson User Manuals

Related Manuals