Telaire Carbon Dioxide and Temperature Monitor Instructions

June 7, 2024
Telaire

Telaire Carbon Dioxide and Temperature Monitor


Telaire CO 2 and Temperature Monitor

Applies to this Telaire CO 2 and Temperature Monitor

Onset Part No. Outputs Telaire Part No.
TEL-7001 0-4V representing 0 to 4000 ppm CO2
0-4V representing 0 to +40°C (+32 to +104°F) 7001

This document provides instructions on connecting the Telaire CO2 and Temperature
Monitor listed above to each of the following:

  • FlexSmart™ Analog Module used with HOBO H22 series data loggers
  • Analog Sensor Port/Module option used with HOBO U30 and RX3000 series loggers
  • Voltage adapter cables used with the U12, UX120-006M, MX1104, and MX1105 data loggers and ZW series data nodes

It also lists configuration values used by HOBO software to configure the logger for the monitor.
Note: For information on powering the monitor for long-term applications, and other monitor details, refer to the documentation provided by GE Sensing.

Required

  • Telaire CO2 and Temperature Monitor listed above
  • Telaire Cable, Onset Part No. CABLE-2070 (not required for U12 or ZW series when recording CO2 only)
  • H22, U12, U30, UX120-006M, MX1104, MX1105, or RX3000 data logger, or HOBO ZW data node
  • FlexSmart Analog Module, S-FS-CVIA (for H22 series); Analog Sensor Port/Module option (for U30 and RX3000 series); voltage adapter, CABLE-ADAP5 or CABLE-CO2 (for U12, UX120-006M, MX1104, MX1105, or ZW series)
  • HOBOware® software, version 2.2.1 or higher for H22 or U12; 2.4.0 or higher for U30 series; 3.6 or higher for UX120-006M; HOBOware Pro 3.0 or higher for ZW series
  • HOBOconnect™ for MX1104 and MX1105
  • HOBOlink® for RX3000 series data loggers

**Connecting the CO 2 and Temperature Monitor to the Analog Module or

Port
**

H22 Connection

U30 or RX3000 Connection (U30 Shown)

ZW, U12, UX120-006M, MX1104, and MX1105 Connection

CO 2 only

ZW, U12, UX120-006M, and MX1105 Connection

**CO 2 and Temperature

**

**Configuring the Data Logger for the CO 2 and Temperature Monitor using

HOBO Software**

Use the following recommended scaling values in the software:

Channel 1


Channel Name| Measurement Type| Raw Value 1| Raw Value 2| Raw Units| Scaled Value 1| Scaled Value 2| Scaled Units
CO2| Voltage| 0| 4| V| 0| 4000| PPM

Channel 2


Channel Name| Measurement Type| Raw Value 1| Raw Value 2| Raw Units| Scaled Value 1| Scaled Value 2| Scaled Units
Temperature| Voltage| 0| 4| V| 0
32| 40
104| C F

Refer to the software documentation for more details on setting up scaling.