Bard Dehumidification Refrigerant Reheat Circuit Installation Guide

June 6, 2024
Bard

Bard Dehumidification Refrigerant Reheat Circuit

This model provides a unique dehumidification circuit for periods of low outdoor ambient temperature and high indoor humidity conditions.
Refer to Specification Sheet S3588 for the standard features of the base units and this manual for electrical data.

Dehumidification Circuit

The dehumidification refrigerant reheat circuit is controlled by a dehumidification valve directing the refrigerant gas to the normal condenser during periods when standard air conditioning is required. During periods of high indoor humidity, a humidistat senses the need for mechanical dehumidification. It then energizes both the compressor circuit and the dehumidification valve, thus directing the hot refrigerant discharge gas into a separate desuperheating condenser circuit, which reheats the conditioned air before it is delivered to the room. The refrigerant gas is then routed from the desuperheating condenser to the system condenser for further heat transfer. When the humidistat is satisfied, the system automatically switches back to normal A/C mode and either continues to operate or turns off based on the signal from the wall thermostat. The result is separate humidity control at minimum operating cost. See Figure 1 on page 2.

Dehumidification Sequence of Operation

Dehumidification is controlled through the thermostat (if capable) or through a separate humidistat. On a call for dehumidification mode of operation, the compressor and dehumidification valve of the unit are energized through circuit R – D to provide dehumidification. Dehumidification will continue until the humidistat is satisfied.

Any time there is a call for circuit R – Y1, the dehumidification mode will cancel and the system will return to cooling operation.

Balanced Climate™ Mode

It is recommended to enable Balanced Climate mode and utilize a 2-stage thermostat to enhance the dehumidification performance and comfort.

NOTE: To activate this mode, the jumper between Y1 and Y2 on the low voltage terminal strip needs to be removed.

In units with an economizer vent, balance climate mode should not be used. The Y1 and Y2 jumper must remain installed.

This mode will allow the indoor blower to run at a reduced airflow on the first stage of cooling. A 2-stage thermostat connected to Y2 will then allow the airflow to return to normal rated speed if the call for dehumidification or cooling is not satisfied within the allotted time frame specified by the thermostat. See latest revision of unit installation instructions 2100-721 for more information regarding the Balanced Climate operation.

Electronic Expansion Valve

Operation

This model employs an electronic expansion valve (EEV) which meters the refrigerant to the evaporator. The EEV is made of a stepper motor that is controlled with a step output from the controller. The valve is capable of 480 steps which drives a needle valve that in turn regulates the flow of refrigerant. The EEV allows for tighter control and better capacity management in varying operating conditions than a standard TXV. The EEV system consists of the electronic valve and stator, control board, relay, suction temperature sensor and suction pressure transducer. The pressure transducer and temperature sensor monitor the suction line to provide real time data to the control board so that a real time superheat can be calculated. This then determines the EEV position. The controller is sent to maintain around 13° superheat. The relay is used to activate the EEV system’s controller anytime that the compressor is energized.

WARNING/AVERTISSEMENT


– Exposure to high pressure refrigerant hazard.
– This unit is equipped with an electronic expansion valve. In order to fully recover refrigerant or evacuate the system during repairs, be sure to use service tool 2151-021 to manually open the electronic expansion valve or be sure to recover and evacuate from all service ports; suction, liquid, and discharge. – Failure to do so could result in eye injuries and/or refrigerant burns.

EEV Instructions for Vacuuming, Reclaiming and Charging Unit

The electronic expansion valve moves to a closed position when there is no call to control. In order to pull a complete vacuum, fully reclaim the system or charge the unit, connections to both the suction and discharge service ports need to be utilized or the valve needs to be manually opened first. The valve can be opened manually using the magnetic EEV service tool (Bard Part # 2151-021) shown in Figure 2. To do this, remove the EEV stator coil (red color with retaining nut on top), slide the magnetic tool over the shaft where the stator was removed and turn in a clockwise direction to open the valve to the full open position (directional arrows are provided on the tool).
Reapply the EEV stator coil and retaining nut once complete. Upon powering the unit back up, the control board will automatically drive the EEV back to the fully shut position. Once the compressor starts, the control board will again modulate the EEV position to control the system superheat.

Troubleshooting the Electronic Expansion Valve

The control board has two status LEDs.

  • The green LED should be lit anytime that the board has power and the control is functioning.
  • The red LED is to show that an alarm is present.

See Table 1 on page 4 for a guide to know where to start troubleshooting the EEV. Refer to the appropriate unit replacement parts manual for any parts that are needed.

Control Board

Check that the controller is getting 24VAC signal (GO 24VAC Hot and G 24VAC common). Reference unit wiring diagram for proper connections. If 24V is present but the green LED is not lit, replace the controller. If the green LED is now lit but the superheat is still not being maintained, troubleshoot the relay to check that the DI is connected to G; refer to Relay in EEV Control Box below.

Electronic Expansion Valve

Check to see if valve can be moved by manually moving the stepper motor using the EEV service tool shown in Figure 1 (Bard Part # 2151-021). If valve still does not control, check the transducer and thermistor sensors as described on page 5. If sensors are good, replace the valve.

Relay in EEV Control Box

Contacts NO to DI and COM to G must be closed for EEV control to start controlling superheat. Check that the relay is getting 24VAC. Reference unit wiring diagram for proper connections. If 24V is present, measure the resistance between COM and NO; it should be 0 ohms when the relay is getting 24V. If the resistance is out of range, replace the relay.

TABLE 1
Electronic Expansion Valve Troubleshooting

Problem Probable Cause Troubleshoot
The green LED is not lit. Controller not receiving 24VAC signal. Control

Board
The green LED is lit, but superheat is not being maintained.| The relay is not closing the controller’s DI connection to ground.| Relay
The red LED is flashing and EEV is not controlling superheat properly (13º superheat). One of the following is likely the fault:
1. Low superheat is detected and the controller is taking steps to protect the system by closing the valve.| Stator is broken or connected incorrectly.| Stator
Valve is stuck open.| EEV Valve
2. Suction temperature sensor error.| Poor connection of sensor or faulty sensor.| Thermistor
3. Suction pressure transducer error.| Pressure transducer wiring incorrect or faulty transducer.| Transducer
The red LED is on steady.| The operating parameters have been damaged.| Replace Control Board

Stator Coil

Disconnect the stator from the valve and the control and measure the resistance of the windings using an electrical tester. The resistance of both windings should be around 40 ohms +/­ 10%. The four wire sets that will have resistance between them are: White and red, green and red, yellow and purple, blue and purple. If the resistance falls outside these values, replace the stator.

Transducer Sensor
  1. Check continuity of all three wires from transducer plug to controller plug. Replace wires if poor connection in any wire.

  2. Check to ensure wires are correctly connected as follows:
    Blue wire = pin 1 of controller plug to pin C on transducer plug
    Red wire = pin 2 of controller plug to pin B on transducer plug
    Black wire = pin 3 of controller plug to pin A on transducer plug

  3. Check that there is 5VDC Nominal between the red and black wires going to the transducer.

  4. Check the signal voltage between the blue and black wires (0.5-4.5VDC Actual). The following formula and Figure 3 can be used to determine if the transducer’s voltage to pressure ratio is within range. Replace transducer if out of range.

Formula for Tech:
(Measured Pressure x .016) + .5 =
Expected Transducer Signal Voltage (see Figure 3)

Thermistor Sensor
  1. Make a visual check for broken wire insulation, broken wires or cracked epoxy material.
  2. Disconnect 10k ohm NTC thermistor from the EEV control box.
  3. Use an ohmmeter to measure the resistance between the two connectors. Also use ohmmeter to check for short or open.
  4. Compare the resistance reading to Table 2. Use sensor ambient temperature. (Tolerance of part is ±10 %.)
  5. If sensor is out of tolerance, shorted, open or reads very low ohms, it should be replaced.

TABLE 2
10K Ohm NTC Sensor: Temperature/Resistance

Temperature Resistance
F C
-40 -40
-38.2 -39
-36.4 -38
-34.6 -37
-32.8 -36
-31 -35
-29.2 -34
-27.4 -33
-25.6 -32
-23.8 -31
-22 -30
-20.2 -29
-18.4 -28
-16.6 -27
-14.8 -26
-13 -25
-11.2 -24
-9.4 -23
-7.6 -22
-5.8 -21
-4 -20
-2.2 -19
-0.4 -18
1.4 -17
3.2 -16
5 -15
6.8 -14
8.6 -13
10.4 -12
12.2 -11
14 -10
15.8 -9
17.6 -8
19.4 -7
21.2 -6
23 -5
24.8 -4
26.6 -3
28.4 -2
30.2 -1
32 0
33.8 1
35.6 2
37.4 3
39.2 4
41 5
42.8 6
44.6 7
46.4 8
48.2 9
50 10
51.8 11
53.6 12
55.4 13
57.2 14
59 15
60.8 16
62.6 17
64.4 18
66.2 19
68 20
69.8 21
71.6 22
73.4 23
75.2 24
77 25
78.8 26
80.6 27
82.4 28
84.2 29
86 30
87.8 31
89.6 32
91.4 33
93.2 34
95 35
96.8 36
98.6 37
100.4 38
102.2 39
104 40
105.8 41
107.6 42
109.4 43
111.2 44
113 45
114.8 46
116.6 47
118.4 48
120.2 49
122 50
123.8 51
125.6 52
127.4 53
129.2 54
131 55
132.8 56
134.6 57
136.4 58
138.2 59
140 60
141.8 61
143.6 62
145.4 63
147.2 64
149 65
150.8 66
152.6 67
154.4 68
156.2 69
158 70
159.8 71
161.6 72
163.4 73
165.2 74
167 75
168.8 76
170.6 77
172.4 78
174.2 79
176 80
177.8 81
179.6 82
181.4 83
183.2 84
185 85
186.8 86
188.6 87
190.4 88
192.2 89
194 90
195.8 91
197.6 92
199.4 93
201.2 94
203 95
204.8 96
206.6 97
208.4 98
210.2 99
212 100

W24G4D Cooling and Dehumidification Application Data1

DB/WB2 OD Temp. 65°F3 70°F 75°F 80°F 85°F 90°F 95°F 100°F 105°F
Mode A/C Dehum A/C Dehum A/C Dehum A/C Dehum A/C Dehum
A/C Dehum A/C Dehum A/C Dehum
75/62.5 (50% RH) Total Cooling Btuh 26,700 13,300 26,100 11,500 25,500
10,300 24,700 7,900 23,900 6,000 23,100 4,000 22,200 2,000 21,200
20,100
Sensible Btuh 19,700 5,700 19,400 4,300 19,700 3,300 18,800 1,400
18,400 18,000 (1,500) 17,600 (3,000) 17,100 (4,400) 16,700 (6,000)
S/T 0.738 0.429 0.743 0.374 0.773 0.320 0.761 0.177 0.770 0.000
0.779 0 0.793 0 0.807 0 0.831 0
Latent Btuh 7,000 7,600 6,700 7,200 5,800 7,000 5,900 6,500 5,500
6,000 5,100 5,500 4,600 5,000 4,100 4,300 3,400 3,800
Lbs. H20/hr. 6.6 7.2 6.3 6.8 5.5 6.6 5.6 6.1 5.2 5.7
4.7 3.9 4.1 3.2 3.6
Supply Air DB 52.5 66.5 52.8 68.6 53.1 70.2 53.5 72.9 53.9 75.0
54.3 77.2 54.9 79.5 55.4 81.7 56.0 83.9
Supply Air WB 51.1 55.6 51.4 56.6 51.6 57.0 51.9 58.6 52.3 59.6
52.7 60.6 53.1 61.7 53.5 62.7 54.0 63.8
Suction PSIG4 123 116 124 118 124 119 126 121 127 123
130 127 131 128 133 130
Discharge PSIG4 273 240 292 253 308 263 333 282 356 298
404 331 430 348 457 367
75/64.1 (55% RH) Total Cooling Btuh 27,500 14,100 26,900 12,400 26,200
10,600 25,500 8,700 24,700 6,800 23,900 4,900 23,000 2,900 22,000
800 20,900
Sensible Btuh 18,700 5,100 18,400 3,700 18,100 2,300 17,800 800
17,400 (600) 17,000 (2,100) 16,600 (3,600) 16,100 (5,100) 15,700

(6,600)
S/T| 0.680| 0.36| 0.684| 0.30| 0.691| 0.22| 0.698| 0.09| 0.704| 0| 0.711| 0| 0.722| 0| 0.732| 0| 0.751| 0
Latent Btuh| 8,800| 9,000| 8,500| 8,700| 8,100| 8,300| 7,700| 7,900| 7,300| 7,400| 6,900| 7,000| 6,400| 6,500| 5,900| 5,900| 5,200| 5,300
Lbs. H20/hr.| 8.3| 8.5| 8.0| 8.2| 7.6| 7.8| 7.3| 7.5| 6.9| 7.0| 6.5| 6.6| 6.0| 6.1| 5.6| 5.6| 4.9| 5.0
Supply Air DB| 53.6| 67.3| 53.9| 69.5| 54.3| 71.6| 54.6| 73.8| 55.0| 75.9| 55.5| 78.1| 56.0| 80.4| 56.6| 82.6| 57.2| 84.8
Supply Air WB| 52.5| 56.7| 52.8| 57.7| 53.0| 58.7| 53.3| 59.7| 53.7| 60.7| 54.1| 61.8| 54.5| 62.8| 55.0| 63.8| 55.5| 64.9
Suction PSIG4| 125| 119| 126| 120| 127| 122| 129| 124| 130| 126| 131| 127| 133| 129| 134| 131| 135| 133
Discharge PSIG4| 273| 240| 292| 254| 312| 268| 334| 283| 356| 299| 380| 315| 404| 332| 430| 349| 457| 367
75/65.5 (60% RH)| Total Cooling Btuh| 28,300| 15,000| 27,700| 13,200| 27,100| 12,000| 26,300| 9,600| 25,500| 7,700| 24,700| 5,700| 23,800| 3,700| 22,800| 1,600| 21,700|
Sensible Btuh| 17,700| 4,500| 17,400| 3,100| 17,700| 2,100| 16,800| 200| 16,400| (1,200)| 16,000| (2,700)| 15,600| (4,200)| 15,100| (5,700)| 14,700| (7,200)
S/T| 0.625| 0.300| 0.628| 0.235| 0.653| 0.175| 0.639| 0.021| 0.643| 0| 0.648| 0| 0.655| 0| 0.662| 0| 0.677| 0
Latent Btuh| 10,600| 10,500| 10,300| 10,100| 9,400| 9,900| 9,500| 9,400| 9,100| 8,900| 8,700| 8,400| 8,200| 7,900| 7,700| 7,300| 7,000| 6,700
Lbs. H20/hr.| 10.0| 9.9| 9.7| 9.5| 8.9| 9.3| 9.0| 8.9| 8.6| 8.4| 8.2| 7.9| 7.7| 7.5| 7.3| 6.9| 6.6| 6.3
Supply Air DB| 54.8| 68.2| 55.1| 70.4| 55.4| 72.0| 55.8| 74.7| 56.2| 76.8| 56.7| 79.0| 57.2| 81.3| 57.7| 83.5| 58.3| 85.7
Supply Air WB| 53.9| 57.8| 54.2| 58.8| 54.4| 59.3| 54.7| 60.8| 55.1| 61.8| 55.5| 62.9| 55.9| 63.9| 56.4| 64.9| 56.9| 66.0
Suction PSIG4| 128| 121| 129| 123| 129| 124| 131| 126| 133| 128| 134| 130| 135| 132| 137| 134| 138| 135
Discharge PSIG4| 274| 241| 293| 255| 309| 265| 334| 284| 356| 299| 380| 316| 405| 332| 431| 350| 458| 368
75/66.7 (65% RH)| Total Cooling Btuh| 29,100| 15,800| 28,500| 14,100| 27,900| 12,800| 27,100| 10,400| 26,300| 8,500| 25,500| 6,600| 24,500| 4,500| 23,600| 2,500| 22,500| 400
Sensible Btuh| 16,700| 3,900| 16,400| 2,500| 16,700| 1,500| 15,800| (400)| 15,400| (1,800)| 15,000| (3,300)| 14,600| (4,800)| 14,100| (6,300)| 13,700| (7,800)
S/T| 0.574| 0.25| 0.575| 0.18| 0.599| 0.12| 0.583| 0| 0.586| 0| 0.588| 0| 0.596| 0| 0.597| 0| 0.609| 0
Latent Btuh| 12,400| 11,900| 12,100| 11,600| 11,200| 11,300| 11,300| 10,800| 10,900| 10,300| 10,500| 9,900| 9,900| 9,300| 9,500| 8,800| 8,800| 8,200
Lbs. H20/hr.| 11.7| 11.2| 11.4| 10.9| 10.6| 10.7| 10.7| 10.2| 10.3| 9.7| 9.9| 9.3| 9.3| 8.8| 9.0| 8.3| 8.3| 7.7
Supply Air DB| 56.0| 69.1| 56.3| 71.3| 56.6| 72.8| 57.0| 75.6| 57.4| 77.7| 57.8| 79.9| 58.3| 82.1| 58.9| 84.4| 59.5| 86.6
Supply Air WB| 55.3| 58.9| 55.6| 59.9| 55.8| 60.4| 56.1| 61.9| 56.5| 63.0| 56.9| 64.0| 57.3| 65.0| 57.8| 66.1| 58.3| 67.1
Suction PSIG4| 131| 124| 132| 126| 132| 127| 134| 129| 135| 131| 137| 133| 138| 134| 140| 136| 141| 138
Discharge PSIG4| 274| 242| 293| 256| 309| 265| 334| 285| 357| 300| 380| 316| 405| 333| 431| 351| 458| 369
75/68 (70% RH)| Total Cooling Btuh| 29,800| 16,700| 29,300| 14,900| 28,700| 13,700| 27,900| 11,300| 27,100| 9,400| 26,200| 7,400| 25,300| 5,400| 24,300| 3,300| 23,300| 1,200
Sensible Btuh| 15,700| 3,300| 15,400| 1,900| 15,700| 900| 14,800| (1,000)| 14,400| (2,400)| 14,000| (3,900)| 13,600| (5,400)| 13,200| (6,900)| 12,700| (8,400)
S/T| 0.527| 0.198| 0.526| 0.128| 0.547| 0.066| 0.530| 0| 0.531| 0| 0.534| 0| 0.538| 0| 0.543| 0| 0.545| 0
Latent Btuh| 14,100| 13,400| 13,900| 13,000| 13,000| 12,800| 13,100| 12,300| 12,700| 11,800| 12,200| 11,300| 11,700| 10,800| 11,100| 10,200| 10,600| 9,600
Lbs. H20/hr.| 13.3| 12.6| 13.1| 12.3| 12.3| 12.1| 12.4| 11.6| 12.0| 11.1| 11.5| 10.7| 11.0| 10.2| 10.5| 9.6| 10.0| 9.1
Supply Air DB| 57.1| 70.0| 57.4| 72.2| 57.7| 73.7| 58.1| 76.5| 58.5| 78.6| 59.0| 80.8| 59.5| 83.0| 60.1| 85.3| 60.7| 87.5
Supply Air WB| 56.8| 60.0| 57.0| 61.0| 57.2| 61.5| 57.6| 63.0| 57.9| 64.1| 58.3| 65.1| 58.7| 66.1| 59.2| 67.2| 59.7| 68.2
Suction PSIG4| 134| 126| 135| 128| 135| 130| 137| 132| 138| 133| 140| 135| 141| 137| 142| 139| 144| 141
Discharge PSIG4| 274| 243| 293| 256| 309| 266| 334| 285| 357| 301| 380| 317| 405| 334| 431| 352| 458| 370
80/68.3 (55% RH)| Total Cooling Btuh| 30,000| 16,700| 29,400| 15,000| 28,800| 13,700| 28,100| 11,300| 27,300| 9,400| 26,400| 7,400| 25,500| 5,400| 24,500| 3,400| 23,500| 1,200
Sensible Btuh| 19,000| 5,900| 18,700| 4,500| 18,900| 3,500| 18,000| 1,600| 17,600| 200| 17,200| (1,300)| 16,800| (2,800)| 16,400| (4,300)| 15,900| (5,800)
S/T| 0.633| 0.35| 0.636| 0.30| 0.656| 0.26| 0.641| 0.14| 0.645| 0.02| 0.652| 0| 0.659| 0| 0.669| 0| 0.677| 0
Latent Btuh| 11,000| 10,800| 10,700| 10,500| 9,900| 10,200| 10,100| 9,700| 9,700| 9,200| 9,200| 8,700| 8,700| 8,200| 8,100| 7,700| 7,600| 7,000
Lbs. H20/hr.| 10.4| 10.2| 10.1| 9.9| 9.3| 9.6| 9.5| 9.2| 9.2| 8.7| 8.7| 8.2| 8.2| 7.7| 7.6| 7.3| 7.2| 6.6
Supply Air DB| 58.0| 71.0| 58.2| 73.2| 58.6| 74.7| 58.9| 77.5| 59.4| 79.6| 59.8| 81.8| 60.3| 84.0| 60.9| 86.3| 61.5| 88.5
Supply Air WB| 56.8| 60.2| 57.0| 61.2| 57.2| 61.7| 57.6| 63.3| 57.9| 64.3| 58.3| 65.3| 58.7| 66.4| 59.2| 67.4| 59.7| 68.5
Suction PSIG4| 136| 127| 137| 129| 137| 131| 139| 133| 140| 134| 141| 136| 143| 138| 144| 140| 146| 142
Discharge PSIG4| 278| 247| 297| 260| 313| 270| 338| 289| 360| 305| 384| 321| 409| 338| 435| 356| 462| 374

  1. Values listed are with ventilation package disabled
  2. Return air temperature °F @ Rated CFM
  3. Below 50°F, unit requires a factory or field installed low ambient control.
  4. Suction pressure +/- 4 psi, Discharge pressure +/- 10 psi

W30G4D Cooling and Dehumidification Application Data1

DB/WB2 OD Temp. 65°F3 70°F 75°F 80°F 85°F 90°F 95°F 100°F 105°F
Mode A/C Dehum A/C Dehum A/C Dehum A/C Dehum A/C Dehum
A/C Dehum A/C Dehum A/C Dehum
75/62.5 (50% RH) Total Cooling Btuh 31,800 15,400 30,800 13,400 29,900
10,900 29,000 9,200 28,100 7,100 27,100 4,900 26,200 2,600 25,200
300 24,200
Sensible Btuh 22,800 6,500 22,300 4,800 21,800 3,300 21,300 1,600
20,800 (100) 20,300 (1,700) 19,800 (3,300) 19,400 (4,900) 18,900

(6,500)
S/T| 0.717| 0.422| 0.724| 0.358| 0.729| 0.303| 0.734| 0.174| 0.740| 0| 0.749| 0| 0.756| 0| 0.770| 0| 0.781| 0
Latent Btuh| 9,000| 8,900| 8,500| 8,600| 8,100| 7,600| 7,700| 7,600| 7,300| 7,200| 6,800| 6,600| 6,400| 5,900| 5,800| 5,200| 5,300| 4,500
Lbs. H20/hr.| 8.5| 8.4| 8.0| 8.1| 7.6| 7.2| 7.3| 7.2| 6.9| 6.8| 6.4| 6.2| 6.0| 5.6| 5.5| 4.9| 5.0| 4.2
Supply Air DB| 52.2| 66.6| 52.7| 68.7| 53.2| 70.8| 53.7| 73.0| 54.2| 75.1| 54.7| 77.2| 55.2| 79.3| 55.6| 81.4| 56.1| 83.5
Supply Air WB| 50.5| 55.4| 50.9| 56.4| 51.1| 57.4| 51.7| 58.4| 52.0| 59.5| 52.4| 60.5| 52.8| 61.5| 53.2| 62.5| 53.6| 63.6
Suction PSIG4| 123| 115| 124| 116| 124| 118| 125| 119| 127| 121| 128| 123| 129| 125| 130| 127| 132| 130
Discharge PSIG4| 264| 238| 283| 251| 307| 265| 324| 280| 346| 296| 370| 312| 394| 329| 420| 347| 447| 366
75/64.1 (55% RH)| Total Cooling Btuh| 32,600| 16,500| 31,700| 14,400| 30,800| 12,400| 29,900| 10,200| 28,900| 8,100| 28,000| 5,900| 27,000| 3,600| 26,000| 1,400| 25,100|
Sensible Btuh| 21,700| 5,800| 21,200| 4,100| 20,700| 2,500| 20,200| 900| 19,700| (700)| 19,200| (2,400)| 18,700| (4,000)| 18,200| (5,600)| 17,800| (7,100)
S/T| 0.666| 0.35| 0.669| 0.28| 0.672| 0.20| 0.676| 0.09| 0.682| 0| 0.686| 0| 0.693| 0| 0.700| 0| 0.709| 0
Latent Btuh| 10,900| 10,700| 10,500| 10,300| 10,100| 9,900| 9,700| 9,300| 9,200| 8,800| 8,800| 8,300| 8,300| 7,600| 7,800| 7,000| 7,300| 6,100
Lbs. H20/hr.| 10.3| 10.1| 9.9| 9.7| 9.5| 9.3| 9.2| 8.8| 8.7| 8.3| 8.3| 7.8| 7.8| 7.2| 7.4| 6.6| 6.9| 5.8
Supply Air DB| 53.2| 67.4| 53.8| 69.6| 54.3| 71.7| 54.8| 73.9| 55.3| 76.0| 55.8| 78.1| 56.2| 80.2| 56.7| 82.3| 57.1| 84.3
Supply Air WB| 51.9| 56.4| 52.2| 57.5| 52.6| 58.5| 53.0| 59.5| 53.4| 60.5| 53.8| 61.5| 54.1| 62.6| 54.5| 63.6| 54.9| 64.6
Suction PSIG4| 126| 118| 127| 119| 128| 121| 129| 122| 130| 124| 131| 126| 132| 128| 134| 131| 135| 133
Discharge PSIG4| 266| 241| 284| 254| 304| 268| 326| 283| 348| 299| 372| 315| 396| 332| 422| 350| 449| 368
75/65.5 (60% RH)| Total Cooling Btuh| 33,500| 17,500| 32,600| 15,500| 31,600| 13,000| 30,700| 11,300| 29,800| 9,100| 28,800| 6,900| 27,900| 4,700| 26,900| 2,400| 25,900| 100
Sensible Btuh| 20,600| 5,100| 20,100| 3,500| 19,600| 1,900| 19,100| 200| 18,600| (1,400)| 18,100| (3,000)| 17,600| (4,600)| 17,100| (6,200)| 16,600| (7,800)
S/T| 0.615| 0.291| 0.617| 0.226| 0.620| 0.146| 0.622| 0.018| 0.624| 0| 0.628| 0| 0.631| 0| 0.636| 0| 0.641| 0
Latent Btuh| 12,900| 12,400| 12,500| 12,000| 12,000| 11,100| 11,600| 11,100| 11,200| 10,500| 10,700| 9,900| 10,300| 9,300| 9,800| 8,600| 9,300| 7,900
Lbs. H20/hr.| 12.2| 11.7| 11.8| 11.3| 11.3| 10.5| 10.9| 10.5| 10.6| 9.9| 10.1| 9.3| 9.7| 8.8| 9.2| 8.1| 8.8| 7.5
Supply Air DB| 54.3| 68.3| 54.8| 70.5| 55.3| 72.5| 55.9| 74.7| 56.3| 76.9| 56.8| 79.0| 57.3| 81.1| 57.8| 83.1| 58.2| 85.2
Supply Air WB| 53.2| 57.5| 53.6| 58.5| 53.8| 59.5| 54.3| 60.6| 54.7| 61.6| 55.1| 62.6| 55.5| 63.6| 55.9| 64.7| 56.2| 65.7
Suction PSIG4| 129| 122| 130| 123| 131| 124| 132| 126| 133| 128| 134| 130| 136| 132| 137| 134| 138| 136
Discharge PSIG4| 267| 244| 286| 257| 310| 271| 327| 286| 350| 301| 373| 318| 398| 335| 424| 353| 451| 371
75/66.7 (65% RH)| Total Cooling Btuh| 34,300| 18,500| 33,400| 16,500| 32,500| 14,000| 31,600| 12,300| 30,600| 10,200| 29,700| 8,000| 28,700| 5,700| 27,800| 3,400| 26,800| 1,100
Sensible Btuh| 19,400| 4,400| 19,000| 2,800| 18,500| 1,200| 18,000| (500)| 17,500| (2,100)| 17,000| (3,700)| 16,500| (5,300)| 16,000| (6,900)| 15,500| (8,500)
S/T| 0.566| 0.24| 0.569| 0.17| 0.569| 0.09| 0.570| 0| 0.572| 0| 0.572| 0| 0.575| 0| 0.576| 0| 0.578| 0
Latent Btuh| 14,900| 14,100| 14,400| 13,700| 14,000| 12,800| 13,600| 12,800| 13,100| 12,300| 12,700| 11,700| 12,200| 11,000| 11,800| 10,300| 11,300| 9,600
Lbs. H20/hr.| 14.1| 13.3| 13.6| 12.9| 13.2| 12.1| 12.8| 12.1| 12.4| 11.6| 12.0| 11.0| 11.5| 10.4| 11.1| 9.7| 10.7| 9.1
Supply Air DB| 55.4| 69.2| 55.9| 71.3| 56.4| 73.4| 56.9| 75.6| 57.4| 77.7| 57.9| 79.8| 58.4| 81.9| 58.8| 84.0| 59.3| 86.1
Supply Air WB| 54.5| 58.6| 54.9| 59.6| 55.1| 60.6| 55.7| 61.6| 56.1| 62.6| 56.4| 63.7| 56.8| 64.7| 57.2| 65.7| 57.6| 66.7
Suction PSIG4| 133| 125| 134| 126| 134| 128| 135| 129| 137| 131| 138| 133| 139| 135| 140| 137| 142| 140
Discharge PSIG4| 269| 246| 288| 260| 312| 274| 329| 289| 351| 304| 375| 321| 400| 338| 425| 356| 452| 374
75/68 (70% RH)| Total Cooling Btuh| 35,200| 19,600| 34,300| 17,500| 33,300| 15,100| 32,400| 13,300| 31,500| 11,200| 30,500| 9,000| 29,600| 6,700| 28,600| 4,500| 27,600| 2,100
Sensible Btuh| 18,300| 3,700| 17,900| 2,100| 17,300| 500| 16,900| (1,200)| 16,400| (2,800)| 15,900| (4,400)| 15,400| (6,000)| 14,900| (7,600)| 14,400| (9,200)
S/T| 0.520| 0.189| 0.522| 0.120| 0.520| 0.033| 0.522| 0| 0.521| 0| 0.521| 0| 0.520| 0| 0.521| 0| 0.522| 0
Latent Btuh| 16,900| 15,900| 16,400| 15,400| 16,000| 14,600| 15,500| 14,500| 15,100| 14,000| 14,600| 13,400| 14,200| 12,700| 13,700| 12,100| 13,200| 11,300
Lbs. H20/hr.| 15.9| 15.0| 15.5| 14.5| 15.1| 13.8| 14.6| 13.7| 14.2| 13.2| 13.8| 12.6| 13.4| 12.0| 12.9| 11.4| 12.5| 10.7
Supply Air DB| 56.4| 70.0| 57.0| 72.2| 57.5| 74.2| 58.0| 76.5| 58.5| 78.6| 59.0| 80.7| 59.4| 82.8| 59.9| 84.9| 60.3| 86.9
Supply Air WB| 55.9| 59.6| 56.2| 60.6| 56.4| 61.7| 57.0| 62.7| 57.4| 63.7| 57.8| 64.7| 58.2| 65.7| 58.5| 66.8| 58.9| 67.8
Suction PSIG4| 136| 129| 137| 130| 138| 131| 139| 133| 140| 134| 141| 136| 142| 139| 144| 141| 145| 143
Discharge PSIG4| 271| 249| 289| 263| 313| 276| 331| 292| 353| 307| 377| 323| 401| 341| 427| 358| 454| 377
80/68.3 (55% RH)| Total Cooling Btuh| 35,300| 20,100| 34,400| 18,100| 33,500| 15,600| 32,600| 13,900| 31,700| 11,700| 30,700| 9,500| 29,700| 7,300| 28,800| 5,000| 27,800| 2,700
Sensible Btuh| 22,500| 7,100| 22,000| 5,400| 21,500| 3,900| 21,100| 2,100| 20,600| 500| 20,100| (1,100)| 19,600| (2,700)| 19,100| (4,300)| 18,600| (5,900)
S/T| 0.637| 0.35| 0.640| 0.30| 0.642| 0.25| 0.647| 0.15| 0.650| 0.04| 0.655| 0| 0.660| 0| 0.663| 0| 0.669| 0
Latent Btuh| 12,800| 13,000| 12,400| 12,700| 12,000| 11,700| 11,500| 11,800| 11,100| 11,200| 10,600| 10,600| 10,100| 10,000| 9,700| 9,300| 9,200| 8,600
Lbs. H20/hr.| 12.1| 12.3| 11.7| 12.0| 11.3| 11.0| 10.8| 11.1| 10.5| 10.6| 10.0| 10.0| 9.5| 9.4| 9.2| 8.8| 8.7| 8.1
Supply Air DB| 57.3| 70.6| 57.8| 72.8| 58.3| 74.8| 58.8| 77.1| 59.3| 79.2| 59.8| 81.3| 60.2| 83.4| 60.7| 85.5| 61.2| 87.5
Supply Air WB| 56.3| 59.7| 56.6| 60.7| 56.8| 61.7| 57.4| 62.7| 57.8| 63.7| 58.2| 64.8| 58.6| 65.8| 58.9| 66.8| 59.3| 67.8
Suction PSIG4| 138| 129| 138| 130| 139| 132| 140| 133| 141| 135| 143| 137| 144| 139| 145| 141| 146| 144
Discharge PSIG4| 269| 250| 288| 263| 312| 277| 329| 292| 351| 308| 375| 324| 400| 341| 425| 359| 452| 378

  1. Values listed are with ventilation package disabled
  2. Return air temperature °F @ Rated CFM
  3. Below 50°F, unit requires a factory or field installed low ambient control.
  4. Suction pressure +/- 4 psi, Discharge pressure +/- 10 psi

W36G4D Cooling and Dehumidification Application Data1

DB/WB2 OD Temp. 65°F3 70°F 75°F 80°F 85°F 90°F 95°F 100°F 105°F
Mode A/C Dehum A/C Dehum A/C Dehum A/C Dehum A/C Dehum
A/C Dehum A/C Dehum A/C Dehum
75/62.5 (50% RH) Total Cooling Btuh 38,500 18,300 37,400 16,100 36,400
13,700 35,200 11,400 34,000 9,000 32,900 6,600 31,800 4,100 30,600
1,600 29,500
Sensible Btuh 28,700 8,200 28,300 6,500 27,800 4,900 27,200 3,100
26,700 1,400 26,100 (400) 25,600 (2,100) 25,000 (3,900) 24,400

(5,700)
S/T| 0.745| 0.448| 0.757| 0.404| 0.764| 0.358| 0.773| 0.272| 0.785| 0.156| 0.793| 0| 0.805| 0| 0.817| 0| 0.827| 0
Latent Btuh| 9,800| 10,100| 9,100| 9,600| 8,600| 8,800| 8,000| 8,300| 7,300| 7,600| 6,800| 7,000| 6,200| 6,200| 5,600| 5,500| 5,100| 4,700
Lbs. H20/hr.| 9.2| 9.5| 8.6| 9.1| 8.1| 8.3| 7.5| 7.8| 6.9| 7.2| 6.4| 6.6| 5.8| 5.8| 5.3| 5.2| 4.8| 4.4
Supply Air DB| 51.4| 66.0| 51.9| 67.9| 52.4| 69.8| 52.9| 71.8| 53.3| 73.7| 53.8| 75.7| 54.3| 77.7| 54.7| 79.7| 55.1| 81.7
Supply Air WB| 50.3| 55.0| 50.8| 56.0| 51.2| 56.9| 51.7| 58.0| 52.1| 59.0| 52.5| 60.1| 52.9| 61.1| 53.2| 62.1| 53.6| 63.1
Suction PSIG4| 123| 114| 124| 115| 124| 116| 126| 117| 127| 118| 128| 120| 129| 121| 130| 123| 132| 125
Discharge PSIG4| 287| 251| 307| 265| 328| 279| 350| 294| 373| 310| 396| 326| 421| 342| 447| 359| 474| 377
75/64.1 (55% RH)| Total Cooling Btuh| 39,500| 19,500| 38,400| 17,200| 37,200| 14,900| 36,100| 12,600| 35,000| 10,200| 33,800| 7,700| 32,700| 5,200| 31,600| 2,700| 30,400| 100
Sensible Btuh| 27,300| 7,300| 26,800| 5,600| 26,300| 3,900| 25,700| 2,200| 25,200| 500| 24,600| (1,200)| 24,100| (3,000)| 23,500| (4,800)| 22,900| (6,600)
S/T| 0.691| 0.37| 0.698| 0.33| 0.707| 0.26| 0.712| 0.17| 0.720| 0.05| 0.728| 0| 0.737| 0| 0.744| 0| 0.753| 0
Latent Btuh| 12,200| 12,200| 11,600| 11,600| 10,900| 11,000| 10,400| 10,400| 9,800| 9,700| 9,200| 8,900| 8,600| 8,200| 8,100| 7,500| 7,500| 6,700
Lbs. H20/hr.| 11.5| 11.5| 10.9| 10.9| 10.3| 10.4| 9.8| 9.8| 9.2| 9.2| 8.7| 8.4| 8.1| 7.7| 7.6| 7.1| 7.1| 6.3
Supply Air DB| 52.6| 67.1| 53.1| 69.0| 53.6| 70.9| 54.1| 72.9| 54.5| 74.8| 55.0| 76.8| 55.5| 78.8| 55.9| 80.8| 56.4| 82.7
Supply Air WB| 51.7| 56.1| 52.2| 57.1| 52.6| 58.1| 53.0| 59.1| 53.4| 60.1| 53.8| 61.1| 54.2| 62.1| 54.6| 63.1| 54.9| 64.1
Suction PSIG4| 126| 118| 126| 118| 127| 119| 128| 120| 130| 121| 131| 123| 132| 124| 133| 126| 135| 128
Discharge PSIG4| 289| 254| 309| 268| 330| 282| 352| 297| 374| 313| 398| 329| 423| 345| 449| 362| 476| 380
75/65.5 (60% RH)| Total Cooling Btuh| 40,400| 20,700| 39,300| 18,400| 38,300| 16,000| 37,100| 13,700| 35,900| 11,300| 34,800| 8,900| 33,700| 6,400| 32,500| 3,900| 31,400| 1,300
Sensible Btuh| 25,800| 6,400| 25,300| 4,700| 24,800| 3,100| 24,300| 1,300| 23,700| (400)| 23,200| (2,100)| 22,600| (3,900)| 22,000| (5,700)| 21,400| (7,400)
S/T| 0.639| 0.309| 0.644| 0.255| 0.648| 0.194| 0.655| 0.095| 0.660| 0| 0.667| 0| 0.671| 0| 0.677| 0| 0.682| 0
Latent Btuh| 14,600| 14,300| 14,000| 13,700| 13,500| 12,900| 12,800| 12,400| 12,200| 11,700| 11,600| 11,000| 11,100| 10,300| 10,500| 9,600| 10,000| 8,700
Lbs. H20/hr.| 13.8| 13.5| 13.2| 12.9| 12.7| 12.2| 12.1| 11.7| 11.5| 11.0| 10.9| 10.4| 10.5| 9.7| 9.9| 9.1| 9.4| 8.2
Supply Air DB| 53.8| 68.2| 54.3| 70.1| 54.8| 71.9| 55.3| 74.0| 55.8| 75.9| 56.2| 77.9| 56.7| 79.8| 57.1| 81.8| 57.6| 83.8
Supply Air WB| 53.1| 57.1| 53.5| 58.2| 53.9| 59.1| 54.4| 60.2| 54.8| 61.2| 55.2| 62.2| 55.6| 63.2| 55.9| 64.2| 56.3| 65.2
Suction PSIG4| 128| 121| 129| 121| 130| 122| 131| 123| 132| 125| 134| 126| 135| 128| 136| 129| 137| 131
Discharge PSIG4| 291| 257| 311| 271| 331| 285| 353| 300| 376| 316| 400| 332| 425| 348| 451| 365| 478| 383
75/66.7 (65% RH)| Total Cooling Btuh| 41,400| 21,800| 40,300| 19,600| 39,200| 17,200| 38,000| 14,900| 36,900| 12,500| 35,700| 10,100| 34,600| 7,600| 33,500| 5,000| 32,300| 2,500
Sensible Btuh| 24,300| 5,500| 23,800| 3,900| 23,400| 2,200| 22,800| 500| 22,200| (1,300)| 21,700| (3,000)| 21,100| (4,800)| 20,500| (6,500)| 19,900| (8,300)
S/T| 0.587| 0.25| 0.591| 0.20| 0.597| 0.13| 0.600| 0.03| 0.602| 0| 0.608| 0| 0.610| 0| 0.612| 0| 0.616| 0
Latent Btuh| 17,100| 16,300| 16,500| 15,700| 15,800| 15,000| 15,200| 14,400| 14,700| 13,800| 14,000| 13,100| 13,500| 12,400| 13,000| 11,500| 12,400| 10,800
Lbs. H20/hr.| 16.1| 15.4| 15.6| 14.8| 14.9| 14.2| 14.3| 13.6| 13.9| 13.0| 13.2| 12.4| 12.7| 11.7| 12.3| 10.8| 11.7| 10.2
Supply Air DB| 55.0| 69.2| 55.5| 71.2| 56.0| 73.0| 56.5| 75.0| 57.0| 77.0| 57.4| 78.9| 57.9| 80.9| 58.4| 82.9| 58.8| 84.9
Supply Air WB| 54.4| 58.2| 54.9| 59.2| 55.3| 60.1| 55.7| 61.3| 56.1| 62.3| 56.5| 63.3| 56.9| 64.3| 57.3| 65.3| 57.6| 66.3
Suction PSIG4| 131| 124| 132| 125| 133| 125| 134| 126| 135| 128| 136| 129| 138| 131| 139| 132| 140| 134
Discharge PSIG4| 293| 260| 313| 274| 333| 288| 355| 303| 378| 319| 402| 335| 427| 351| 453| 368| 480| 386
75/68 (70% RH)| Total Cooling Btuh| 42,300| 23,000| 41,200| 20,700| 40,200| 18,300| 39,000| 16,100| 37,800| 13,700| 36,700| 11,200| 35,600| 8,700| 34,400| 6,200| 33,300| 3,600
Sensible Btuh| 22,800| 4,700| 22,300| 3,000| 21,900| 1,400| 21,300| (400)| 20,800| (2,100)| 20,200| (3,900)| 19,600| (5,600)| 19,000| (7,400)| 18,500| (9,200)
S/T| 0.539| 0.204| 0.541| 0.145| 0.545| 0.077| 0.546| 0| 0.550| 0| 0.550| 0| 0.551| 0| 0.552| 0| 0.556| 0
Latent Btuh| 19,500| 18,300| 18,900| 17,700| 18,300| 16,900| 17,700| 16,500| 17,000| 15,800| 16,500| 15,100| 16,000| 14,300| 15,400| 13,600| 14,800| 12,800
Lbs. H20/hr.| 18.4| 17.3| 17.8| 16.7| 17.3| 15.9| 16.7| 15.6| 16.0| 14.9| 15.6| 14.2| 15.1| 13.5| 14.5| 12.8| 14.0| 12.1
Supply Air DB| 56.3| 70.3| 56.8| 72.2| 57.2| 74.1| 57.7| 76.1| 58.2| 78.1| 58.7| 80.0| 59.1| 82.0| 59.6| 84.0| 60.0| 86.0
Supply Air WB| 55.8| 59.3| 56.2| 60.3| 56.7| 61.2| 57.1| 62.3| 57.5| 63.4| 57.9| 64.4| 58.3| 65.4| 58.6| 66.4| 59.0| 67.4
Suction PSIG4| 134| 127| 135| 128| 136| 128| 137| 130| 138| 131| 139| 132| 141| 134| 142| 136| 143| 138
Discharge PSIG4| 295| 263| 314| 277| 335| 291| 357| 306| 380| 322| 404| 338| 429| 354| 455| 371| 482| 389
80/68.3 (55% RH)| Total Cooling Btuh| 42,700| 23,200| 41,600| 21,000| 40,500| 18,500| 39,300| 16,300| 38,200| 13,900| 37,000| 11,400| 35,900| 9,000| 34,800| 6,400| 33,600| 3,800
Sensible Btuh| 28,100| 8,600| 27,600| 6,900| 27,200| 5,300| 26,600| 3,500| 26,100| 1,800| 25,500| –| 24,900| (1,700)| 24,400| (3,500)| 23,800| (5,300)
S/T| 0.658| 0.37| 0.663| 0.33| 0.672| 0.29| 0.677| 0.21| 0.683| 0.13| 0.689| 0.00| 0.694| 0| 0.701| 0| 0.708| 0
Latent Btuh| 14,600| 14,600| 14,000| 14,100| 13,300| 13,200| 12,700| 12,800| 12,100| 12,100| 11,500| 11,400| 11,000| 10,700| 10,400| 9,900| 9,800| 9,100
Lbs. H20/hr.| 13.8| 13.8| 13.2| 13.3| 12.5| 12.5| 12.0| 12.1| 11.4| 11.4| 10.8| 10.8| 10.4| 10.1| 9.8| 9.3| 9.2| 8.6
Supply Air DB| 56.6| 70.7| 57.1| 72.6| 57.6| 74.4| 58.1| 76.5| 58.5| 78.4| 59.0| 80.4| 59.5| 82.3| 59.9| 84.3| 60.4| 86.3
Supply Air WB| 55.7| 59.4| 56.2| 60.4| 56.6| 61.3| 57.0| 62.4| 57.5| 63.4| 57.9| 64.4| 58.2| 65.4| 58.6| 66.4| 59.0| 67.4
Suction PSIG4| 137| 128| 137| 129| 138| 130| 139| 131| 141| 132| 142| 133| 143| 135| 144| 137| 146| 139
Discharge PSIG4| 294| 263| 314| 276| 335| 290| 357| 306| 379| 321| 403| 337| 428| 354| 454| 371| 481| 389

  1. Values listed are with ventilation package disabled
  2. Return air temperature °F @ Rated CFM
  3. Below 50°F, unit requires a factory or field installed low ambient control.
  4. Suction pressure +/- 4 psi, Discharge pressure +/- 10 psi

W42G4D Cooling and Dehumidification Application Data1

DB/WB2 OD Temp. 65°F3 70°F 75°F 80°F 85°F 90°F 95°F 100°F 105°F
Mode A/C Dehum A/C Dehum A/C Dehum A/C Dehum A/C Dehum
A/C Dehum A/C Dehum A/C Dehum
75/62.5 (50% RH) Total Cooling Btuh 43,800 21,200 43,400 18,300 42,800
15,400 41,900 12,400 40,800 9,500 39,600 6,600 38,100 3,700 36,400
800 34,500
Sensible Btuh 32,800 9,300 32,600 7,000 32,400 4,800 31,800 2,400
31,300 200 30,600 (1,900) 29,900 (3,900) 29,000 (5,900) 28,000

(7,700)
S/T| 0.749| 0.439| 0.751| 0.383| 0.757| 0.312| 0.759| 0.194| 0.767| 0.021| 0.773| 0| 0.785| 0| 0.797| 0| 0.812| 0
Latent Btuh| 11,000| 11,900| 10,800| 11,300| 10,400| 10,600| 10,100| 10,000| 9,500| 9,300| 9,000| 8,500| 8,200| 7,600| 7,400| 6,700| 6,500| 5,600
Lbs. H20/hr.| 10.4| 11.2| 10.2| 10.7| 9.8| 10.0| 9.5| 9.4| 9.0| 8.8| 8.5| 8.0| 7.7| 7.2| 7.0| 6.3| 6.1| 5.3
Supply Air DB| 51.8| 67.0| 52.2| 68.9| 52.7| 70.8| 53.2| 72.9| 53.7| 74.9| 54.3| 76.9| 54.8| 79.0| 55.3| 81.1| 55.9| 83.2
Supply Air WB| 50.6| 55.7| 50.9| 56.8| 51.2| 57.7| 51.6| 58.7| 52.0| 59.7| 52.4| 60.6| 52.8| 61.6| 53.2| 62.5| 53.7| 63.4
Suction PSIG4| 124| 116| 126| 118| 126| 119| 128| 121| 129| 122| 130| 122| 131| 123| 131| 123| 132| 123
Discharge PSIG4| 282| 249| 300| 263| 319| 277| 340| 291| 363| 307| 387| 323| 413| 339| 441| 356| 471| 374
75/64.1 (55% RH)| Total Cooling Btuh| 44,800| 22,600| 44,400| 19,600| 43,800| 16,700| 43,000| 13,800| 41,900| 10,900| 40,600| 7,900| 39,200| 5,000| 37,400| 2,100| 35,500|
Sensible Btuh| 31,200| 8,400| 31,000| 6,000| 30,600| 3,700| 30,200| 1,400| 29,600| (700)| 29,000| (2,800)| 28,200| (4,900)| 27,300| (6,800)| 26,400| (8,700)
S/T| 0.696| 0.37| 0.698| 0.31| 0.699| 0.22| 0.702| 0.10| 0.706| 0| 0.714| 0| 0.719| 0| 0.730| 0| 0.744| 0
Latent Btuh| 13,600| 14,200| 13,400| 13,600| 13,200| 13,000| 12,800| 12,400| 12,300| 11,600| 11,600| 10,700| 11,000| 9,900| 10,100| 8,900| 9,100| 7,900
Lbs. H20/hr.| 12.8| 13.4| 12.6| 12.8| 12.5| 12.3| 12.1| 11.7| 11.6| 10.9| 10.9| 10.1| 10.4| 9.3| 9.5| 8.4| 8.6| 7.5
Supply Air DB| 52.9| 68.0| 53.4| 69.9| 53.9| 71.8| 54.4| 73.8| 54.9| 75.8| 55.4| 77.8| 56.0| 79.9| 56.5| 82.0| 57.0| 84.1
Supply Air WB| 52.0| 56.8| 52.3| 57.8| 52.7| 58.8| 53.0| 59.8| 53.4| 60.8| 53.8| 61.7| 54.2| 62.7| 54.6| 63.6| 55.1| 64.5
Suction PSIG4| 127| 119| 129| 121| 130| 123| 131| 124| 132| 125| 133| 126| 134| 126| 134| 126| 135| 126
Discharge PSIG4| 284| 253| 302| 266| 321| 280| 342| 295| 365| 310| 389| 326| 415| 342| 443| 359| 472| 377
75/65.5 (60% RH)| Total Cooling Btuh| 45,900| 23,900| 45,500| 21,000| 44,900| 18,100| 44,000| 15,100| 43,000| 12,200| 41,700| 9,300| 40,200| 6,400| 38,500| 3,500| 36,600| 600
Sensible Btuh| 29,500| 7,400| 29,300| 5,000| 29,100| 2,900| 28,500| 500| 28,000| (1,700)| 27,300| (3,800)| 26,600| (5,800)| 25,700| (7,800)| 24,700| (9,700)
S/T| 0.643| 0.310| 0.644| 0.238| 0.648| 0.160| 0.648| 0.033| 0.651| 0| 0.655| 0| 0.662| 0| 0.668| 0| 0.675| 0
Latent Btuh| 16,400| 16,500| 16,200| 16,000| 15,800| 15,200| 15,500| 14,600| 15,000| 13,900| 14,400| 13,100| 13,600| 12,200| 12,800| 11,300| 11,900| 10,300
Lbs. H20/hr.| 15.5| 15.6| 15.3| 15.1| 14.9| 14.3| 14.6| 13.8| 14.2| 13.1| 13.6| 12.4| 12.8| 11.5| 12.1| 10.7| 11.2| 9.7
Supply Air DB| 54.1| 68.9| 54.6| 70.8| 55.1| 72.6| 55.6| 74.7| 56.1| 76.8| 56.6| 78.8| 57.1| 80.8| 57.7| 82.9| 58.2| 85.0
Supply Air WB| 53.4| 57.9| 53.7| 58.9| 54.0| 59.9| 54.4| 60.9| 54.8| 61.9| 55.2| 62.8| 55.6| 63.7| 56.0| 64.6| 56.5| 65.5
Suction PSIG4| 130| 123| 132| 124| 132| 125| 134| 127| 135| 128| 136| 129| 137| 129| 137| 129| 138| 129
Discharge PSIG4| 286| 256| 303| 269| 322| 283| 344| 298| 366| 313| 391| 329| 417| 345| 444| 362| 474| 380
75/66.7 (65% RH)| Total Cooling Btuh| 47,000| 25,300| 46,600| 22,400| 46,000| 19,400| 45,100| 16,500| 44,000| 13,600| 42,800| 10,700| 41,300| 7,700| 39,600| 4,800| 37,700| 1,900
Sensible Btuh| 27,800| 6,400| 27,600| 4,100| 27,400| 1,900| 26,800| (500)| 26,300| (2,700)| 25,600| (4,800)| 24,900| (6,800)| 24,000| (8,800)| 23,000| (10,600)
S/T| 0.591| 0.25| 0.592| 0.18| 0.596| 0.10| 0.594| 0| 0.598| 0| 0.598| 0| 0.603| 0| 0.606| 0| 0.610| 0
Latent Btuh| 19,200| 18,900| 19,000| 18,300| 18,600| 17,500| 18,300| 17,000| 17,700| 16,300| 17,200| 15,500| 16,400| 14,500| 15,600| 13,600| 14,700| 12,500
Lbs. H20/hr.| 18.1| 17.8| 17.9| 17.3| 17.5| 16.5| 17.3| 16.0| 16.7| 15.4| 16.2| 14.6| 15.5| 13.7| 14.7| 12.8| 13.9| 11.8
Supply Air DB| 55.3| 69.8| 55.8| 71.7| 56.3| 73.6| 56.8| 75.7| 57.3| 77.7| 57.8| 79.7| 58.3| 81.8| 58.8| 83.9| 59.4| 86.0
Supply Air WB| 54.8| 59.0| 55.1| 60.0| 55.4| 61.0| 55.8| 62.0| 56.2| 62.9| 56.6| 63.9| 57.0| 64.8| 57.4| 65.7| 57.9| 66.6
Suction PSIG4| 133| 126| 135| 127| 135| 128| 137| 130| 138| 131| 139| 132| 140| 132| 141| 132| 141| 132
Discharge PSIG4| 287| 259| 305| 272| 324| 286| 345| 301| 368| 316| 392| 332| 418| 348| 446| 365| 476| 383
75/68 (70% RH)| Total Cooling Btuh| 48,000| 26,600| 47,600| 23,700| 47,000| 20,800| 46,200| 17,900| 45,100| 14,900| 43,800| 12,000| 42,400| 9,100| 40,600| 6,200| 38,700| 3,300
Sensible Btuh| 26,200| 5,500| 26,000| 3,100| 25,800| 1,000| 25,200| (1,500)| 24,600| (3,600)| 24,000| (5,700)| 23,200| (7,800)| 22,300| (9,700)| 21,400| (11,600)
S/T| 0.546| 0.207| 0.546| 0.131| 0.549| 0.048| 0.545| 0| 0.545| 0| 0.548| 0| 0.547| 0| 0.549| 0| 0.553| 0
Latent Btuh| 21,800| 21,100| 21,600| 20,600| 21,200| 19,800| 21,000| 19,400| 20,500| 18,500| 19,800| 17,700| 19,200| 16,900| 18,300| 15,900| 17,300| 14,900
Lbs. H20/hr.| 20.6| 19.9| 20.4| 19.4| 20.0| 18.7| 19.8| 18.3| 19.3| 17.5| 18.7| 16.7| 18.1| 15.9| 17.3| 15.0| 16.3| 14.1
Supply Air DB| 56.5| 70.8| 56.9| 72.7| 57.4| 74.5| 57.9| 76.6| 58.4| 78.6| 59.0| 80.7| 59.5| 82.7| 60.0| 84.8| 60.6| 86.9
Supply Air WB| 56.2| 60.1| 56.5| 61.1| 56.8| 62.1| 57.2| 63.1| 57.6| 64.0| 58.0| 65.0| 58.4| 65.9| 58.8| 66.8| 59.3| 67.7
Suction PSIG4| 136| 129| 138| 131| 138| 131| 140| 133| 141| 134| 142| 135| 143| 135| 144| 136| 144| 136
Discharge PSIG4| 289| 262| 306| 275| 325| 289| 347| 304| 369| 319| 394| 335| 420| 351| 448| 368| 477| 386
80/68.3 (55% RH)| Total Cooling Btuh| 48,500| 27,200| 48,100| 24,200| 47,500| 21,300| 46,700| 18,400| 45,600| 15,400| 44,400| 12,500| 42,900| 9,600| 41,200| 6,700| 39,200| 3,800
Sensible Btuh| 32,300| 10,200| 32,100| 7,900| 31,900| 5,700| 31,300| 3,300| 30,800| 1,100| 30,100| (1,000)| 29,300| (3,000)| 28,500| (5,000)| 27,500| (6,800)
S/T| 0.666| 0.38| 0.667| 0.33| 0.672| 0.27| 0.670| 0.18| 0.675| 0.07| 0.678| 0| 0.683| 0| 0.692| 0| 0.702| 0
Latent Btuh| 16,200| 17,000| 16,000| 16,300| 15,600| 15,600| 15,400| 15,100| 14,800| 14,300| 14,300| 13,500| 13,600| 12,600| 12,700| 11,700| 11,700| 10,600
Lbs. H20/hr.| 15.3| 16.0| 15.1| 15.4| 14.7| 14.7| 14.5| 14.2| 14.0| 13.5| 13.5| 12.7| 12.8| 11.9| 12.0| 11.0| 11.0| 10.0
Supply Air DB| 57.2| 71.6| 57.6| 73.5| 58.1| 75.3| 58.6| 77.4| 59.1| 79.4| 59.7| 81.4| 60.2| 83.5| 60.7| 85.6| 61.2| 87.7
Supply Air WB| 56.2| 60.0| 56.5| 61.0| 56.8| 62.0| 57.2| 63.0| 57.6| 64.0| 58.0| 64.9| 58.4| 65.9| 58.8| 66.8| 59.3| 67.7
Suction PSIG4| 139| 129| 140| 131| 140| 132| 143| 134| 144| 135| 145| 135| 145| 136| 146| 136| 146| 136
Discharge PSIG4| 287| 261| 304| 274| 323| 288| 345| 303| 367| 318| 392| 334| 418| 350| 446| 368| 475| 385

  1. Values listed are with ventilation package disabled
  2. Return air temperature °F @ Rated CFM
  3. Below 50°F, unit requires a factory or field installed low ambient control.
  4. Suction pressure +/- 4 psi, Discharge pressure +/- 10 psi

W48G4D Cooling and Dehumidification Application Data1

DB/WB2 OD Temp. 65°F3 70°F 75°F 80°F 85°F 90°F 95°F 100°F 105°F
Mode A/C Dehum A/C Dehum A/C Dehum A/C Dehum A/C Dehum
A/C Dehum A/C Dehum A/C Dehum
75/62.5 (50% RH) Total Cooling Btuh 51,700 24,800 50,300 21,800 48,900
18,700 47,500 15,500 46,000 12,200 44,600 8,900 43,100 5,400 41,600
1,900 40,200
Sensible Btuh 38,600 11,500 38,100 9,100 37,300 6,800 36,900 4,400
36,300 2,000 35,700 (400) 35,000 (2,800) 34,300 (5,200) 33,600

(7,700)
S/T| 0.747| 0.464| 0.757| 0.417| 0.763| 0.364| 0.777| 0.284| 0.789| 0.164| 0.800| 0| 0.812| 0| 0.825| 0| 0.836| 0
Latent Btuh| 13,100| 13,300| 12,200| 12,700| 11,600| 11,900| 10,600| 11,100| 9,700| 10,200| 8,900| 9,300| 8,100| 8,200| 7,300| 7,100| 6,600| 5,900
Lbs. H20/hr.| 12.4| 12.5| 11.5| 12.0| 10.9| 11.2| 10.0| 10.5| 9.2| 9.6| 8.4| 8.8| 7.6| 7.7| 6.9| 6.7| 6.2| 5.6
Supply Air DB| 51.8| 66.0| 52.3| 67.9| 52.5| 69.7| 53.2| 71.7| 53.6| 73.6| 54.0| 75.5| 54.4| 77.5| 54.8| 79.4| 55.2| 81.4
Supply Air WB| 50.7| 55.3| 51.1| 56.3| 51.3| 57.2| 51.9| 58.2| 52.3| 59.2| 52.6| 60.2| 53.0| 61.2| 53.3| 62.2| 53.7| 63.2
Suction PSIG4| 119| 109| 120| 110| 120| 112| 121| 113| 122| 115| 123| 116| 124| 118| 126| 119| 127| 121
Discharge PSIG4| 282| 252| 301| 265| 325| 279| 343| 294| 366| 309| 390| 324| 415| 340| 442| 357| 470| 375
75/64.1 (55% RH)| Total Cooling Btuh| 52,900| 26,300| 51,600| 23,300| 50,200| 20,200| 48,700| 17,000| 47,300| 13,700| 45,900| 10,400| 44,400| 6,900| 42,900| 3,400| 41,400|
Sensible Btuh| 36,600| 10,300| 36,000| 8,000| 35,500| 5,600| 34,900| 3,300| 34,200| 900| 33,600| (1,500)| 32,900| (4,000)| 32,200| (6,400)| 31,500| (8,900)
S/T| 0.692| 0.39| 0.698| 0.34| 0.707| 0.28| 0.717| 0.19| 0.723| 0.07| 0.732| 0| 0.741| 0| 0.751| 0| 0.761| 0
Latent Btuh| 16,300| 16,000| 15,600| 15,300| 14,700| 14,600| 13,800| 13,700| 13,100| 12,800| 12,300| 11,900| 11,500| 10,900| 10,700| 9,800| 9,900| 8,600
Lbs. H20/hr.| 15.4| 15.1| 14.7| 14.4| 13.9| 13.8| 13.0| 12.9| 12.4| 12.1| 11.6| 11.2| 10.8| 10.3| 10.1| 9.2| 9.3| 8.1
Supply Air DB| 53.1| 67.0| 53.5| 68.9| 54.0| 70.8| 54.4| 72.7| 54.8| 74.6| 55.2| 76.6| 55.6| 78.5| 56.0| 80.5| 56.4| 82.4
Supply Air WB| 52.1| 56.4| 52.5| 57.4| 52.9| 58.3| 53.3| 59.3| 53.6| 60.3| 54.0| 61.3| 54.4| 62.3| 54.7| 63.3| 55.1| 64.3
Suction PSIG4| 122| 112| 123| 113| 123| 115| 124| 116| 125| 117| 126| 119| 127| 120| 129| 122| 130| 123
Discharge PSIG4| 284| 256| 303| 269| 324| 282| 345| 297| 368| 312| 392| 327| 417| 344| 444| 360| 472| 378
75/65.5 (60% RH)| Total Cooling Btuh| 54,200| 27,900| 52,800| 24,800| 51,400| 21,700| 50,000| 18,500| 48,600| 15,300| 47,200| 11,900| 45,700| 8,400| 44,200| 4,900| 42,700| 1,300
Sensible Btuh| 34,500| 9,200| 34,000| 6,800| 33,200| 4,500| 32,800| 2,100| 32,200| (300)| 31,500| (2,700)| 30,900| (5,100)| 30,200| (7,600)| 29,400| (10,000)
S/T| 0.637| 0.330| 0.644| 0.274| 0.646| 0.207| 0.656| 0.114| 0.663| 0| 0.667| 0| 0.676| 0| 0.683| 0| 0.689| 0
Latent Btuh| 19,700| 18,700| 18,800| 18,000| 18,200| 17,200| 17,200| 16,400| 16,400| 15,600| 15,700| 14,600| 14,800| 13,500| 14,000| 12,500| 13,300| 11,300
Lbs. H20/hr.| 18.6| 17.6| 17.7| 17.0| 17.2| 16.2| 16.2| 15.5| 15.5| 14.7| 14.8| 13.8| 14.0| 12.7| 13.2| 11.8| 12.5| 10.7
Supply Air DB| 54.3| 68.0| 54.8| 69.9| 55.0| 71.8| 55.6| 73.7| 56.0| 75.7| 56.5| 77.6| 56.9| 79.5| 57.3| 81.5| 57.7| 83.4
Supply Air WB| 53.5| 57.5| 53.9| 58.5| 54.0| 59.4| 54.6| 60.4| 55.0| 61.4| 55.4| 62.4| 55.7| 63.4| 56.1| 64.4| 56.4| 65.4
Suction PSIG4| 125| 115| 126| 116| 126| 118| 127| 119| 128| 120| 129| 122| 130| 123| 132| 125| 133| 126
Discharge PSIG4| 287| 259| 305| 272| 329| 285| 347| 300| 370| 315| 394| 330| 419| 347| 446| 364| 474| 381
75/66.7 (65% RH)| Total Cooling Btuh| 55,500| 29,400| 54,100| 26,400| 52,700| 23,200| 51,300| 20,100| 49,900| 16,800| 48,400| 13,400| 47,000| 10,000| 45,500| 6,400| 44,000| 2,800
Sensible Btuh| 32,500| 8,000| 31,900| 5,700| 31,100| 3,400| 30,700| 1,000| 30,100| (1,400)| 29,500| (3,800)| 28,800| (6,300)| 28,100| (8,700)| 27,400| (11,200)
S/T| 0.586| 0.27| 0.590| 0.22| 0.590| 0.15| 0.598| 0.05| 0.603| 0| 0.610| 0| 0.613| 0| 0.618| 0| 0.623| 0
Latent Btuh| 23,000| 21,400| 22,200| 20,700| 21,600| 19,800| 20,600| 19,100| 19,800| 18,200| 18,900| 17,200| 18,200| 16,300| 17,400| 15,100| 16,600| 14,000
Lbs. H20/hr.| 21.7| 20.2| 20.9| 19.5| 20.4| 18.7| 19.4| 18.0| 18.7| 17.2| 17.8| 16.2| 17.2| 15.4| 16.4| 14.2| 15.7| 13.2
Supply Air DB| 55.6| 69.1| 56.0| 70.9| 56.3| 72.8| 56.9| 74.8| 57.3| 76.7| 57.7| 78.6| 58.1| 80.5| 58.5| 82.5| 58.9| 84.5
Supply Air WB| 54.9| 58.6| 55.3| 59.6| 55.4| 60.5| 56.0| 61.5| 56.4| 62.5| 56.8| 63.5| 57.1| 64.5| 57.5| 65.5| 57.8| 66.5
Suction PSIG4| 128| 118| 129| 119| 129| 121| 130| 122| 131| 123| 132| 124| 133| 126| 135| 128| 136| 129
Discharge PSIG4| 289| 262| 307| 275| 331| 288| 349| 303| 372| 318| 396| 333| 421| 350| 448| 367| 476| 384
75/68 (70% RH)| Total Cooling Btuh| 56,800| 30,900| 55,400| 27,900| 54,000| 24,800| 52,600| 21,600| 51,200| 18,300| 49,700| 14,900| 48,300| 11,500| 46,800| 7,900| 45,300| 4,300
Sensible Btuh| 30,400| 6,900| 29,900| 4,500| 29,100| 2,200| 28,700| (200)| 28,100| (2,600)| 27,400| (5,000)| 26,700| (7,400)| 26,000| (9,900)| 25,300| (12,300)
S/T| 0.535| 0.223| 0.540| 0.161| 0.539| 0.089| 0.546| 0| 0.549| 0| 0.551| 0| 0.553| 0| 0.556| 0| 0.558| 0
Latent Btuh| 26,400| 24,000| 25,500| 23,400| 24,900| 22,600| 23,900| 21,800| 23,100| 20,900| 22,300| 19,900| 21,600| 18,900| 20,800| 17,800| 20,000| 16,600
Lbs. H20/hr.| 24.9| 22.6| 24.1| 22.1| 23.5| 21.3| 22.5| 20.6| 21.8| 19.7| 21.0| 18.8| 20.4| 17.8| 19.6| 16.8| 18.9| 15.7
Supply Air DB| 56.8| 70.1| 57.2| 72.0| 57.5| 73.8| 58.1| 75.8| 58.5| 77.7| 58.9| 79.6| 59.3| 81.6| 59.7| 83.5| 60.1| 85.5
Supply Air WB| 56.2| 59.7| 56.6| 60.7| 56.8| 61.6| 57.4| 62.6| 57.8| 63.6| 58.1| 64.6| 58.5| 65.6| 58.9| 66.6| 59.2| 67.6
Suction PSIG4| 131| 120| 132| 122| 132| 123| 133| 124| 134| 126| 135| 127| 136| 129| 138| 130| 139| 132
Discharge PSIG4| 291| 265| 309| 278| 333| 291| 351| 306| 374| 321| 398| 337| 423| 353| 450| 370| 478| 387
80/68.3 (55% RH)| Total Cooling Btuh| 56,900| 31,200| 55,600| 28,200| 54,200| 25,100| 52,700| 21,900| 51,300| 18,600| 49,900| 15,300| 48,400| 11,800| 46,900| 8,300| 45,400| 4,600
Sensible Btuh| 37,700| 12,000| 37,100| 9,700| 36,300| 7,400| 35,900| 5,000| 35,300| 2,600| 34,700| 200| 34,000| (2,300)| 33,300| (4,700)| 32,600| (7,200)
S/T| 0.663| 0.38| 0.667| 0.34| 0.670| 0.29| 0.681| 0.23| 0.688| 0.14| 0.695| 0.01| 0.702| 0| 0.710| 0| 0.718| 0
Latent Btuh| 19,200| 19,200| 18,500| 18,500| 17,900| 17,700| 16,800| 16,900| 16,000| 16,000| 15,200| 15,100| 14,400| 14,100| 13,600| 13,000| 12,800| 11,800
Lbs. H20/hr.| 18.1| 18.1| 17.5| 17.5| 16.9| 16.7| 15.8| 15.9| 15.1| 15.1| 14.3| 14.2| 13.6| 13.3| 12.8| 12.3| 12.1| 11.1
Supply Air DB| 57.4| 70.7| 57.9| 72.6| 58.1| 74.4| 58.7| 76.4| 59.2| 78.3| 59.6| 80.2| 60.0| 82.2| 60.4| 84.1| 60.8| 86.1
Supply Air WB| 56.5| 59.7| 56.9| 60.7| 57.0| 61.6| 57.6| 62.6| 58.0| 63.6| 58.4| 64.6| 58.7| 65.6| 59.1| 66.6| 59.4| 67.6
Suction PSIG4| 132| 121| 133| 122| 133| 124| 134| 125| 135| 126| 136| 128| 137| 129| 139| 131| 140| 132
Discharge PSIG4| 286| 264| 305| 277| 328| 291| 347| 305| 369| 320| 393| 336| 419| 352| 445| 369| 473| 386

  1. Values listed are with ventilation package disabled
  2. Return air temperature °F @ Rated CFM
  3. Below 50°F, unit requires a factory or field installed low ambient control.
  4. Suction pressure +/- 4 psi, Discharge pressure +/- 10 psi

W60G4D Cooling and Dehumidification Application Data1

DB/WB2 OD Temp. 65°F3 70°F 75°F 80°F 85°F 90°F 95°F 100°F 105°F
Mode A/C Dehum A/C Dehum A/C Dehum A/C Dehum A/C Dehum
A/C Dehum A/C Dehum A/C Dehum
75/62.5 (50% RH) Total Cooling Btuh 61,600 31,700 59,800 28,400 58,000
25,000 56,200 21,600 54,400 18,200 52,600 14,600 50,900 11,000
49,100 7,300 47,400 3,600
Sensible Btuh 45,400 14,000 44,700 11,600 44,200 9,200 43,100 6,500
42,300 3,900 41,500 1,300 40,600 (1,300) 39,800 (4,100) 39,000

(6,800)
S/T| 0.737| 0.442| 0.747| 0.408| 0.762| 0.368| 0.767| 0.301| 0.778| 0.214| 0.789| 0.089| 0.798| 0| 0.811| 0| 0.823| 0
Latent Btuh| 16,200| 17,700| 15,100| 16,800| 13,800| 15,800| 13,100| 15,100| 12,100| 14,300| 11,100| 13,300| 10,300| 12,300| 9,300| 11,400| 8,400| 10,400
Lbs. H20/hr.| 15.3| 16.7| 14.2| 15.8| 13.0| 14.9| 12.4| 14.2| 11.4| 13.5| 10.5| 12.5| 9.7| 11.6| 8.8| 10.8| 7.9| 9.8
Supply Air DB| 50.1| 64.8| 50.6| 66.6| 50.9| 68.4| 51.6| 70.4| 52.0| 72.4| 52.5| 74.3| 52.9| 76.3| 53.4| 78.4| 53.8| 80.4
Supply Air WB| 49.4| 53.9| 49.9| 54.9| 50.1| 55.8| 50.8| 56.8| 51.2| 57.8| 51.6| 58.8| 52.0| 59.8| 52.4| 60.8| 52.8| 61.7
Suction PSIG4| 122| 114| 123| 115| 124| 116| 125| 118| 126| 120| 127| 121| 128| 122| 130| 124| 131| 125
Discharge PSIG4| 284| 267| 304| 280| 325| 293| 347| 308| 370| 323| 394| 339| 419| 355| 445| 372| 473| 390
75/64.1 (55% RH)| Total Cooling Btuh| 63,100| 33,200| 61,300| 29,900| 59,500| 26,500| 57,700| 23,100| 55,900| 19,600| 54,200| 16,100| 52,400| 12,500| 50,600| 8,800| 48,900| 5,100
Sensible Btuh| 43,100| 12,600| 42,400| 10,200| 41,600| 7,700| 40,800| 5,100| 40,000| 2,600| 39,200| (100)| 38,300| (2,700)| 37,500| (5,400)| 36,700| (8,200)
S/T| 0.683| 0.38| 0.692| 0.34| 0.699| 0.29| 0.707| 0.22| 0.716| 0.13| 0.723| 0| 0.731| 0| 0.741| 0| 0.751| 0
Latent Btuh| 20,000| 20,600| 18,900| 19,700| 17,900| 18,800| 16,900| 18,000| 15,900| 17,000| 15,000| 16,200| 14,100| 15,200| 13,100| 14,200| 12,200| 13,300
Lbs. H20/hr.| 18.9| 19.4| 17.8| 18.6| 16.9| 17.7| 15.9| 17.0| 15.0| 16.0| 14.2| 15.3| 13.3| 14.3| 12.4| 13.4| 11.5| 12.5
Supply Air DB| 51.5| 65.9| 51.9| 67.8| 52.4| 69.6| 52.9| 71.5| 53.3| 73.5| 53.8| 75.5| 54.2| 77.5| 54.7| 79.5| 55.1| 81.6
Supply Air WB| 50.8| 55.0| 51.3| 56.0| 51.7| 57.0| 52.2| 58.0| 52.6| 59.0| 53.0| 60.0| 53.4| 61.0| 53.8| 61.9| 54.2| 62.9
Suction PSIG4| 126| 117| 126| 119| 127| 120| 128| 121| 129| 123| 130| 124| 132| 126| 133| 127| 134| 128
Discharge PSIG4| 286| 270| 306| 283| 327| 297| 349| 311| 372| 326| 396| 342| 421| 359| 447| 376| 475| 394
75/65.5 (60% RH)| Total Cooling Btuh| 64,600| 34,600| 62,800| 31,400| 61,000| 28,000| 59,200| 24,600| 57,500| 21,100| 55,700| 17,600| 53,900| 14,000| 52,200| 10,300| 50,400| 6,600
Sensible Btuh| 40,900| 11,300| 40,100| 8,800| 39,600| 6,400| 38,500| 3,700| 37,700| 1,200| 36,900| (1,500)| 36,000| (4,100)| 35,200| (6,800)| 34,400| (9,600)
S/T| 0.633| 0.327| 0.639| 0.280| 0.649| 0.229| 0.650| 0.150| 0.656| 0.057| 0.662| 0| 0.668| 0| 0.674| 0| 0.683| 0
Latent Btuh| 23,700| 23,300| 22,700| 22,600| 21,400| 21,600| 20,700| 20,900| 19,800| 19,900| 18,800| 19,100| 17,900| 18,100| 17,000| 17,100| 16,000| 16,200
Lbs. H20/hr.| 22.4| 22.0| 21.4| 21.3| 20.2| 20.4| 19.5| 19.7| 18.7| 18.8| 17.7| 18.0| 16.9| 17.1| 16.0| 16.1| 15.1| 15.3
Supply Air DB| 52.8| 67.0| 53.3| 68.9| 53.5| 70.6| 54.2| 72.7| 54.7| 74.6| 55.1| 76.6| 55.6| 78.6| 56.0| 80.6| 56.4| 82.7
Supply Air WB| 52.2| 56.2| 52.7| 57.2| 52.9| 58.2| 53.6| 59.2| 54.0| 60.2| 54.4| 61.1| 54.8| 62.1| 55.2| 63.1| 55.6| 64.1
Suction PSIG4| 129| 120| 130| 122| 130| 123| 131| 124| 132| 126| 134| 127| 135| 129| 136| 130| 137| 131
Discharge PSIG4| 287| 274| 308| 287| 329| 300| 351| 315| 374| 330| 398| 346| 423| 362| 449| 379| 476| 397
75/66.7 (65% RH)| Total Cooling Btuh| 66,200| 36,100| 64,400| 32,800| 62,500| 29,500| 60,800| 26,100| 59,000| 22,600| 57,200| 19,100| 55,400| 15,500| 53,700| 11,800| 51,900| 8,100
Sensible Btuh| 38,600| 9,900| 37,800| 7,400| 37,300| 5,100| 36,200| 2,400| 35,400| (200)| 34,600| (2,800)| 33,700| (5,500)| 32,900| (8,200)| 32,100| (11,000)
S/T| 0.583| 0.27| 0.587| 0.23| 0.597| 0.17| 0.595| 0.09| 0.600| 0| 0.605| 0| 0.608| 0| 0.613| 0| 0.618| 0
Latent Btuh| 27,600| 26,200| 26,600| 25,400| 25,200| 24,400| 24,600| 23,700| 23,600| 22,800| 22,600| 21,900| 21,700| 21,000| 20,800| 20,000| 19,800| 19,100
Lbs. H20/hr.| 26.0| 24.7| 25.1| 24.0| 23.8| 23.0| 23.2| 22.4| 22.3| 21.5| 21.3| 20.7| 20.5| 19.8| 19.6| 18.9| 18.7| 18.0
Supply Air DB| 54.1| 68.1| 54.6| 70.0| 54.8| 71.8| 55.5| 73.8| 56.0| 75.7| 56.4| 77.7| 56.9| 79.7| 57.3| 81.7| 57.7| 83.8
Supply Air WB| 53.6| 57.4| 54.1| 58.4| 54.3| 59.3| 55.0| 60.4| 55.4| 61.3| 55.8| 62.3| 56.2| 63.3| 56.6| 64.3| 57.0| 65.3
Suction PSIG4| 132| 123| 133| 125| 134| 126| 135| 128| 136| 129| 137| 130| 138| 132| 139| 133| 141| 135
Discharge PSIG4| 289| 277| 310| 290| 331| 304| 353| 318| 376| 334| 400| 349| 425| 366| 451| 383| 478| 401
75/68 (70% RH)| Total Cooling Btuh| 67,700| 37,600| 65,900| 34,300| 64,100| 30,900| 62,300| 27,600| 60,500| 24,100| 58,700| 20,500| 57,000| 16,900| 55,200| 13,300| 53,500| 9,500
Sensible Btuh| 36,300| 8,500| 35,500| 6,000| 35,000| 3,700| 33,900| 1,000| 33,100| (1,600)| 32,300| (4,200)| 31,400| (6,900)| 30,600| (9,600)| 29,800| (12,400)
S/T| 0.536| 0.226| 0.539| 0.175| 0.546| 0.120| 0.544| 0.036| 0.547| 0| 0.550| 0| 0.551| 0| 0.554| 0| 0.557| 0
Latent Btuh| 31,400| 29,100| 30,400| 28,300| 29,100| 27,200| 28,400| 26,600| 27,400| 25,700| 26,400| 24,700| 25,600| 23,800| 24,600| 22,900| 23,700| 21,900
Lbs. H20/hr.| 29.6| 27.5| 28.7| 26.7| 27.5| 25.7| 26.8| 25.1| 25.8| 24.2| 24.9| 23.3| 24.2| 22.5| 23.2| 21.6| 22.4| 20.7
Supply Air DB| 55.4| 69.3| 55.9| 71.1| 56.2| 72.9| 56.8| 74.9| 57.3| 76.8| 57.7| 78.8| 58.2| 80.8| 58.6| 82.8| 59.1| 84.9
Supply Air WB| 55.0| 58.6| 55.5| 59.5| 55.7| 60.5| 56.4| 61.5| 56.8| 62.5| 57.2| 63.5| 57.6| 64.5| 58.0| 65.5| 58.4| 66.4
Suction PSIG4| 135| 126| 136| 128| 137| 129| 138| 131| 139| 132| 140| 134| 141| 135| 142| 136| 144| 138
Discharge PSIG4| 291| 281| 311| 294| 332| 307| 355| 322| 378| 337| 402| 353| 427| 369| 453| 386| 480| 404
80/68.3 (55% RH)| Total Cooling Btuh| 67,900| 37,800| 66,100| 34,500| 64,300| 31,100| 62,500| 27,700| 60,700| 24,200| 58,900| 20,700| 57,200| 17,100| 55,400| 13,400| 53,700| 9,700
Sensible Btuh| 43,900| 14,400| 43,100| 11,900| 42,700| 9,600| 41,500| 6,900| 40,700| 4,300| 39,900| 1,700| 39,100| (1,000)| 38,300| (3,700)| 37,400| (6,400)
S/T| 0.647| 0.38| 0.652| 0.34| 0.664| 0.31| 0.664| 0.25| 0.671| 0.18| 0.677| 0.08| 0.684| 0| 0.691| 0| 0.696| 0
Latent Btuh| 24,000| 23,400| 23,000| 22,600| 21,600| 21,500| 21,000| 20,800| 20,000| 19,900| 19,000| 19,000| 18,100| 18,100| 17,100| 17,100| 16,300| 16,100
Lbs. H20/hr.| 22.6| 22.1| 21.7| 21.3| 20.4| 20.3| 19.8| 19.6| 18.9| 18.8| 17.9| 17.9| 17.1| 17.1| 16.1| 16.1| 15.4| 15.2
Supply Air DB| 55.9| 69.6| 56.4| 71.5| 56.6| 73.3| 57.3| 75.3| 57.8| 77.2| 58.2| 79.2| 58.7| 81.2| 59.1| 83.2| 59.5| 85.3
Supply Air WB| 55.3| 58.6| 55.7| 59.6| 55.9| 60.6| 56.6| 61.6| 57.0| 62.6| 57.4| 63.6| 57.9| 64.6| 58.3| 65.5| 58.6| 66.5
Suction PSIG4| 136| 127| 136| 128| 137| 129| 138| 131| 139| 133| 140| 134| 142| 135| 143| 137| 144| 138
Discharge PSIG4| 291| 280| 311| 293| 332| 306| 354| 321| 377| 336| 401| 352| 426| 368| 452| 385| 480| 403

  1. Values listed are with ventilation package disabled
  2. Return air temperature °F @ Rated CFM
  3. Below 50°F, unit requires a factory or field installed low ambient control.
  4. Suction pressure +/- 4 psi, Discharge pressure +/- 10 psi

Specifications

TABLE 3A
W24G4D, W30G4D and W36G4D Model

Models| W24G4DA| W24G4DB| W24G4DC| W30G4DA| W30G4DB| W30G4DC| W36G4DA| W36G4DB| W36G4DC
---|---|---|---|---|---|---|---|---|---
Electrical Rating – 60 Hz| 230/208-1| 230/208-3| 460-3| 230/208-1| 230/208-3| 460-3| 230/208-1| 230/208-3| 460-3
Operating Voltage Range| 197-253| 187-253| 414-506| 197-253| 187-253| 414-506| 197-253| 187-253| 414-506
Minimum Circuit Ampacity| 20.8| 12.8| 7.8| 22.5| 16| 7.8| 26.4| 18.7| 10.6

  • Field Wire Size| 10| 14| 14| 10| 12| 14| 8| 10| 14
    Ground Wire Size| 10| 14| 14| 10| 12| 14| 10| 10| 14
    Delay Fuse or Circuit Breaker Max.| 30| 15| 10| 30| 20| 10| 35| 25| 15
    Compressor
    Voltage| 230/208| 230/208| 460| 230/208| 230/208| 460| 230/208| 230/208| 460
    Rated Load Amps| 7.9/9.2| 4.8/5.6| 2.6| 9.3/10.6| 6/6.8| 3.2| 12.6/14.3| 8.2/9.3| 5.1
    Branch Circuit Selection Current| 12.9| 6.5| 3.6| 14.2| 9| 4.2| 16.7| 10.5| 5.8
    Lock Rotor Amps| 58.3| 55.4| 28| 73| 58| 28| 79| 73| 38
    Compressor Type| Scroll| Scroll| Scroll| Scroll| Scroll| Scroll| Scroll| Scroll| Scroll
    Fan Motor and Condenser
    Fan Motor – HP/RPM/SPD| 1/5-1100-1| 1/5-1100-1| 1/5-1100-1| 1/5-1100-1| 1/5-1100-1| 1/5-1100-1| 1/5-1100-1| 1/5-1100-1| 1/5-1100-1
    Fan Motor – Amps| 1.4| 1.4| 0.8| 1.4| 1.4| 0.8| 1.4| 1.4| 0.8
    Fan – DIA/CFM| 20” – 2100| 20” – 2100| 20” – 2100| 20” – 2100| 20” – 2100| 20” – 2100| 20” – 2000| 20” – 2000| 20” – 2000
    Blower Motor and Evaporator
    Blower Motor – HP/RPM/SPD| 1/2-670-5| 1/2-670-5| 1/2-670-5| 1/2-750-5| 1/2-750-5| 1/2-750-5| 1/2-870-5| 1/2-870-5| 1/2-870-5
    Blower Motor – Amps| 1| 1| 1.2| 1.1| 1.1| 0.6| 1.9| 1.9| 1.2
    CFM Cooling and E.S.P.| 800 – 0.15| 800 – 0.15| 800 – 0.15| 900 – 0.15| 900 – 0.15| 900 – 0.15| 1100 – 0.15| 1100 – 0.15| 1100 – 0.15
    Filter Size| 20 x 25 x 2| 20 x 25 x 2| 20 x 25 x 2| 20 x 25 x 2| 20 x 25 x 2| 20 x 25 x 2| 20 x 25 x 2| 20 x 25 x 2| 20 x 25 x 2
    Shipping Weight – LBS.| 500| 500| 500| 530| 530| 530| 540| 540| 540
    Unit Charge (R-410A lb.)**| 5.750| 5.750| 5.750| 6.125| 6.125| 6.125| 7.125| 7.125| 7.125

  • 75° C Copper wire size
    ** Maximum time delay fuse or circuit breaker

TABLE 3B
W42G4D, W48G4D and W60G4D Models

Models| W42G4DA| W42G4DB| W42G4DC| W48G4DA| W48G4DB| W48G4DC| W60G4DA| W60G4DB| W60G4DC
---|---|---|---|---|---|---|---|---|---
Electrical Rating – 60 Hz| 230/208-1| 230/208-3| 460-3| 230/208-1| 230/208-3| 460-3| 230/208-1| 230/208-3| 460-3
Operating Voltage Range| 197-253| 187-253| 414-506| 197-253| 187-253| 414-506| 197-253| 187-253| 414-506
Minimum Circuit Ampacity| 31.3| 23.4| 11.6| 34.8| 25| 12| 40.6| 30.1| 15.2

  • Field Wire Size| 8| 10| 14| 8| 10| 14| 8| 8| 12
    Ground Wire Size| 10| 10| 14| 10| 10| 14| 10| 10| 12
    Delay Fuse or Circuit Breaker Max.| 40| 30| 15| 50| 30| 15| 50| 40| 20
    Compressor
    Voltage| 230/208| 230/208| 460| 230/208| 230/208| 460| 230/208| 230/208| 460
    Rated Load Amps| 14.3/16.2| 9.8/11.1| 5.9| 16.2/18.6| 10.2/11.8| 6.2| 20/22.6| 13.2/14.9| 7.2
    Branch Circuit Selection Current| 19.9| 13.6| 6.1| 21.8| 13.8| 6.3| 24.4| 16| 7.8
    Lock Rotor Amps| 112| 88| 44| 117| 83.1| 41| 144.2| 110| 52
    Compressor Type| Scroll| Scroll| Scroll| Scroll| Scroll| Scroll| Scroll| Scroll| Scroll
    Fan Motor and Condenser
    Fan Motor – HP/RPM/SPD| 1/3-850-1| 1/3-850-1| 1/3-850-1| 1/3-830-1| 1/3-830-1| 1/3-830-1| 1/2-1000-1| 1/2-1000-1| 1/2-1000-1
    Fan Motor – Amps| 1.9| 1.9| 1| 1.9| 1.9| 1| 3.8| 3.8| 2.5
    Fan – DIA/CFM| 24” – 2900| 24” – 2900| 24” – 2900| 24” – 2700| 24” – 2700| 24” – 2700| 24” – 3400| 24” – 3400| 24” – 3400
    Blower Motor and Evaporator
    Blower Motor – HP/RPM/SPD| 3/4-850-5| 3/4-850-5| 3/4-850-5| 3/4-940-5| 3/4-940-5| 3/4-940-5| 3/4-1040-5| 3/4-1040-5| 3/4-1040-5
    Blower Motor – Amps| 2.3| 2.3| 1.7| 3.4| 3.4| 1.7| 4.1| 4.1| 1.7
    CFM Cooling and E.S.P.| 1300 – 0.15| 1300 – 0.15| 1300 – 0.15| 1450 – 0.20| 1450 – 0.20| 1450 – 0.20| 1650 – 0.20| 1650 – 0.20| 1650 – 0.20
    Filter Size| 20 x 30 x 2| 20 x 30 x 2| 20 x 30 x 2| 20 x 30 x 2| 20 x 30 x 2| 20 x 30 x 2| 20 x 30 x 2| 20 x 30 x 2| 20 x 30 x 2
    Shipping Weight – LBS.| 500| 500| 500| 530| 530| 530| 550| 550| 550
    Unit Charge (R-410A lb.)**| 6.375| 6.375| 6.375| 7.500| 7.500| 7.500| 10.250| 10.250| 10.250

  • 75° C Copper wire size
    ** Maximum time delay fuse or circuit breaker

TABLE 4
Wiring Diagram Index

Unit Model No. Basic Wiring Diagram
W24G4DA 4085-173
W24G4DB 4085-273
W24G4DC 4085-396
W30G4DA 4085-173
W30G4DB 4085-273
W30G4DC 4085-396
W36G4DA 4085-173
W36G4DB 4085-273
W36G4DC 4085-396
W42G4DA 4085-173
W42G4DB 4085-273
W42G4DC 4085-396
W48G4DA 4085-173
W48G4DB 4085-273
W48G4DC 4085-396
W60G4DA 4085-171
W60G4DB 4085-271
W60G4DC 4085-394

TABLE 5
Thermostat Wire Size

Transformer VA FLA Wire Gauge Maximum Distance in Feet
20 gauge 45
18 gauge 60
55 2.3 16 gauge 100
14 gauge 160
12 gauge 250

TABLE 6
Wall Thermostat

Thermostat Predominant Features
8403-060* (1120-445) 3 Stage Cool; 3 Stage Heat Programmable/Non-Programmable

Electronic HP or Conventional Auto or Manual changeover
8403-082 (VT8600U5500B)| 2 stage Cool; 2 stage Heat Programmable/Non- Programmable Electronic HP or Conventional, Auto or Manual changeover with Occupancy Sensor, BACnet
8403-084 (VT8600U5000B)| 2 stage Cool; 2 stage Heat Programmable/Non- Programmable Electronic HP or Conventional, Auto or Manual changeover with BACnet
8403-089 (T4 Pro)| 1 stage Cool; 1 stage Heat – Heat Pump 1 stage Cool; 1 stage Heat – Conventional Programmable/Non-Programmable Electronic Auto or Manual changeover
8403-090 (T6 Pro)| 2 stage Cool; 3 stage Heat – Heat Pump 2 stage Cool; 2 stage Heat – Conventional Programmable/Non-Programmable Electronic Auto or Manual changeover
8403-091 (T701-FEMA)| 1 stage Cool, 1 stage Heat Non-Programmable FEMA use
8403-092 (T6 Pro Wi-Fi)| 2 stage Cool, 3 stage Heat – Heat Pump 2 stage Cool, 2 stage Heat – Conventional Programmable/Non-Programmable Electronic Auto or Manual changeover Wi-Fi

  • Integrated thermostat and humidistat in one

TABLE 7
Humidistat

Thermostat Predominant Features
8403-060* (1120-445) Programmable Thermostat (above) with Integral Humidistat
8403-038 (H600A 1014) Humidistat SPDT
8403-047 (H200 10-21-10) Dehumidistat – Electronic (range 10% to 90% with

adjustable stops, 3.6% differential)

  • Integrated thermostat and humidistat in one

TABLE 8
Dehumidification Relay Logic Board

24V Terminal Block Connections G Y 3 W1 Outputs from Board
Inputs to Board G Y D W2 G1
Cooling Mode Unoccupied X X
Cooling Mode Occupied X X
Cooling Mode j With Dehum X X X
1st Stage Heating Unoccupied X
1st Stage Heating Occupied X
1st Stage Heating With Dehum X X
2nd Stage Heating Unoccupied X
2nd Stage Heating Occupied X
2nd Stage Heating k With Dehum X X
Dehumidification Unoccupied X
Dehumidification Occupied X
  1. Cooling takes precedence over dehumidification. A cooling call cancels dehumidification.
  2. First stage heating cancels dehumidification.
  3. If jumper on RLB is set to “1-2 full-time dehumidification”, outputs will energize. This is the factory default setting. If jumper is set to “2-3 occupied dehumidification only”, outputs will be off.

Refrigerant Charge

The correct system R-410A charge is shown on the unit rating plate.
Reference Table 9 to validate proper system operation (+2 psig suction, +5 psig discharge) in cooling mode, not dehumidifation mode. However, it is recommended that if incorrect charge is suspected, the system refrigerant be reclaimed, evacuated and charged to the nameplate charge quantity and type.

The nameplate charge quantity is optimized for thermal performance and efficiency of this self-contained package system.
The system operating pressures in Table 9 are based upon rated airflow across the evaporator during cooling cycle.
Total system charge for these models can be found in Tables 3A and 3B on pages 12 and 13.

TABLE 9
Cooling Pressure Table

Model| Return Air Temperature| Pressure| 75°| 80°| 85°| 90°| 95°| 100°| 105°| 110°| 115°| 120°| 125°
---|---|---|---|---|---|---|---|---|---|---|---|---|---
W24G4D| 75° DB

62° WB

| Low Side

High Side

| 126.3

301.3

| 127.3

322.1

| 128.4

344.2

| 129.6

367.4

| 130.8

391.9

| 132.2

417.6

| 133.7

444.4

| 135.2

472.5

| 136.9

501.8

| 138.6

532.4

| 140.4

564.1

80° DB

67° WB

| Low Side

High Side

| 135.1

309.0

| 136.2

330.4

| 137.3

353.0

| 138.6

376.8

| 139.9

401.9

| 141.4

428.3

| 143.0

455.8

| 144.6

484.6

| 146.4

514.7

| 148.2

546.0

| 150.2

578.6

85° DB

72° WB

| Low Side

High Side

| 139.8

319.8

| 141.0

342.0

| 142.1

365.4

| 143.5

390.0

| 144.8

416.0

| 146.3

443.3

| 148.0

471.8

| 149.7

501.6

| 151.5

532.7

| 153.4

565.1

| 155.5

598.9

W30G4D| 75° DB

62° WB

| Low Side

High Side

| 127.0

304.5

| 127.9

325.5

| 128.8

347.5

| 130.0

370.6

| 131.1

394.8

| 132.4

419.9

| 133.8

446.3

| 135.3

473.7

| 136.9

502.0

| 138.7

531.6

| 140.4

562.1

80° DB

67° WB

| Low Side

High Side

| 135.8

312.3

| 136.8

333.8

| 137.8

356.4

| 139.0

380.1

| 140.2

404.9

| 141.6

430.7

| 143.1

457.7

| 144.7

485.8

| 146.4

514.9

| 148.3

545.2

| 150.2

576.5

85° DB

72° WB

| Low Side

High Side

| 140.6

323.2

| 141.6

345.5

| 142.6

368.9

| 143.9

393.4

| 145.1

419.1

| 146.6

445.8

| 148.1

473.7

| 149.8

502.8

| 151.5

532.9

| 153.5

564.3

| 155.5

596.7

W36G4D| 75° DB

62° WB

| Low Side

High Side

| 126.1

324.8

| 127.2

345.4

| 128.2

367.4

| 129.3

390.5

| 130.5

414.8

| 131.6

440.2

| 133.0

466.9

| 134.3

494.7

| 135.7

523.9

| 137.1

554.1

| 138.6

585.6

80° DB

67° WB

| Low Side

High Side

| 134.9

333.1

| 136.0

354.3

| 137.1

376.8

| 138.3

400.5

| 139.6

425.4

| 140.8

451.5

| 142.2

478.9

| 143.6

507.4

| 145.1

537.3

| 146.6

568.3

| 148.2

600.6

85° DB

72° WB

| Low Side

High Side

| 139.6

344.8

| 140.8

366.7

| 141.9

390.0

| 143.1

414.5

| 144.5

440.3

| 145.7

467.3

| 147.2

495.7

| 148.6

525.2

| 150.2

556.1

| 151.7

588.2

| 153.4

621.6

W42G4D| 75° DB

62° WB

| Low Side

High Side

| 126.8

318.2

| 127.8

338.8

| 128.8

360.9

| 129.9

384.5

| 130.9

409.7

| 132.0

436.3

| 133.1

464.5

| 134.2

494.1

| 135.3

525.3

| 136.4

558.0

| 137.5

592.2

80° DB

67° WB

| Low Side

High Side

| 135.6

326.4

| 136.7

347.5

| 137.8

370.2

| 138.9

394.4

| 140.0

420.2

| 141.2

447.5

| 142.3

479.4

| 143.5

506.8

| 144.7

538.8

| 145.9

572.3

| 147.1

607.4

85° DB

72° WB

| Low Side

High Side

| 140.3

337.8

| 141.5

359.7

| 142.6

383.2

| 143.8

408.2

| 144.9

434.9

| 146.1

463.2

| 147.3

493.1

| 148.5

524.5

| 149.8

557.7

| 151.0

592.3

|
W48G4D| 75° DB

62° WB

| Low Side

High Side

| 124.0

320.3

| 124.5

341.3

| 125.3

363.6

| 126.1

387.0

| 127.1

411.7

| 128.2

437.7

| 129.4

464.9

| 130.8

493.3

| 132.3

523.0

| 133.9

553.8

| 135.7

586.0

80° DB

67° WB

| Low Side

High Side

| 132.6

328.5

| 133.2

350.1

| 134.0

372.9

| 134.9

396.9

| 135.9

422.3

| 137.1

448.9

| 138.4

476.8

| 139.9

505.9

| 141.5

536.4

| 143.2

568.0

| 145.1

601.0

85° DB

72° WB

| Low Side

High Side

| 137.2

340.0

| 137.9

362.4

| 138.7

386.0

| 139.6

410.8

| 140.7

437.1

| 141.9

464.6

| 143.2

493.5

| 144.8

523.6

| 146.5

555.2

| 148.2

587.9

| 150.2

622.0

W60G4D| 75° DB

62° WB

| Low Side

High Side

| 124.8

326.7

| 125.9

347.6

| 127.0

369.9

| 128.1

393.7

| 129.2

419.0

| 130.3

445.6

| 131.5

473.8

| 132.7

503.3

| 133.9

534.3

| 135.1

566.8

| 136.3

600.6

80° DB

67° WB

| Low Side

High Side

| 133.5

335.1

| 134.6

356.5

| 135.8

379.4

| 137.0

403.8

| 138.2

429.7

| 139.4

457.0

| 140.6

485.9

| 141.9

516.2

| 143.2

548.0

| 144.5

581.3

| 145.8

616.0

85° DB

72° WB

| Low Side

High Side

| 138.2

346.8

| 139.3

369.0

| 140.6

392.7

| 141.8

417.9

| 143.0

444.7

| 144.3

473.0

| 145.5

502.9

| 146.9

534.3

| 148.2

567.2

| 149.6

601.6

|

Low side pressure ± 4 PSIG High side pressure ±10 PSIG
Tables based upon rated CFM (airflow) across the evaporator coil.
If there is any doubt as to correct operating charge being in the system, the charge should be reclaimed, and the system evacuated and recharged to serial plate instruction.

Bard Manufacturing Company, Inc. Bryan, Ohio 43506
www.bardhvac.com