AQUALISA RS.A1.EV.18 Rise Digital Diverter Installation Guide

June 6, 2024
AQUALISA

AQUALISA RS.A1.EV.18 Rise Digital Diverter Installation Guide

Rise Digital diverter

Components

Important information

Safety information
This product must be installed by a competent person in accordance with all relevant current Water Supply Regulations. ALL SHOWERS REQUIRING AN ELECTRICAL CONNECTION MUST BE INSTALLED BY A QUALIFIED PERSON FOLLOWING THE LATEST REVISION OF BS 7671 (WIRING REGULATIONS) AND CERTIFIED TO CURRENT BUILDING REGULATIONS.

This product is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning safe use of the product, understanding the hazards involved, by a person responsible for their safety.

Children should be supervised to ensure they do not play with the product.
Cleaning and user maintenance shall not be made by children without supervision.

This system should be installed so that other taps or appliances operated elsewhere within the premises do not significantly affect the flow.
The shower must not be used with a hot water supply temperature over 65°C.
The processor is supplied factory pre-set at a maximum temperature of 45°C. The maximum temperature is fully adjustable to suit site conditions.

If adjusted, we recommend the outlet temperature is set to a MAXIMUM of 46°C. The Digital processor must be installed in a location that is safely accessible for servicing and maintenance purposes.

The Digital processor must not be installed in situations where either the ambient temperature is likely to exceed 40°C or where freezing may occur.
The control must not be installed in situations where the ambient temperature is likely to fall below 5°C or rise above 40°C.
We do not recommend the use of Rise Digital in steam therapy facilities.

This appliance must be earthed.

Cables which are chased into the wall must be protected by a suitably sized conduit or sheathing to allow for removal in the event of service and maintenance purposes.

Surface mounted cables must also be protected by a suitable approved conduit, even in a loft, where there may be a risk of damage from vermin.

The power lead must only be replaced by the manufacturer or his accredited agent. The user control is supplied from a safety low voltage source. This product is suitable for domestic use only.

Rise Digital is supplied with a 5 year guarantee.

Installation of Digital Gravity Pumped processor (for gravity stored systems)

The Rise Digital Gravity Pumped shower system is designed to operate up to a maximum static pressure of 100kPa ((1 bar)(10 metres head)(14.5psi)).

Under no circumstances must the pumped processor be connected directly to the water main or in line with another booster pump.

The minimum actual capacity of the cold water storage cistern should be not less than 225 litres (50 gallons).

The capacity of the hot water cylinder must be capable of meeting anticipated demand.

Installation of Digital HP/Combi processor (for balanced high pressure and unvented systems, combination boiler systems and separately pumped gravity systems)

Pressures: The Rise Digital HP/Combi shower system is designed to operate up to a maximum static pressure of 700kPa ((7 bar)(100psi)). Where pressures are likely to exceed 700kPa ((7 bar)(100psi)), a pressure reducing valve must be fitted to the incoming mains supply. A setting of 400kPa ((4 bar)(60psi)) is recommended. It should be noted that daytime pressures approaching 600kPa((6 bar)(80psi)) can rise above the stated maximum overnight.

Special notes for combination boiler systems

The appliance must have a minimum domestic hot water rating of 24kW (80,000BTU) and be of the type fitted with a fully modulating gas valve. If in any doubt, please contact the appliance manufacturer before installation commences. PLEASE NOTE: DUE TO PERFORMANCE CHARACTERISTICS OF COMBINATION BOILERS, SEASONAL INLET TEMPERATURE CHANGE WILL AFFECT THE PROCESSOR OUTLET FLOW RATE RESULTING IN VARYING SHOWER FLOW RATE AND FLOW CONTROL RANGE. INLET TEMPERATURE CHANGE MAY ALSO CAUSE THE TEMPERATURE LED’S TO FLASH; THIS IS NOT NECESSARILY CHANGING THE OUTLET TEMPERATURE.

Special notes for separately pumped gravity systems

We recommend a MINIMUM pump rating of 1.5 bar. For optimum performance a 2.5 bar pump should be used for all separately pumped installations. A twin ended pump is required for use with single outlet Digital products. A universal type twin ended pump (works on both positive and negative head conditions) is required for use with Digital Divert products.

The minimum actual capacity of the cold water storage cistern should be not less than 225 litres (50 gallons). The capacity of the hot water cylinder must be capable of meeting the anticipated demand.
THIS PRODUCT IS NOT SUITABLE FOR USE WITH A SINGLE ENDED PUMP.

Connections
This product incorporates `push-fit’ type connections. Tube should be cut using a rotary type cutter and lubricated using a silicone-based lubricant or petroleum jelly (Vaseline or similar) prior to insertion into the fitting.
If plastic pipe is used, the tube insert must not increase the tube diameter or extend the cut-off length by more than 2mm. THESE FITTINGS ARE NOT SUITABLE FOR STAINLESS STEEL TUBE. COMPRESSION FITTINGS MUST NOT BE USED.

Pipe sizing
Long pipe runs, on both inlet and outlet, will reduce the flow rate at the shower head, 22mm pipe work should be used on inlets and reduce down to 15mm as close to the valve as possible to reduce pressure losses and help maintain flow rate. If using 15mm pipe, copper pipe is preferred, to optimise performance minimise the number of elbows used. If long pipe runs are unavoidable on the outlet, use copper pipe rather than plastic, particularly if a diverter is used, and minimise the number of elbows as the pipe inserts are very restrictive.

Flushing
Some modern fluxes can be very corrosive and, if left in contact, will attack the working parts of this unit. All soldering must be completed and the pipe work thoroughly flushed out in accordance with current Water Supply Regulations prior to connection of the product.

After installation
Familiarise the end user with the Rise Digital operation and hand them this guide. Complete and post the guarantee card or register online at www.aqualisa.co.uk

Installation instructions

! This product must be installed by a competent person in accordance with the relevant Water Supply Regulations.
! Fit the Digital processor, main controller and outlets following the installation instructions provided separately.
! Prior to connecting the blended supply connections to the shower/bath fittings, follow the procedure below to install the Digital diverter valve.

  • 1 To ensure safe operation and installation of this product, the Digital diverter valve MUST be installed in one of the orientations shown.

! PLEASE NOTE THE ORIENTATIONS MATCH THE PROCESSOR ORIENTATIONS AND ARE SHOWN ON THE DIGITAL DIVERTER VALVE LABEL.

  • 2 In addition to the isolation valves supplied with the Digital processor, isolation valves are also provided for use with the Digital diverter inlet and outlets. All pipe work should be run in 15mm pipe and all pipe work should be supported.

! For optimum performance use copper pipe and minimise the pipe length runs and amount of elbow fittings.

  • 3 Choose the position for your Digital diverter valve as close to the Digital processor as possible, within range of the 2m low voltage connecting data cable provided. Like the Digital processor, the Digital diverter valve may be sited in the roof space above the proposed shower/bath site, in the airing cupboard or behind a screwed bath panel if more convenient. If siting in the roof space, ensure that freezing cannot occur and that no insulation material is placed under or over the Digital diverter valve and processor.

! The Digital diverter valve inlet has been designed, to enable connection directly inline with the HP/Combi Digital processor outlet isolation valve connection, or off the Gravity Pumped Digital processor outlet, using the cranked elbow connection fitting.

The distance between the Digital diverter valve and processor must be within the 2m range of the patch lead data cable connection provided.

THE PROCESSOR MUST BE SITED IN A POSITION THAT IS SAFELY ACCESSIBLE FOR SERVICING AND MAINTENANCE PURPOSES. WHEN FITTED IN THE LOFT SPACE, THE ROUTE TO AND THE AREA AROUND THE PROCESSOR AND DIVERTER VALVE MUST BE BOARDED TO ENSURE A SAFE WORKING ENVIRONMENT.

  • 4 Place the Digital diverter valve onto a solid mounting surface, adjusting the fixing feet into suitable positions. Mark then drill and prepare suitable fixings before securing the processor to the mounting surface using the screws provided, if suitable.

  • 5 Ensuring the supply pipe work connections have been flushed through in accordance with the main installation instructions provided, connect the processor outlet pipe to the diverter inlet pipe.

! PLEASE NOTE DIRECTION OF ARROW ON ISOLATION VALVE TO INDICATE DIRECTION OF FLOW.

HP/Combi processor
IMAGES SHOWN ARE AERIAL VIEWS AND ARE FOR ILLUSTRATIVE PURPOSES ONLY.

Gravity Pumped processor
IMAGES SHOWN ARE AERIAL VIEWS AND ARE FOR ILLUSTRATIVE PURPOSES ONLY.

  • 6 Ensure that the isolation valves are connected to the diverter valve outlets, with the arrows correctly aligned according to the direction of flow.

  • 7 Run the pipes from the mixed water outlets on the Digital diverter valve through the wall to the proposed siting for the shower hose outlet, fixed head arm or bath outlet, depending on the system purchased.

! BEFORE ANY ELECTRICAL ADJUSTMENT IS ATTEMPTED, THE ELECTRICITY SUPPLY MUST BE TURNED OFF AT THE MAINS SWITCH. ELECTRICAL INSTALLATION MAY ONLY BE CARRIED OUT BY A QUALIFIED PERSON.

  • 8 Unscrew the single fixing screw from the diverter valve lid, and carefully pull the lid clear.

  • 9 Plug the end of the 10m low voltage data cable feeding from the main controller, into the open entry port on the main Digital processor.

  • 10 Plug one end of the 2m data cable (supplied with the Digital Diverter) into the secondary entry port of the main Digital processor, this can be accessed by carefully snapping off and removing the entry pillar.

  • 11 Plug the other end of the 2m data cable (supplied with the Digital Diverter) into port 1 on the Digital Diverter, this is indicated by the single dot.

! If fitting this system complete with a secondary Digital remote control, a further data cable socket has been provided within the Digital diverter valve. The Digital remote control MUST be connected here and NOT within the main Digital processor.

  • 12 Resume installation following the main and shower/bath fittings installation instructions provided prior to completing the commissioning procedure.
  • 13 Your Rise Digital shower has a High flow/Low flow, Warm up, Pause & Timer function available. Please note these features are disabled and flow is set to Low flow on both outlets as a factory default. To activate and programme these features please refer to the separate user guide for commissioning and user instructions on how to operate the shower.

Commissioning
The controller top button will automatically be assigned to diverter outlet A and the controller bottom button will automatically be assigned to diverter outlet B. If required, a default/master outlet can be selected; meaning when operated via a remote control, the preferred outlet will always operate first. With the processor set to “Normal” flow mode, the default flow rate mode for both outlets is LOW FLOW. However, if required, either or both outlets can be set to HIGH FLOW mode by following the Rise Digital Divert shower control – Setup/ programming instructions provided within the separate Rise Digital User guide.

Setting the default/master outlet

  1. For systems fitted with a remote, select position 1 (Outlet A (controller top button)) or position 2 (Outlet B (controller bottom button)) using the Digital diverter switch, to determine the default master outlet for the remote only.

After Commissioning

  1. Replace the lid onto the diverter valve and secure using the captive fixing screw.

Aqualisa Products Limited The Flyer’s Way Westerham Kent TN16 1DE

Customer helpline: 01959 560010
Brochure Hotline: 0800 652 3669
Website: www.aqualisa.co.uk
Email: [email protected]

Republic of Ireland
Sales enquiries: 01-864-3363
Service enquiries: 01-844-3212

Part No: 701106 Issue 01 Mar 14

Please note that calls may be recorded for training and quality purposes The company reserves the right to alter, change or modify the product specifications without prior warning
® Registered Trademark Aqualisa Products Limited

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

AQUALISA User Manuals

Related Manuals