AL-436-00-902 EnoSense People Counter
EnOcean Sensor for people counting / PIR based
EnOcean 902 MHz
Part no. 12466 (beige) / 12467 (black) / 12468 (white)
Version 1.02, valid since FW/HW 1.0 / 1.1
Product manual
© 2021 DEUTA Controls GmbH
All rights reserved
This Manual, including all figures and illustrations, is copyright-protected. Any further use of this Manual by third parties that violate pertinent copyright provisions is prohibited. Reproduction, translation, electronic and photomechanical filing/archiving (e.g., photocopying), as well as any amendments, require the written consent of DEUTA Controls GmbH, Bergisch Gladbach, Germany. Non-observance will involve the right to assert damage claims.
DEUTA Controls GmbH
Paffrather Straße 140
51465 Bergisch Gladbach
Phone: +49 2202 28557-61
Fax: +49 2202 28557-79
E-Mail: info@deuta-controls.de
Web: www.deuta-controls.net
Every conceivable measure has been taken to ensure the accuracy and completeness of this documentation. However, as errors can never be fully excluded, we always appreciate any information or suggestions for improving the documentation.
E-Mail: info@deuta-controls.de
Validity of this documentation
This documentation is only applicable to the product
AL-436-00-902 EnoSense People Counter
and is only applicable starting from products with FW/HW Version 1.0/1.1.
The device must only be installed and operated according to the instructions
in these operating instructions.
Intended use
The AL-436-00-902 EnoSense People Counter must not be used in any relation
with equipment that supports, directly or indirectly, human health or life or
with applications
that can result in danger for people, animals, or real value.
Disposal
Electrical and electronic equipment may not be disposed of with household
waste. This also applies to products without this symbol.
Electrical and electronic equipment contain materials and substances that can
be harmful to the environment and health. Electrical and electronic equipment
must be disposed of properly after use.
Note only for EU: WEEE 2012/19/EU applies throughout Europe. Directives
and laws may vary nationally.
Device description
4.1 Functionality
The AL-436-00-902 EnoSense People Counter offers the possibility to recognize
passing people in both directions and to send the current count value via
radio (EnOcean).
The sensor electronics, which are built into a plastic housing, are attached
with a double-sided adhesive pad over the door (vertical detection) or on a
door frame (horizontal detection).
Depending on your requirements, the sensor is available in black, white, or
beige housing. In this case, the power is supplied by two internal AA
batteries. Depending on
the application, these typically last 5 years or more.
The information is transmitted via the EnOcean wireless standard (EEP: MSC,
47-D1-07-10).
The following information is currently available for the evaluation:
- Count value (with overflow): 8 bit, 0..255
- Battery voltage: 8 bit [mV/20]
4.2 External product interface
The external product interface consists of the following items:
- Lens opening of the passive infrared sensor for passing people detection
- Service button to send teach in / learn telegram
- Push area to open sensor (access to battery holder)
4.3 Observe intended use
The AL-436-00-902 EnoSense People Counter must not be used in any relation
with equipment that supports, directly or indirectly, human health or life or
with applications
that can result in danger for people, animals, or real value.
4.4 Observe statutory provisions for operating frequency range.
The AL-436-00-902 EnoSense People Counter must only be operated in
compliance with the country-specific provisions regarding the operation of
radio equipment.
4.5 Non-conduction mounting surface
A non-conductive mounting surface is necessary.
Ensure the AL-436-00-902 EnoSense People Counter is mounted on a non-
conductive surface. If it is not, performance may be adversely affected.
Technical data
5.1 Communication / EnOcean wireless interface
Type | EnOcean |
---|---|
Number | 1 |
Transmit / receive center frequency | 902.875 MHz |
Maximum transmission power | +99 dBµV/m |
Table 1: Technical data / communication
5.2 Sensor: Motion / PIR
Detection angle | 120 degrees |
---|---|
Detection range | 0.5 – 2 m |
Table 2: Technical data / PIR sensor
5.3 User interfaces
Service button | Yes |
---|---|
Service LED | – |
5.4 Housing/connection technology
Connection technology | – |
---|---|
Housing | Plastic, PC, white / black / beige |
Table 4: Technical data/housing
5.5 Power supply
Power supply voltage | 2x AA, 1,5V internal batteries |
---|---|
Power consumption | Typ. 1 mW, 50 µA standby |
Table 5: Technical data/power supply
5.6 Environmental conditions
Operating temp. | 15°.. 40 °C |
---|---|
Storage temp. | -20 ..+70 °C |
Rel. humidity | 0..99 % rel. humidity, noncondensing |
Protection class | IP20 |
Table 6: Technical data/environmental conditions
5.7 Dimensions and weight
Weight | 87 g |
---|---|
Dimensions | 36 x 37 x 80 mm |
Table 7: Technical data/dimensions and weight
5.8 Approvals
FCC Rule parts | 15.231 |
---|---|
Equipment class | Part 15 Security / Remote control |
Table 8: Technical data/tests and approvals
5.9 Standards and guidelines
EMC| EN IEC 61000-6-2:2016
EN IEC 61000-3-2:2019
EN 61000-3-3:2013
EN 55032:2012/AC:2013
---|---
Table 9: Technical data/standards and guidelines
Functional description in detail
6.1 People counting
The AL-436-00-902 EnoSense People Counter will detect and count people
passing by the sensor element, based on PIR technology.
Depending on the direction, the counter will be incremented or decremented by
one for each event.
6.2 Send learn telegram
To connect the EnoSense People Counter to any building automation system,
a so-called learn telegram can be sent by the device.
Simply push the service button. The EnoSense People Counter will
immediately a learn telegram.
6.3 Table of supported EEP’s (EnOcean Equipment Profiles)
6.3.1 Transmit / TX
The EnOcean wireless standard defines the so-called EnOcean Equipment Profiles (EEP). Each EnOcean-based product sends and receives data according to at least one standardized data format. The EnoSense People Counter transmits data described as follows:
Cons. nr. | EEP | Description | Tx-ID |
---|---|---|---|
1 | 47-D1-07-10 | Counting value, bit (BYTE 0)+ Power | |
supply voltage, 8 bit (BYTE 3) | EURID |
Table 10: Technical data / EnOcean EEP for TX
The following table describes in detail data sent by the EnoSense People Counter according to the EEP 47-D1-07-10:
Offset| Size| Bitrange| Data| Shortcut| Description| Valid
range| Scale| Unit
---|---|---|---|---|---|---|---|---
0| 8| DB3.7…DB3.0| Supply
voltage| SVC| Battery
voltage| 0..250| 0…5.0| V
8| 23| DB2.7…DB1.0| Not used (= 0)
24| 8| DB0.7…DB0.0| Counter
value| CNT| Counter
value| 0..255| 1| –
Table 11: EnOcean transmit data
6.3.2 People counting/data transmission rules
Operational description of People counting/data transmission rules
In general, the lens in the front of the EnoSense People Counter forms two
detection zones B1 and B2. Depending on the sequence of triggering these
areas, the counter value will be increased or decreased.
As long as no motion is detected by the sensor element, no message will be
transmitted by the EnoSense People Counter. The wireless transmitter will not
be activated.
In the moment when a motion (people passing by) will be detected, the wireless
transmitter will be activated and a data message will be transmitted by the
People Counter immediately. A second message (sub telegram) will be sent after
25 ms with the same data contents.
If no further motion is detected, the People Counter will not send any further
message.
If more people are counted in the following time period, the People Counter
will send the new accumulated counter value after 65 seconds (and the second
message again after 25 ms).
This behavior is also shown in the following picture:
6.3.3 Receive/ RX
The EnoSense People Counter only sends EnOcean telegrams. No data is received/interpreted.
Cons. Nr. | EEP | Description |
---|---|---|
– | – | – |
Service/changing batteries
Caution: When opening the device, you have to take care of electrostatic discharge. Otherwise, electronics can be damaged.
In the case of discharged batteries, they can be replaced with two new AA batteries, 1.5 V. You have to push the housing with your fingers within the marked area on the side of the EnoSense People Counter to open it.
Safety remarks
CAUTION: Risk of damage or explosion if a battery of incorrect type is
used.
This product contains AA-type batteries. If a battery is swallowed, it
can cause severe internal burns in just 2 hours and can lead to death.
Keep new and used batteries away from children.
Device labels
The following labels are placed on the bottom side of the EnoSense People Counter:
Label 1:
FCC ID: 2AZTH-AL-436-00-902
PMN: AL-436-00-902
FVIN: 1.0 HVIN: 1.1
12408 / AL-602-03-902
EnoSense People Counter / RoHS
Label 2:
Label 2, Line 1: Serial number, 10 digits
Label 2, Line 2, EURID, EnOcean ID
QR-Code:
FCC (United States) Regulatory Statement
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
- This device may not cause harmful interference, and
- This device must accept any interference received, including interference that may cause undesired operation.
Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
Dimensions/drawings
Ordering information
Part name | Part nr. | Description |
---|---|---|
AL-436-00-902 EnOcean sensor „EnoSense People Counter“ / beige / FCC | 12466 |
Sensor EnOcean “EnoSense People Counter”, for counting people passing by (bi-
directional); for mounting on smooth surfaces; EEP: 47-D1-07-10; Supply
voltage 2x AA 1.5 V internal, Dimensions 36 x 37 x 80 mm, EnOcean 902 MHz,
FCC, Housing: PC, beige (similar to RAL 9010 / pure white); incl. adhesive pad
AL-436-00-902 EnOcean sensor „EnoSense People Counter“ / black / FCC| 12467|
Sensor EnOcean “EnoSense People Counter”, for counting people passing by (bi-
directional); for mounting on smooth surfaces; EEP: 47-D1-07-10; Supply
voltage 2x AA 1.5 V internal, Dimensions 36 x 37 x 80 mm, EnOcean 902 MHz,
FCC, housing: PC, Signal black (RAL 9004); incl. adhesive pad;
AL-436-00-902 EnOcean sensor „EnoSense People Counter“ / white / FCC| 12468|
Sensor EnOcean “EnoSense People Counter”, for counting people passing by (bi-
directional); for mounting on smooth surfaces; EEP: 47-D1-07-10; Supply
voltage 2x AA 1.5 V internal, Dimensions 36 x 37 x 80 mm, EnOcean 902 MHz,
FCC, housing: PC, Signal white (RAL 9003); incl. adhesive pad;
Revision history
Version | Author | Reviewer | Date | Major changes |
---|---|---|---|---|
1.00 | Lehzen | Pohl | 15.06.2021 | Initial release |
1.01 | Lehzen | Pohl | 19.11.2021 | Adopted data transmission to optimize power |
consumption
1.02| Lehzen| Pohl| 01.12.2021| Removed FCC §15.101 statement in 10;
Added/changed functional description
———— End of document ———–
© DEUTA Controls GmbH
01.12.2021
Technical data might change
Paffrather Str. 140, 51465 Bergisch Gladbach
Hauptstraße 76, 32479 Hille
info@deuta-controls.de; www.deuta-
controls.dnet
Tel.:+49 2202 285 57- 61
Tel: +49 5734 51466 – 0
Fax:+49 5734 51466 – 28