valpes DSBA3304 AXMART Doc Technique User Manual
- June 6, 2024
- Valpes
Table of Contents
valpes DSBA3304 AXMART Doc Technique
Download and install
The AXMART® software is free and available on Google Play for Android version
(v5.0 or higher) and on Apple store for the Apple version.
Software name: AXMART (v3)
Android version
Access requested by AXMART :
- Access to position
- Access to gallery/photos
Apple version
- Before launching AXMART , the device clock must be correct.
- During the switch between winter and summer time, a connection to the actuators is imperative for clocks synchronisation.
General description
Because of the screen size, the display isn’t the same according the device
(tablet or smartphone). Les functionalities are the same.
Smartphone display
Tablet display
Connection to an actuator
Status
The status screen shows all actuator parameters in real time.
Functionalities
Control activation
The functionalities described from this section allow the actuator control.
Therefore, the actuator password is required (default password: pwd or User
for actuators .GBH).
Functioning modes
Mode « Bluetooth® control » :
This mode is activated using these functions:
This mode allows a local control (on-off) of the actuator.
Mode « Positioning » :
This mode is activated using these functions:
This mode allows a local control of the actuator with percentage of opening. This mode also gives priority to electric wiring on terminals 15/16 (setpoint) and 13/14 (feedback)
Mode « Wired control » :
This mode is activated using this function:
This mode gives priority to electric wiring on power supply terminals (1, 2, 3 and 4).
Mode « Weekly scheduling » :
This mode is activated using this function:
This mode gives priority to stored tasks of the scheduler. Each functioning mode activation deactivates the other ones. Before exiting AXMART, It’s mandatory selecting the mode corresponding to the desired use of the actuator.
Local control
AXMART allows to locally manipulate the actuator.
Basic control:
Control with percentage of opening (positioning):
Each functioning mode activation deactivates the other ones. Before exiting
AXMART, It’s mandatory selecting the mode corresponding to the desired use of
the actuator.
Weekly scheduling
With AXMART, it’s possible to automate and making standalone the actuators,
using a weekly scheduler (capacity of 20 tasks).
Each functioning mode activation deactivates the other ones. Before exiting AXMART, It’s mandatory selecting the mode corresponding to the desired use of the actuator.
Task scheduling:
Example:
Each functioning mode activation deactivates the other ones. Before exiting AXMART, It’s mandatory selecting the mode corresponding to the desired use of the actuator.
Sharing and sending status report
The icon allows sending a complete report including all actuator parameters
and using the communication functions available on the device (Bluetooth®,
Wifi direct, cloud, Email…)
Report content (available in English only):
Actuator VS150 GPS -4 (88:6b:0f:8f:89:fd)
Generated on: 11/12/2019 – 12:04:50
State
Property | Value |
---|---|
Name | VS150 GPS -4 |
Address | 88:6b:0f:8f:89:fd (NB when generated on iOS, MAC addresses ends |
by XX:XX:XX)
Status mode| OK
Temperature| 45°C
Temperature Min| -9°C
Temperature Max| 64°C
Cycle counter| 2504
Working time| 06h 36m 21s
Fault counter| 245
EEPROM error counter| 0
Current mode| Prog.
Password| 12FEC69B94
Charging level| Charged
Battery status| Available
Nb power fail| 242
Nb torque fault| 220
Nb temperature fault| 25
Actuator position| 0%
Start ramp| 0
Torque limit| 80
Torque delay| 1
Gear unlock| 0
Temp regulation| 10
Temp security| 70
Fail safe position| CLOSED
Pilotage wired| 0
SetPoint sensor point| 2
SetPoint sensor direction| RISING
Feedback sensor point| 2
Feedback sensor direction| RISING
Type| GPS
Rotation direction| INVERTED
Tasks
| SlotId| Duration| Time| Command| Position
0| 10:00| 16h10| Ouvrir| Fermeture
Mon| Tue| Wed| Thu| Fri| Sat| Sun
TRUE| TRUE| FALSE| FALSE| TRUE| TRUE| TRUE
User picture| | |
Actuator setup
Clicking on setting button icon gives access to setup screen.
Modification of the actuator name
Type in the field « Name » the new name of the actuator (12 characters
maximum).
Modification of the actuator password
for obvious safety reasons , the password must be modified at the first use of
the actuator. Type the new password in the field « Password». The icon shows
the characters.
8 characters maximum. Available characters: a-z, A-Z, 0-9 only.
Wiring setup
Concerns the control with the actuator electric wiring.
- 4-wires: specific wiring with all terminals of the power supply terminal block or for pulse control wiring.
- Standard: for all other wiring including positioning.
Positioning setup
The setpoint signal (terminals 15/16) is the actuator positioning signal. The
feedback signal gives the actuator position (terminals 13/14).
-
0-10 V : Setpoint or feedback with voltage range
0 V = 0° ; 10 V = 90° -
4-20 mA : Setpoint or feedback with intensity range
4 mA = 0° ; 20 mA = 90° -
Normal : Correspondence signal/position as descripted above
-
Inverted : Inverted voltage/intensity ranges
10 V = 0° ; 0 V = 90° and 20 mA = 0° ; 4 mA = 90°
FAILSAFE safety position setup
The FAILSAFE system insure that the actuator will reach a predetermined safety
position in case of power failure.
- Open : The valve reaches open position in case of power failure.
- Closed: The valve reaches closed position in case of power failure (default).
- Inactive : The FAILSAFE unit is disabled (example : maintenance…)
Read User Manual Online (PDF format)