valpes DSBA3304 AXMART Doc Technique User Manual

June 6, 2024
Valpes

valpes DSBA3304 AXMART Doc Technique

Download and install

The AXMART® software is free and available on Google Play for Android version (v5.0 or higher) and on Apple store for the Apple version.
Software name: AXMART (v3)

Android versionvalpes DSBA3304 AXMART Doc Technique fig
1

Access requested by AXMART :

  • Access to position
  • Access to gallery/photos

Apple versionvalpes DSBA3304 AXMART Doc Technique fig
2

  • Before launching AXMART , the device clock must be correct.
  • During the switch between winter and summer time, a connection to the actuators is imperative for clocks synchronisation.

General description
Because of the screen size, the display isn’t the same according the device (tablet or smartphone). Les functionalities are the same.

Smartphone displayvalpes DSBA3304 AXMART Doc Technique fig
3

valpes DSBA3304 AXMART Doc Technique fig 4

Tablet displayvalpes DSBA3304 AXMART Doc Technique fig
5valpes DSBA3304 AXMART Doc Technique fig
6

Connection to an actuatorvalpes DSBA3304 AXMART Doc Technique fig
7

Status
The status screen shows all actuator parameters in real time.

valpes DSBA3304 AXMART Doc Technique fig 8

Functionalities

Control activation
The functionalities described from this section allow the actuator control. Therefore, the actuator password is required (default password: pwd or User for actuators .GBH).valpes DSBA3304 AXMART Doc Technique fig
9

Functioning modes

Mode « Bluetooth® control » :
This mode is activated using these functions:valpes DSBA3304 AXMART Doc
Technique fig 10

This mode allows a local control (on-off) of the actuator.

Mode « Positioning » :
This mode is activated using these functions:valpes DSBA3304 AXMART Doc
Technique fig 11

This mode allows a local control of the actuator with percentage of opening. This mode also gives priority to electric wiring on terminals 15/16 (setpoint) and 13/14 (feedback)

Mode « Wired control » :
This mode is activated using this function:valpes DSBA3304 AXMART Doc
Technique fig 12

This mode gives priority to electric wiring on power supply terminals (1, 2, 3 and 4).

Mode « Weekly scheduling » :
This mode is activated using this function:valpes DSBA3304 AXMART Doc
Technique fig 13

This mode gives priority to stored tasks of the scheduler. Each functioning mode activation deactivates the other ones. Before exiting AXMART, It’s mandatory selecting the mode corresponding to the desired use of the actuator.

Local control
AXMART allows to locally manipulate the actuator.

Basic control:valpes DSBA3304 AXMART Doc Technique fig
14

Control with percentage of opening (positioning):valpes DSBA3304 AXMART
Doc Technique fig 15
Each functioning mode activation deactivates the other ones. Before exiting AXMART, It’s mandatory selecting the mode corresponding to the desired use of the actuator.

Weekly scheduling
With AXMART, it’s possible to automate and making standalone the actuators, using a weekly scheduler (capacity of 20 tasks).valpes DSBA3304 AXMART Doc
Technique fig 16

Each functioning mode activation deactivates the other ones. Before exiting AXMART, It’s mandatory selecting the mode corresponding to the desired use of the actuator.

Task scheduling:valpes DSBA3304 AXMART Doc Technique fig
17

Example:valpes DSBA3304 AXMART Doc Technique fig 18

Each functioning mode activation deactivates the other ones. Before exiting AXMART, It’s mandatory selecting the mode corresponding to the desired use of the actuator.

Sharing and sending status report
The icon allows sending a complete report including all actuator parameters and using the communication functions available on the device (Bluetooth®, Wifi direct, cloud, Email…)

Report content (available in English only):
Actuator VS150 GPS -4 (88:6b:0f:8f:89:fd)
Generated on: 11/12/2019 – 12:04:50

State

Property Value
Name VS150 GPS -4
Address 88:6b:0f:8f:89:fd (NB when generated on iOS, MAC addresses ends

by XX:XX:XX)
Status mode| OK
Temperature| 45°C
Temperature Min| -9°C
Temperature Max| 64°C
Cycle counter| 2504
Working time| 06h 36m 21s
Fault counter| 245
EEPROM error counter| 0
Current mode| Prog.
Password| 12FEC69B94
Charging level| Charged
Battery status| Available
Nb power fail| 242
Nb torque fault| 220
Nb temperature fault| 25
Actuator position| 0%
Start ramp| 0
Torque limit| 80
Torque delay| 1
Gear unlock| 0
Temp regulation| 10
Temp security| 70
Fail safe position| CLOSED
Pilotage wired| 0
SetPoint sensor point| 2
SetPoint sensor direction| RISING
Feedback sensor point| 2
Feedback sensor direction| RISING
Type| GPS
Rotation direction| INVERTED

Tasks

| SlotId| Duration| Time| Command| Position
0| 10:00| 16h10| Ouvrir| Fermeture
Mon| Tue| Wed| Thu| Fri| Sat| Sun
TRUE| TRUE| FALSE| FALSE| TRUE| TRUE| TRUE
User picture|  | |

Actuator setup

Clicking on setting button icon gives access to setup screen.

Modification of the actuator name
Type in the field « Name » the new name of the actuator (12 characters maximum).valpes DSBA3304 AXMART Doc Technique fig 20

Modification of the actuator password
for obvious safety reasons , the password must be modified at the first use of the actuator. Type the new password in the field « Password». The icon shows the characters.
8 characters maximum. Available characters: a-z, A-Z, 0-9 only.

Wiring setup
Concerns the control with the actuator electric wiring.

  • 4-wires: specific wiring with all terminals of the power supply terminal block or for pulse control wiring.
  • Standard: for all other wiring including positioning.

Positioning setup
The setpoint signal (terminals 15/16) is the actuator positioning signal. The feedback signal gives the actuator position (terminals 13/14).

  • 0-10 V : Setpoint or feedback with voltage range
    0 V = 0° ; 10 V = 90°

  • 4-20 mA : Setpoint or feedback with intensity range
    4 mA = 0° ; 20 mA = 90°

  • Normal : Correspondence signal/position as descripted above

  • Inverted : Inverted voltage/intensity ranges
    10 V = 0° ; 0 V = 90° and 20 mA = 0° ; 4 mA = 90°

FAILSAFE safety position setup
The FAILSAFE system insure that the actuator will reach a predetermined safety position in case of power failure.

  • Open : The valve reaches open position in case of power failure.
  • Closed: The valve reaches closed position in case of power failure (default).
  • Inactive : The FAILSAFE unit is disabled (example : maintenance…)