5800CMBOVC
Combination Smoke/Carbon Monoxide (CO) Detector
Quick Installation Guide
This device is intended for use with Resideo control panels that support 5800
series devices including the 5800CMBOVC. Check the control for compatibility
with this device. This device occupies 3 control panel zones, one zone for
each service (smoke detection, heat detection, carbon monoxide detection).
NOTE: This device must be installed by a qualified technician.
FEATURES
-
Multi-Criteria Sensing: uses three sensing elements to react faster while minimizing false alarms:
– Photoelectric smoke sensor detects airborne smoke particles
– Carbon Monoxide (CO) sensor detects CO concentrations
– Thermal detection monitors for a dangerous rises in temperature -
CO Detector End-of-Life reporting (detector needs replacing)
-
Smoke detector maintenance reporting (detector needs cleaning or replacing)
-
Low Battery Detection
-
Low temperature sensing: senses ambient temperature and reports if temperature drops below 41° F (5°C)
-
Voice announcements (English or French)
-
Supervision: The detector will transmit its status every 60 to 70 minutes.
See Installation Instructions (R800-26685-1) –
www.resideo.com and the Limitations of Fire Alarm
Systems
Insert (800-15144), System Smoke Detectors Guide (RD-GS101-39-001; ST-QP-
RD-001-039/10Y), and
Limitations of Carbon Monoxide Detectors (P/N K14670V1).
LED INDICATORS
The 5800CMBOVC Smoke/CO detector features a multi-color top LED:
Green = Supervisory indication; blinks during power on, reset, and during
normal operation
Amber = Signal maintenance and trouble events
Red = Alarm condition (Smoke, CO, or Heat)
Side LED windows indicate alarms:
Red = Smoke or Heat alarm
Blue = CO alarm
The carbon monoxide alarming circuit of this device is designed to detect
carbon monoxide gas from ANY source of combustion. The carbon monoxide
alarming circuit of this device is NOT designed to detect smoke, fire, or any
other gases.
WARNING: This product is intended for use in ordinary indoor residential
areas. It is not designed to measure compliance with commercial and industrial
standards
POWER UP and LANGUAGE SELECTION
- Remove the battery pull tab. Be sure batteries are seated properly to avoid a low battery condition after15 seconds.
- Upon power up, Green LED Blinks every 2 seconds / Sounder is Silent. After power up, the detector prompts for language selection.
- Select the desired language.
English: Press the Smoke (•) test button
ENROLLMENT
IMPORTANT NOTE: The Smoke and Carbon Monoxide (CO) sensors each have
unique serial numbers that are enrolled in separate zones.
Enroll the Smoke Sensor
-
Remove the detector from the base plate (tamper switch must be faulted when enrolling).
-
Put the control panel in Zone Programming mode.
-
Assign a zone number for the smoke detector zone. Loop = 1; Zone Type = 09 (Fire) or 16 (Fire
with Verification); Input Type = 03 (Supervised RF)
When prompted for the serial number, press and release the Smoke Test button for 1 second. The sensor sends two transmissions for enrollment. Alternatively, you can manually enter the smoke
sensor serial number found on the unit’s label. -
If Maintenance monitoring is desired:
VISTA-15P/20P/21iP, LYNX Touch, & Lyric:
Assign a separate zone number using the Smoke Detector serial number. Loop = 2; (maintenance); Zone Type = choose a zone type based on the desired operation (ex.24hr Trouble, Monitor, or Auxiliary); Input Type = 03 (Supervised RF)
VISTA-128/250 Series: Enable the “Smart Contact” option in the zone programming menu for the assigned smoke detector zone. -
If Low-Temperature monitoring is desired, program a separate zone for the smoke detector serial number. Loop = 3; Zone Type = choose a zone type based on desired operation (ex.24hr Trouble, Monitor, or Auxiliary); Input Type = 03 (Supervised RF).
WARNING: The fire protection zone must always be enrolled as Loop 1. Otherwise, fire alarms will not be reported by the control.
Enroll the CO Sensor
- Remove the detector from the base plate.
- With the control panel in Zone Programming mode, assign a zone number for the CO detector zone. Loop = 1; Zone Type =14 (CO alarm); Input Type = 03 (Supervised RF) When prompted for the serial number, press and release the CO Test button for 1 second. The sensor sends two transmissions for enrollment. Alternatively, you can manually enter the CO sensor serial number, which is the smoke serial number plus 1 (ex. if smoke s/n is 0000781, the CO s/n is 0000782).
- If End-of-Life monitoring is desired:
VISTA-15P/20P/21iP, LYNX Touch, & Lyric: automatically sent
VISTA-128/250 Series: program a separate zone for the CO serial number.
Loop = 2; Zone Type = choose a zone type based on desired operation (ex.24 hr Trouble or Auxiliary); Input Type = 03 (Supervised RF).
TO SILENCE THE DETECTOR
Press the test switch. The detector sounds again after 5 minutes if the alarm
condition continues.
Note: The detector cannot be silenced if the smoke concentration exceeds
4ft% or the CO concentration exceeds 350 ppm.
MOUNTING
After enrolling and before mounting permanently, conduct a Go/No Go test
(refer to the control panel instructions) to verify adequate signal strength
with the device in its intended mounting location. Adjust the device location
and orientation as necessary. Adjust the device location and orientation as
necessary. Refer to Installation Guide (R800-26685-1) for full mounting
instructions.
NOTE: This device should not be located within 5 ft (1.5 m) of any
cooking appliance.
RESETTING THE LANGUAGE
- Press and hold both the Smoke (•) and CO (••) Test buttons simultaneously for 5 seconds until language message is announced, then release. The green LED flashes rapidly.
- Press the Test button corresponding to the desired language:
English: Smoke (•) test button
Operation Modes
MODE| Status LED (Top)| LED Windows (Side)| Sounder|
Speaker
---|---|---|---|---
First Power Up| Blink Green once| Dark| Silent| Voice welcome, instructions,
and language selection prompt
Power Up (except first power-up)| Blink Green once| Dark| Silent| Silent
Normal (Standby)| | Dark| Silent| Silent
Smoke Alarm| Blink Red every second| Blink Red| Temp-3| “Warning, smoke,
evacuate”
Heat Alarm| Blink Red every 10 seconds| Blink Red| Temp-3| “Warning, smoke,
evacuate”
CO Alarm| Blink Red every 10 seconds| Blink Blue| Temp-4| “Warning, carbon
monoxide, move to fresh air”
Smoke Alarm or Heat Alarm Silence| Blink Red every 8 seconds| Blink Red|
Silent| “Smoke alarm hush for 5 minutes”
CO Alarm Silence| Blink Red every 8 seconds| Blink Blue| Silent| “CO alarm
hush for 5 minutes”
FUNCTIONAL TESTING
CANNED SMOKE NOTE : Detector sounds an alarm when using canned smoke only
when in Functional Test mode (canned smoke does not cause alarm sounding when
in normal mode).
Product must be tested at least once each year
- Use UL/ANSI Approved canned smoke.
PERIODIC CLEANING
NOTE: Notify the proper authorities that the smoke detector is undergoing maintenance and the system will temporarily be out of service.
BATTERY REPLACEMENT
Caution: The batteries used in this device may present a fire or chemical
burn hazard if mistreated. Do not recharge, disassemble, heat above 212°F
(100°C) or dispose of it in a fire. Use only Panasonic CR123A Lithium
batteries. Use of other batteries may present a risk of fire or explosion.
Keep used batteries away from children. Dispose of used batteries properly.
Remove old batteries. Wait 10 seconds and then replace with four new
batteries. To avoid a low battery indication when installing new batteries,
all 4 batteries must be installed within 15 seconds of installing the first
one. Any low battery condition that may have occurred should clear when the
backplate is installed.
NOTE: Constant exposure to high or low temperature or high humidity may
reduce battery life.
LED Indication & Sounder During Test and Trouble
MODE| Status LED (Top)| Side LED
Windows| Sounder| Speaker
---|---|---|---|---
Smoke AlarmTest lab| Blink Red during alarm| Dark| Temp-3 (two times)| Test
mode announcement
Functional SMOKE Testlab — Waiting for canned smoke entry| Blink Green once
every second| Dark| Silent| Voice instructions and warning of alarm signal
Functional SMOKE Test – Successful smoke entry| Blink Red every 10 seconds|
Blink Red| Temp-3| Voice smoke warning
CO Test ‘3°| Blink Red during alarm| Dark| Temp-4 (two times)| Test mode
announcement
Functional CO Test lab — Waiting for gas entry| Blink Green once every second|
Dark| Silent| Voice instructions and warning of alarm signal
Functional CO Test- Successful gas entry| Blink Red every 10 seconds| Blink
Blue every 10 secs| Temp-4| “Warning, carbon monoxide, move to fresh air”
Low Battery| Blink Amber every 45 seconds| Dark| Chirp every 45 seconds after
7 days| Silent
Smoke Maintenance 3| Blink Amber every 4 seconds| Dark| Silent| Voice smoke
maintenance instructions when either test button is pressed
CO Trouble| Double Blink Amber every 8 seconds| Dark| Silent| Voice CO sensor
failure (if CO Test button pressed)
CO End of Life2– First 29 days| Double Blink Amber every 4 seconds| Dark|
Silent| Voice end of life instructions when either test button is pressed
CO End of Life2– After 30 days| Double Blink Amber every 4 seconds| Dark|
Chirp every 45 seconds| Voice end of life instructions when either test button
is pressed
Freeze Waming (low temp)| Blink Red every 8 seconds| Dark| Silent| Silent
1a Test activated by pressing and releasing the test switch; Detector is
functioning properly (within proper sensitivity). See Functional Test section
for Functional Test activation and procedure.
1b If Test mode is activated and the LED and Sounder do not function, check
for maintenance or trouble conditions.
2 Starts chirping after 30 days, continues until the batteries are replaced or
die
3 See Periodic Cleaning section. If maintenance trouble condition persists,
the detector may need to be replaced.
SPECIFICATIONS
Battery ………… 4 x 3V, CR123A Lithium; Panasonic CR123A only
Sensitivity ……………….. UL limits 0.9 to 3.50%/ft ; ULC limits 0.9 to 3.08%/ft
Heat alarm ……………………….. 57° C (135° F)
Freeze trouble ………….. 5° C (41° F)
Audible Signal…………………………. 85 dBA
Dimensions: …………………..157mm (6.2 in) Diameter
Weight ………………….. 14.3 oz; 406 g / 14,3 oz; 406 g
Tamper …………. Cover
Operating Temperature ……………………. 0° à 38° C / 32° to 100° F
Storage Temperature ………. -10° à 70° C / 14 to 158° F
Relative Humidity ……………………….. 95% max, non-condensing