TECHview LA-5351 RFID Access Card Reader
DESCRIPTION AND FEATURES
Description
RFID Access Card Reader is fully waterproof standalone Proximity access
control. It adopts the advanced MCU and large capacity Flash from Atmel,
supporting up to 10000 cards. It is easy to add or delete card users by
infrared remote keypad and master cards. It has the interfaces for external
alarm, door contact, and exit button. They also have the functions of
antipassback.
Features
Feature | Description |
---|---|
Card Type | EM&HIDcard |
IP Grade | IP65 |
Anti strong magnetism to open illegally | Field Effect Transistor control door |
Large capacity | 10,000 card users |
Wiegand input/output | Wiegand 26. Can work as controller or reader |
Anti passback | One door or two doors anti passback |
Block enrollment | Gan add 10,000 card users whose series number next to each |
other
INSTALLATION AND WIRE INSTRUCTION
installation
- Drill holes on the wall or prepare the cassette
- Wire through the hole, and blanket the unused cable in case of short circuit
- Fix the back cover firmly on the cassette or the wall
- Attach the machine to the back cover
Features
Connection Diagram
There have 2 types of electronic lock in market, Factory default setting are
Type B electronic lock, The lock time is 5 seconds.
- Type A electronic lock: Fail Secure lock (Unlock when power on), such as Electronic Controlling lock
- Type B electronic lock: Fail safe lock(Unlock when power off), such as EM lock, Electronic Bolt Lock, etc
Note: Do not power on until all wiring has been completed
TO RESET TO FACTORY DEFAULT
Power off, use the supplied Contact Pin to short out the 2P socket on the main
board, then power on, if successful, the beeper will beep twice, the LED
shines in orange, remove the Short Pin, then read the Two Manager cards
(Manager add card firstly, Manager delete card secondly),after that the LED
turns in red, means reset to factory default setting successfully.
Remarks: Reset to factory default setting, the users’ information enrolled is
still retained. When re-set to Factory setting, the two Manager cards must be
re-enrolled.
USE MANAGER CARD
To add user by Manager Card
Read Manager add card Read user card Read Manager card
Quit add user mode
To delete user by Manager card
Read Manager delete card Read user card Read Manager card
Quit add user mode
Note: Users can be added or deleted continuously
MASTER OPERATION ( BY REMOTE CONTROL)
Enter the programming mode
·008888# .888888 is the default factory master code
Note. tho following operation with “5” We must enter into programming mode ii
moans confirm, I ast ii moans omi current setting situation,,. means quit
Change the master code
Code must be 6-8 digits numbers.
To change the master code again, the master user must be logged in and key ‘0’
‘New code’ # ‘New code’ #.
Add user
- To read card continuously – 1 read user card #
- To input card number continuously – 1 8 digit card number II
- To add series card number –
8 8digits card number II card quantity II
Card quantity is between 1-9999 It takes 45minutes to add 9999 cards.
During the time, the green light blinks
Delete user
- Delete card by reading continuously 2 read card II
- Doloto card by inputting card number continuously 2 Bdigits card number #
- Delete all 2 0000#
This option will delete all users but manager cards. Be careful when using.
Anti-paaaback aetting
- Anti-passback disabled (Factory default) 30 #
- Anti-passback master mode 3U
- Anli-passback Auxiliary mode 3 2 #
Note: 7710 detailed wiring diagram and illustration, please rotor to the “Advanced application”
Lock power setting
- Fail secure (Unlocked when power on) 4 0-9911 is to set the door relay tirrn,.Os-5Oms
- Fail safe (Unlocked when power is off) 5 1-99
Door open detection
- To disable door open detection 6 O #
- To enable door open detection 6 1 #
When this function is enabled, there are two situations
- If the door is opened normally, but not closed after 1 minute, the inside buzzer will beep automatically to remind people to close the door. Close the door or read user card can stop the beep
- Push the door after it is opened in 120minutes by legal way; or the door is forced open, the external alarm system and Buzzer built-in controller will give alarm sound
Secure mode and LED light setting
-
Secure mode setting
-
Normal mode: 70#
No lockout or alarm, and it is factory default setting. -
Lockout mode: 71#
The machine will lockout for 10 minutes if we swipe 10 times invalid card in 10 minutes. -
Alarm mode: 72#
External alarm system and Buzzer built-in controller will give alarm sound in the same time when we swipe 10 times invalid card in 10 minutes. -
LED light setting
-
RED LED ON(factory default setting): 73#
-
RED LED OFF: 74#
Time of alarm setting
5.8 0-3#
Alarm time: 0-3 minutes, default setting is 1 minute
OPERATION OF OPENING THE DOOR
Open the door by swiping valid card.
DISALERT ALAM OPERATION
Three ways: swiping user card, manager card, input manager’s PIN.
SOUND AND LED LIGHT INDICATION
Operation Status | Colour of LED | Sound of Buzzer |
---|---|---|
Stand by Status | Slow RED flash | |
Press key of remote control | Bee-eep | |
Enter into programming | RED on | Bee-eep |
Enter into setting | ORANGE on | Beep |
Error | Beep, Beep, Beep | |
Open the door | GREEN | Bee-eep |
Alarm | Quick RED flash | Alarm Sound |
TECHNICAL PARAMETERS
Working Voltage | DC12V±10% |
---|---|
Stand by Cunent | <15mA |
Swiping Distance | 3-Bcm |
Operating Temperature | -40°C |
Operating Humidity | 0-95% RH |
Max Current of lock output load | 3A |
Max Current of alarm output load | 3A |
Manager card (EM card) | One add card, one delete card |
Dimension | 103 x 48 x 23mm |
PACKING LIST
Name | Quantity | Remark |
---|---|---|
Waterproof Reader | 1 | |
Infrared Remote Control | 1 | |
Manager Add Gard | 1 | |
Manager Delete Card | 1 | |
Short Pin | 1 | Used for factory default setting |
User Manual | 1 | |
SelfTapping Screws | 4/2 | 3.5(Dia.) x 27mm |
Please ensure that all the above contents are correct. If any are missing, Please notify the supplier.
ADVANCED APPLICATION
Operating as a Wiegand output reader.
Diagram of output reader and anti-pass back for single door.
Anti-passback function for single door (Set as function 5. 4.2)
The connection diagram is as figure 4. Install one Wiegand reader (without
user information as reader) outside the door, connecting to one Controller
inside the door, which acts as the Anti-passback Master unit of the two
devices, they build up an Anti-passback system for single door.
The operation function is as below:
Set the needed function and enroll the User Cards on the inside Antipassback Master unit.
With the valid user card, the user can only enter the door from the outside reader, and exit from the inside Controller. On the other hand, without entering record from the reader, the user can’t exit from the controller inside, also, the user can’t enter in twice without the first exit record , and vice versa.
Anti-passback function for 2 doors (Set as function 5.4.2)
The connection diagram is as Figure 5. Door 1 with one Card Reader, and Door 2
with one Card Reader, set one Card Reader on Door 1 as the Antipassback
Auxiliary unit, and set the other Card Reader on Door 2 as the Anti-passback
Master unit. They build up a two doors Antipassback system, which is normally
used for parking lot.. …. etc.
The operation function Is as below:
Set the needed function and enroll the User Cards from Anti-passback Master unit on Door 2.
With the valid user card, the user can only enter in from Door 1, and exit from Door 2. On the other hand, without entering record from the Auxiliary unit, the user can’t exit from the Master unit or Auxiliary unit , also, the user can, enter in twice without the first exit record , and vice versa
Colour | Function | Description |
---|---|---|
Green | DO | Wiegand output, input signal wire DO |
While | D1 | Wiegand output, input signal wire D1 |
Grey | Alarm+ | Connecting to the negative pole of the alarm equipment |
Yellow | OPEN | To connect to one part of Exit Button |
Brown | D_IN | Door Contact input |
Red | 12V | (+) 12Vdc Positive Regulated Power Input |
Black | GND | (-) Negative Regulated Power Input |
Blue | vss | The negative pole of the controller, connect to the other part of |
Exit button and door contact
Purple| L-| Connect to the negative pole of the Lock
Orange| L+/Alarm+| Connect to the positive pole of the lock and alarm
equipment
Distributed by:
TechBrands by Electus Distribution Ply. Ltd.
320 Victoria Rd, Rydalmere
NSW 2116 Australia
Ph: 1300 738 555
lnt’I: +61 2 8832 3200
Fax: 1300 738 500
www.techbrands.com
Made in China