MEASURING INSTRUMENT DAL-69N Non-Contact Type High Voltage Detector Instruction Manual

June 5, 2024
MEASURING INSTRUMENT

MEASURING INSTRUMENT DAL-69N Non-Contact Type High Voltage Detector
LOGO

MEASURING INSTRUMENT DAL-69N Non-Contact Type High Voltage Detector

MEASURING INSTRUMENT DAL-69N Non-Contact Type High Voltage Detector
PRO

Operation and Safety Notices

Instruction Manual
Thank you very much for the purchase of the audio-signaling and light emitting type voltage detector. For safety operation, please read this instruction manual carefully to use this product correctly. Keep this manual always on hand while using this product. Should you lose this manual, please contact us.
Safety Instructions
This instruction manual uses safety alert symbols to ensure safe operation by users. The instructions with these symbols alert you to important notices to prevent potential hazards or damages to you or other people. The instructions with the warning symbols are used to alert you to the following hazards. Please understand them well before reading the main text of this manual.

Warning

| | Operating this product incorrectly without following the messages with

this “Warning” symbol could result in death or serious injury.

---|---|---

Caution

|

| Operating this product incorrectly without following the messages with this “Caution” symbol could cause incorrect voltage detection.

Depending on situation, it may result in serious results. So be sure to

observe these messages.

Prohibition

| | This indicates that the operations with this symbol are “Prohibition”

items that must be strictly avoided.

Compulsory

| | This indicates that the operations with this symbol are “Compulsory”

items that must be followed without fail.

|      Warning
---|---
| 1. Before use, always make visual inspection & operation check and confirm if there is no abnormality. In addition, make operation check not only by test button but also by the

known power supply.

| 2. Use this voltage detector connected with long enough insulation rod (hot stick).

Do not use the detector alone to secure safety.

| 3. Prepare the insulation rod with length according to electric standard/regulation in each

country to be used.

| 4. Use the insulation rods with good quality FRP or having more sufficient insulation performance.

Do not use the self-making rod absolutely.

| 5.     Do not give strong shock to the instrument body and connection part with insulation rod.

6.   Make regular inspection for instrument body and insulation rod to maintain the safety. As to the regular inspection, apply the electric standard/regulation in each country to be used.

Do not use the instrument absolutely if you find any abnormality.

7.   Voltage detecting operation should be done definitely by electrical operation professionals belonging to power company and or consigned by power company in charge for inspection areas.

8.   Detection part has waterdrop-proof structure but do not use the instrument in rainy and thunder surroundings which will remarkably obstruct safety.

9.   The operation performance will get worse at high place. Confirm the circumstances at the place to be used and operate after making sure of safety.

10.    Before use, confirm if the detector & connection part and or the connection part & insulation rod are fixed very firmly. It may cause serious accident if the detector is dropping off during operation.

11.   Do not use the instrument in the way not specified in this manual.

|      Caution
---|---
| 1.   Do not apply the instrument body except for the use of voltage detector.

2.  As the operating temperature range is -10℃~+40℃, do not use this instrument at the temperature beyond this range.

| 3. Do not disassemble, modify or repair this product by yourself.
| 4. Equip the instrument with batteries before use, in case of new one.
| 5. Do not leave the instrument in the place with direct sunshine. It may cause

deterioration.

| 6. To prevent water penetration into the battery replacement part, use the instrument after

fastening it tightly.

| 7. In case that the soil and or dust are adhered on the surface of instrument and insulation

rod, use the instrument after washed and took off accretion completely.

| 8. In case that the moisture contents are adhered on the surface of the instrument, use

the instrument after wiped off clean.

| 9. Use pure water for washing and do not apply wastewater and or organic solvent like as thinner, benzene, etc. for cleaning.

After washing, dry the instrument in the shade of room, etc. where the direct sunshine

does not enter in.

| 11. It may cause failure, when twisting the range exchange switch by excessive force. As the switch does not turn to the back side, twist it within the movable range.

MEASURING INSTRUMENT DAL-69N Non-Contact Type High Voltage Detector
1

Description of Voltage Detector
This voltage detector is intended for use of AC circuit with less than 36kV and shall indicate the result of voltage detection in sound and light.

The Specification of Voltage Detector

T        y        p       e DAL-69N

Range of

operating voltage

| AC100V – 69,000V [L] AC100V~1,000V         [H] AC1,500V~690,00V

Voltage at the operation startup (Voltage to earth)

| Selector switch “L” Position: bare wire 100V

“H” Position: bare wire 1,500V

(Note) “L” and “H” stand for sensitivity range class, and the voltages shown above are the minimum detectable

voltages.

Operating

frequency

| 50Hz/60Hz (Common)
Representation

level

| Sound: 50dB or more (at the distance of 2m from sound port)

Light: to be visible at the luminance of 8,000lx.

Battery to be used| R3 or LR03(1.5V)×2 pieces
Range of operating

temperature

| -10℃ - +40℃
Weight| Approx. 190g (including battery)

Operation of Voltage Detector

Check before voltage detection

  1. Ensure that the appearance and structure are normal (no crack, break or chip is found in the detecting part or the pipe). Never use the instrument if something abnormal is found.

  2. Connect the voltage detector with insulation rod firmly.

  3. Set the selector switch to “L” or “H” position and confirm that the intermittent light-emission & beeping sound continue by pushing test button (Test Operation).
    Note : Set each range selection switch certainly until catching the click sound. If they don’t work or they work weakly, replace the battery with new ones. At “OFF” position of range selection switch, the instrument does not work even by pushing test button.

  4. Ensure the operation of this instrument with the known power supply, etc.

How to detect voltage

  1. For the voltage detection of low voltage circuit, set selector switch to “L”. By the way, voltage cannot be detected with coated wire.
  2. For the voltage detection of high voltage circuit (bare wire of 1.5kV or more), set selector switch to “H”.
  3. Hold the grip firmly and set the detecting element at the tip to the point where it surely contacts to the object of voltage detection.
  4. If the object of voltage detection is charged, the instrument produces intermittent sound and light.

How to replace a battery

  1. Fix the insulation rod and turn detecting part and remove it. The battery will then come out.
  2. Replace the batteries and be sure not to make a mistake in polarity of the battery (+/-: shown on the battery chamber).
  3. To confirm that the batteries are installed correctly, set the range switch at “L” or “H” and check the continuous intermittent sound & light-emission by test button.
  4. Fix the insulation rod and fasten the detecting part firmly. In case of insufficient fasten, the water may penetrate into the instrument body and also, the change of range switch may be unable correctly.

Caution at voltage detection

  1. This instrument sometimes operates when the hot line induces voltage in stop line as in the cases where both lines cross or run together and come close with each other.
  2. This instrument sometimes operates when you put the detecting element on the earth while the voltage detector is receiving induction voltage.
  3. Operation startup voltage may vary depending on the place where the instrument is affected by the voltage of other substance or depending on how voltage detector is put on the object.
  4. It is allowed to detect voltage of high voltage circuit (1.5kV or more) with the selector switch at “L” position but the instrument produces sound and light even when it just comes close to the object.

Repair, maintenance and management

  1. Keep the product in a dry place away from direct sunlight.
  2. When disposing of the product, treat it as an industrial waste.
  3. Dispose used batteries adequately according to the regulation in each country or district.
  4. Remove the battery when storing the product for long periods of time.
  5. Conduct periodic inspections as needed. (We accept orders for periodic inspections.)

(Note) The specifications of this voltage detector are subject to change without prior notice for further improvement of the product.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals