Honeywell TR21-WS Wireless Temperature Sensor Instruction Manual
- June 5, 2024
- Honeywell
Table of Contents
Honeywell TR21-WS Wireless Temperature Sensor
APPLICATION
The WRECVR receiver and TR21-WS, TR23-WS, TR21-WK, and TR23-WK are a family of wireless wall modules and receiver for use with:
- Spyder Unitary Controllers: PUL, PVL, etc.
- Excel 10 W7750, W7751, W7752, and W7753 controllers
- T7350, T7351, and TB8575 low-voltage SuitePRO™ thermostats
- Will not work with TB7220, TB8220 or TB line voltage thermostats, XL15s, W7762, W7763 or certain other XL controllers,
- Will work with WEBs-AX™ I/O Module products if using a separate transformer
- Compatibility with various other non-Honeywell controllers that accept 10K type2 NTC temperature inputs NOTE: Refer to the TR21 and TR23 Wall Modules Specification Data, form 63-1332, for specific model features and additional information.
Model No. | FCC/IC ID’s |
---|---|
TR21-WS |
FCC ID: HS9WLKFWM IC: 573R-WLKF
TR21-WK
TR23-WS
TR23-WK
TR21-WSU
TR23-WSU
WRECVR| FCC ID: HS9WLKFRV IC: 573R-WLKF
WRECVRU
FEATURES
- Wall module to Receiver (point to point) wireless kits can replace any standard wired sensor
- Wireless Kits (wall module and receiver) are pre-bound at the factory for quick installation
- Signal Strength LED built into the wall module
- Low battery indication
- Optional dip switches available to bind any wall module to any receiver
- Approximate 5-year battery life with AA Alkaline (included), 7.5 years with Lithium
- The locking screw discourages tampering and battery theft.
SPECIFICATIONS
Models: For specific model information, see Specification
Data, form 63-1332.
Environmental Ratings:
- Wall Module Operating Temperature: 45° to 99°F (7° to 37°C).
- Receiver Operating Temperature: -40° to 150°F (-40° to 65.5°C).
- Storage Temperature: -40° to 150°F (-40° to 65.5°C).
- Operating Humidity: 5% to 95% RH (non-condensing)
Accuracy: +/- 1ºF (+/- 0.5ºC) across 12ºC to 30ºC
Setpoint Range for TR23: 56° to 84°F (13° to 29°C) Accessories:
50007298-001 (pack of 12) medium, cover plate; 6-7/8 x 5 in. (175 x 127 mm).
Power:
- Receiver Voltage: 20 – 30VAC/DC, 50/60Hz; 24VAC typical
Housing:
- Wall Module: UL94-HB
- Receiver: UL94-5VA
Radio Frequency 2.4 GHz (IEEE Std 802.15.4-2003 compliant)
- Open Range: 3000 feet
- Typical Range: 100 feet
- Output power: 16dBm
- Receiver power consumption: <1.5 VA@24VAC
TR21-WS, TR23-WS, TR21-WK, TR23-WK, WRECVR
Approximate battery life under normal operating conditions:
- 5 years with two AA Alkaline batteries (included)
- 7.5 years with two AA Lithium Batteries
Transmission interval: 30 seconds
Pressing override button or signal strength button will force an immediate
transmission.
Approvals:
This device complies with Part 15 of the FCC rules. Operation is subject to
the following two conditions:
- this device may not cause harmful interference, and
- this device must accept any interference received, including interference that may cause undesired operation.
INSTALLATION
CAUTION
Erratic System Operation Hazard.
Failure to follow proper wiring practices can introduce disruptive electrical
interference (noise). Keep wiring at least one foot away from large inductive
loads such as motors line starters, lighting ballasts, and large power
distribution panels.
Shielded cable is required in installations where these guidelines cannot be
met.
Ground shield only to grounded controller case.
IMPORTANT
All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams.
- Receiver wiring can be sized from 16 to 22 AWG (1.31 to 0.33 sq. mm) depending on the application.
- The maximum length of wire from a device to a receiver is 100 ft. (30.5 m).
Mounting the Receiver
The receiver can be mounted on any surface using screws (No. 6 or No. 8) appropriate for the mounting surface. The receiver can also be mounted to the Spyder controller using the mounting slots and tabs (dovetails), and can be mounted to a DIN rail.
Mounting the Wall Module
Mount the wall module on an inside wall approximately 54 in. (1372 mm) from
the floor (or in the specified location) to allow exposure to the average zone
temperature. Do not mount the wall module on an outside wall, on a wall
containing water pipes, or near air ducts. Avoid locations that are exposed to
discharge air from registers or radiation from lights, appliances, or the sun.
When mounting to drywall, use the horizontal mounting screw locations, as
shown in Fig. 3
There is a locking screw option to prevent tampering and access to batteries. The screw is provided with the wall module, and screws into the slot shown in Fig. 9 after the device is snapped onto the subbase.
If desired, insert the two red end stoppers into the temperature scale to set
the desired temperature range limit. See Fig. 3.
For TR23 models, insert the desired dial through the opening in the cover.
Align the keyed shaft on the knob with the keyed slot into the fitting on the
subbase, then press down until it snaps into place.
WIRING
Attach the wires from the device terminals to the appropriate receiver
terminals..
CAUTION
Improper Electrical Contact Hazard.
Screw-type terminal blocks are designed to accept no more than one 16 AWG
(1.31 sq. mm) conductor.
Connect multiple wires that are 16-18 AWG
(1.31-0.82 sq. mm) with a wire nut. Include a pigtail with this wire group and
attach the pigtail to the individual terminal block.
Wire the terminal block as follows:
-
For single wires, strip 3/16 in. (5 mm); for multiple wires going into one terminal, strip 1/2 in. (13 mm) insulation from the conductor.
-
If two or more wires (18 to 22 AWG only) are being inserted into one terminal, twist the wires together before inserting.
NOTE: When two or more wires are being inserted into one terminal, be sure to twist them together. Deviation from this rule can result in improper electrical contact. See Fig. 4. -
Insert the wire in the required terminal location and tighten the screw to complete the termination.
-
Review and verify the terminal connection wiring and DIP switch settings.
STRIP 1/2 IN. (13 MM) FROM WIRES TO BE ATTACHED AT ONE TERMINAL TWIST WIRES TOGETHER WITH PLIERS (A MINIMUM OF THREE TURNS).
CUT TWISTED END OF WIRES TO 3/16 IN. (5 MM) BEFORE INSERTING INTO TERMINAL AND TIGHTENING SCREW. THEN PULL ON EACH WIRE IN ALL TERMINALS TO CHECK FOR GOOD MECHANICAL CONNECTION
Fig. 4. Attaching two wires (18 to 22 AWG) to receiver terminals
TR21-WS, TR23-WS, TR21-WK, TR23-WK, WRECVR
NOTE: WHEN USING THE WIRELESS TR23 SENSOR WITH THE T7350 BE SURE TO USE
THE RELATIVE SCALE SETPOINT KNOB.
NOTE: WHEN USING THE WIRELESS TR21 SENSOR WITH THE T7350, DO NOT WIRE
TERMINAL 5 AND TERMINAL 6.
DIP Switch Labels
This device is packed with tear-off DIP switch labels you can attach to the
receiver and indicate which DIP switches are on and off.
TESTING FOR SIGNAL STRENGTH
When the receiver is powered and batteries are placed in the wall module,
communication will begin automatically within 2 seconds. The receiver RF
signal light will flash every 30 seconds to confirm each transmission. You can
force immediate communication by pressing the signal strength button on the
side of the wall module with a 1-1.6 mm diameter probe with flat or rounded
face (a common paperclip will do) (see Fig. 9). This may be required to
initiate communication when replacing a wall module.
The signal strength LED next to the signal strength button will light up on
the side to show the relative signal strength. The signal strength LED will
initially light amber when the signal strength button is pressed to verify
that you are pressing the signal strength button. When you release the signal
strength button, the light will behave as shown in Table 1.
Table 1. Signal Strength LED.
LED | Signal Strength |
---|---|
Remains Green for 5 seconds | Strong |
Remains Amber for 5 seconds | Weaker (still acceptable) |
Amber blinks for 5 seconds | No signal |
If no signal is received, test the wall module in a different location until
suitable signal strength is received by the receiver. Pressing the signal
strength button on the wall module will cause a five-second flash on the RF
signal LED on the receiver, and pressing the override button will cause a
single flash on the receiver.
In normal operation, the sensor transmits to the receiver every 30 seconds. If
the receiver fails to receive a signal after 15 attempts (7.5 minutes), the
receiver will try to re-establish communication every minute for 8 consecutive
minutes. During this time (maximum 15.5 minutes) the receiver will continue to
output the last valid temperature value it received from the sensor. If there
is no valid signal received after 15.5 minutes, the receiver will simulate an
open circuit (like a cut wire on a wired sensor) and go into sleep mode.
Thereafter, every ten minutes, the receiver will try to re-establish the
signal.
BINDING THE WALL MODULE AND RECEIVER TO EACH OTHER
The TR21-WK and TR23-WK wireless kits include a wall module and receiver that
have already been bound in the factory to automatically communicate with each
other. They can be identified as matching by the identical bind numbers
printed on the labels. The S2 and S3 DIP switches on the receiver (used to
bind the two devices) and the 12 DIP switches on the wall module will all be
in the OFF position. As soon as power is applied to the receiver and the
batteries are installed in the wall module, the two devices start to talk to
each other. If the two devices don’t communicate immediately, remove and re-
install one battery, leaving it out for 10 seconds OR you can initiate
communication by pressing the signal strength button on the sensor (using a
paperclip).
Each wireless kit has a unique binding, so even though multiple wireless kits
have S2 and S3 switches all in the OFF position, each device will only
communicate to the device to which it was paired and shipped as a kit.
There may be times when you want to bind a receiver to a wall module using the
DIP switches. This is done simply by matching any S2/S3 DIP switch settings on
the receiver with the DIP switch settings on the wall module. Wall modules in
close proximity must have different DIP switch settings
(except when modules are using the all-OFF default binding).
DIP switches S2/S3 are provided for two reasons:
- If the wall module needs to be replaced, a TR21-WS or TR23-WS wall module can be purchased. To bind any wall module and receiver, simply set the DIP switches S2/S3 on both the receiver and the wall module to any matching DIP configuration. To prepare for this ahead of time, the receiver and wall module in the WK kit can be set with a matching dip switch configuration when mounted. The tear off tab on the receiver allows the installer to write down the on/off DIP configuration. Then the new wall module’s DIP switches can be set by matching the old wall module’s DIP switches, without having to set or check the DIP switches on the receiver.
- If wall modules and receivers get mixed up in the field
(even though they are marked with matching numbers from the factory), DIP switches can be used to bind any wall module to any receiver simply by matching the S2/S3 DIP switches. If setting DIP switches, be sure that each wireless sensor/receiver pair in a given building has a unique DIP switch setting to prevent cross-talk.
Fig. 8 shows matching DIP switch settings binding the wall module and receiver.
Controller Matching
The TR21 and TR23 wireless wall modules can be used with many different
controllers. The S1 switch on the receiver can be set for a number of
different controller requirements. See Table 2 for DIP switch settings, and
see Table 3 for a description of the controller.
Table 2. S1 DIP Switch Settings.
| ****
Controller
| S1 DIP Switches
---|---|---
1| 2| 3| 4| 5| 6
1.| Spyder/ComfortPoint 20Kohm, XL10| ON| OFF| OFF| OFF| OFF| OFF
2.| XL600, 500, 100, 80| OFF| ON| OFF| OFF| OFF| OFF
3.| 10K type 2, 3-wire| ON| ON| OFF| OFF| OFF| OFF
4.| 10K type 2, see I&I| OFF| OFF| ON| OFF| OFF| OFF
5.| 10K type 2, 4-wire| ON| OFF| ON| OFF| OFF| OFF
6.| 10K type 2, 3-wire| OFF| ON| ON| OFF| OFF| OFF
Table 3. Controller Descriptions.
Controller | Description | |
---|---|---|
1. | Spyder/ComfortPoint 20Kohm, XL 10 | Default setting. For use with Spyder |
and Comfort Point 20K ohm controllers For use with XL10 VAV, W7750, W7751,
etc.
2.| Honeywell Other| For use with XL600/500/100.
3.| 10K type 2| 10K ohm NTC type 2 output, 2K-3K ohm knob span:
• Common
• Temperature (Override button temporarily shorts the temperature output)
• Setpoint
4.| 10K type 2| 10K ohm NTC type 2 output, 1K -11K ohm knob span.
5.| 10K type 2| 10K ohm NTC type 2 output, 0-10K ohm knob span:
• 10K out
• Common (for temperature, override, and setpoint)
• Override
• Setpoint
6.| 10K type 2 (ComfortPoint 10K ohm controllers)| 10K ohm NTC type 2 output, 0-9500 ohm knob span:
• Common
• Temperature (Override button temporarily shorts the temperature output)
• Setpoint
Low Battery Signal
When there are approximately 2 months of battery life remaining, the LED on
the front of the wall module (next to the Override button) will flash red
every 15 seconds. In addition, the LOW BAT digital output from the receiver
will close. This LOW BAT output signal can be sent to an unused DI on the
controller to let the user know that there is a low battery condition. Replace
the batteries whenever the LOW BAT contact closes, or a flashing red light is
seen next to the Override LED on the face of the wall module. Normal operation
will automatically resume.
NOTE: If the batteries go dead, the LOW BAT digital output (open/close)
signal will open again. The LOW BAT digital output will close only when
batteries are running low, not when they are completely dead, or are not
installed. This ensures that a lack of signal is not confused with dead or
missing batteries. Whenever there is no signal, or batteries have gone
completely dead, the receiver LOW BAT output will send an open circuit reading
to the controller for temperature (and setpoint, if applicable).
Override Button
To save battery life, the override button LED will only light when the button
is pressed. It will not remain lit, as on standard wired TR23 and TR24 models.
Override will still be activated when the button is pressed. If used with the
XL10, pressing and briefly holding the override button will cause it to behave
like other standard wired TR23s. The LED will remain lit for 9 seconds max. to
confirm it has been pressed from 1-4 seconds.
REPLACING A WALL MODULE
When replacing a wall module, set the DIP switches the same as the wall module being replaced. If the previous wall module DIP switches are all set to OFF, it will be necessary to reset the S2 and S3 receiver dip switches to any configuration not being used by other receivers in the area, and then set the wall module DIP switches to the same setting. At least one of the 12 DIP switches must be set to the ON (up) position.
General Rules for Installing Wireless Wall Modules
Communication between the wall module and receiver can be influenced by a number of factors. The type and thickness of building materials and the way in which they are oriented in relation to the wall module and receiver will affect communication. Try to orient the wall module and receiver so that if they are separated by a wall(s), the direction of signal travel is as perpendicular to the wall(s) as possible. This reduces the effective wall thickness.
Do not place either the wall module or receiver inside metal cabinets or enclosures. Signal reliability can be diminished if the receiver is installed in metal fan coil units. Older buildings may have plaster and lathe walls with metal mesh that can significantly reduce signal strength.
When mounting the receiver on a metal duct, stronger communication is possible
if the wall module is on the same side of the duct so the signal doesn’t need
to travel through the metal duct.
Standard drywall (gypsum board) does not greatly affect signal strength.
Be aware that occasional signal dropouts may occur in any wireless installation, and the controller must be able to accomodate for sensor and setpoint outputs from the receiver that may occasionally go into a brief open circuit mode. Reduce as much as possible the amount of metal (ducts, file cabinets, etc.) between and around the sensor and the wall module.
For the most robust wireless link, install the wall module in locations with a
strong signal (Greenlight as described in Table 1). While the signal may
appear green at any given moment, movement of people, repositioning of
furniture or other structures (especially when made of metal), or the presence
of other strong radio signals may cause temporary and/or frequent functional
disruption of the wireless signal.
The TR21-WK and TR23-WK have been successfully employed in hundreds of
different locations and applications. However, because of the variability of
various environments, Honeywell cannot guarantee that these wireless kits will
work successfully in every application, even when green signal strength is
indicated on initial installation. Although no standalone diagnostics tools
are available for the TR wireless products, the self-diagnostics and LED
indicators on the wall module and receiver do provide a reliable indication of
signal strength at any given point in time.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>