ACI KW350-P1-D-S-SC Power Meters User Guide

June 5, 2024
ACI

ACI KW350-P1-D-S-SC Power Meters User Guide
ACI KW350-P1-D-S-SC Power Meters

Appearance and Dimension

Appearance and Dimension

Installation Method

Steps:

This product id DIN Railed mounted and fit on the standard 35mm rail.

  1. To install the meter on the rail insert the top of the rail into the groove on the back of the meter. Pull the metal clips back and slide the rail across the groove of the meter.
    Installation Method

  2. Use the metal clips to tighten the rail to complete installation.
    Installation Method

  3. Before mentioning this step, the steps needed to remove the seal/cover need to be mentioned .I.E Step 5 below should come first.\
    To attach seal/cover back onto the meter place the left side of the cover down onto meter and press down on the right side. When installed correctly you will hear a clicking sound. The steps to attach the other cover is opposite to the above step.
    Installation Method

  4. After inserting the cover, tighten the sealing screws and lay the seal.
    Installation Method

  5. To open the cover, remove the seal if applicable, unscrew the sealing screws and life the cover upwards to remove.
    Installation Method

Terminals

Terminals

Wiring Diagram

  • 3 phase 4 wire (3LN, 3CT)
    Wiring Diagram

  • 3 phase 3 wire (2LL, 3CT)
    Wiring Diagram
    Wiring Diagram

Settings Mode

Meter Setting

Press and release the “SET” key to enter settings mode, now the password is inquired with the first cursor flashing. You can change the number at the cursor by pressing the “SCROLL” key, and shift the cursor by pressing the “SET” key. When the cursor is moved to the rightmost position, press ‘SET” key to confirm the password input. The meter’s default password is 0000. After entering the settings mode, you can inquire settings by “SCROLL” key with the cursor not flashing, and make the cursor flashing by “SET” key , then you can change the settings. The settings could also be change through the PC software.

LCD Page Contents KW350
Addr Address S-01
bd Baud Rate S-02
Pr Parity S-03
Ct CT1 S-09
  CT2 S-10
Pt PT1 S-11
  PT2 S-12

In settings mode, scroll to the page 5-01 to set the communication address, the address can be any integer between 1 and 247. Setting method is as follows: Press “SET” key, the first cursor flashing, change the flashing number by “SCROLL”key and shift the cursor by “SET” key, when the cursor is moved to the rightmost location, press “SET” to confirm the communication address, now there is no cursor blinking.

The other settings are the same as the operation of address.

The communication baud rate can be set to 1200, 2400, 4800, 9600, 19200 or 38400.

The communication parity can be set to EVEN, ODD, NONE1 or NONE2.

Communication

KW350 meter communication uses RS485 interface and Modbus -RTU protocol. Wiring terminals are A, B, S. If master device does not support RS485 but only RS232, an adapter named RS232/RS485 needs to be used for connection. In practical alapplications, there are multiple topologies for RS485 network, such as Line, Star and Wye. In addition, the Display Module has an infrared port to support meter reading via infrared in the field.

Energy Pulse Output

Users can choose either energy pulse output or reactive energy pulse output. The energy pulse output function needs an external auxiliary power to supply.

Relay Output(RO)

Two modes available: control or alarm output. One module only supports one mode at a time.

Event Logging

The KW350 series also provides a system status self-testing feature. When crucial operations are implemented (such as programming, open/close the cover, clear the demand, clear the meter’s data etc), it immediately logs the event time and the event type.

Specifications

Voltage Input

Rated Voltage| 400Vac L-N 690Vac L-L
Input Impedance| 2MΩ/Phase
Measurement Frequency| 50/60Hz
Accuracy| 0.5%
Current Input|
---|---
Rated Current| 333mV (1A)
Start Current| 10mA
Accuracy| 0.5%
Power Supply

Working Power Supply| 100~415Vac,50/60Hz; 100~300Vdc
Power Consumption| <2W or 10VA
Pulse Output

Isolation Voltage| 2500Vac
Load Voltage| 0~250Vac
Load Current| 100mA(max)
Relay Output

Load Voltage| 250Vac 30Vdc
Max Load Current| 5A(Resistant Load)
Isolation Voltage| 2000Vac(1min)
Action Time| 10ms
Mechanical Life| 20 million times
Electrical Life| About 50,000 times(5A, 250Vac,Resistant Load)
Communication

RS485 Baud Rate| 1200~38400
Communication Protocol| ModBus-RTU
Infrared Communication| Non-contact infrared
Infrared Baud Rate| 1200
Environment

Working Temperature| -25~70°C
Storage Temperature| -40~85°C

Support

Automation Components, Inc.
2305 Pleasant View Road, Middleton WI
Phone: 1-888-967-5224
Web: www.workaci.com
Email: [email protected]
Document#2305E3201 Revision Date: Apr., 2021

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

ACI User Manuals

Related Manuals