Sensata ISOSLICE-5 8 Reconfigurable Digital Input Isoslice Unit User Manual
- June 3, 2024
- Sensata
Table of Contents
ISOSLICE-5
8 Reconfigurable Digital Input Isoslice Unit
User Manual
ISOSLICE-5 8 Reconfigurable Digital Input Isoslice Unit
ISOSLICE-5
This slice unit has 8 digital inputs.
The inputs can be configured to work in two different ways, depending on the
position of the links inside. It is possible to have some inputs configured as
volt-free contacts and the others configured as +24Vdc inputs.
Volt Free Contact
The Input terminal must be connected to the Common terminal to switch the
input “ON”.
The input links must be fitted in the higher positions like this:
+24V dc Input
+24V dc must be connected to the Input terminal, with the corresponding
Ground to the Common terminal, to switch the input “ON”.
The input links must be fitted in the lower positions like this:
It is possible to have some inputs configured as volt-free contacts and the
others configured as +24Vdc inputs.
The logic can be reversed if switch 1 of S1 is on, so the inputs are“OFF”
instead of “ON” when the circuits are completed as described earlier.
Links must be fitted in pairs as shown above to avoid the possibility of
shorting +24V dc directly to the ground.
Channel Number
The channel number is set up using the 12-way dipswitch.
If all switches are off, the channel number is 1 (invalid):
Address Switches| Action|
---|---|---
8| add 1
7| add 2
6| add 4
5| add 8
4| add 16
3| add 32
2| add 64
Switches
1 = On, 0 = Off
Channel| 2| 3| 4| 5| 6| 7| 8
1| 0| 0| 0| 0| 0| 0| 0
2| 0| 0| 0| 0| 0| 0| 1
3| 0| 0| 0| 0| 0| 1| 0
4| 0| 0| 0| 0| 0| 1| 1
5| 0| 0| 0| 0| 1| 0| 0
6| 0| 0| 0| 0| 1| 0| 1
7| 0| 0| 0| 0| 1| 1| 0
8| 0| 0| 0| 0| 1| 1| 1
9| 0| 0| 0| 1| 0| 0| 0
10| 0| 0| 0| 1| 0| 0| 1
11| 0| 0| 0| 1| 0| 1| 0
12| 0| 0| 0| 1| 0| 1| 1
13| 0| 0| 0| 1| 1| 0| 0
14| 0| 0| 0| 1| 1| 0| 1
15| 0| 0| 0| 1| 1| 1| 0
16| 0| 0| 0| 1| 1| 1| 1
Switch 1 can be used to reverse the on/off logic of all 8 inputs.
Connections
The digital inputs are wired as shown:
7. Digital Input 7
8. Digital Input 8
12. Common
5. Digital Input 5
6. Digital Input 6
11. Common
1. Digital Input 1
2. Digital Input 2
9. Common
3. Digital Input 3
4. Digital Input 4
10. Common
Whilst every effort has been taken to ensure the accuracy of this document, we
accept no responsibility for damage, injury, loss, or expense resulting from
errors or omissions, and reserve the right of amendment without notice.
This document may not be reproduced in any way without the prior written
permission of the company
AUG 2022
Sensata Technologies
220808
Documents / Resources
|
Sensata ISOSLICE-5 8 Reconfigurable Digital Input Isoslice
Unit
[pdf] User Manual
ISOSLICE-5 8 Reconfigurable Digital Input Isoslice Unit, ISOSLICE-5, 8
Reconfigurable Digital Input Isoslice Unit, Digital Input Isoslice Unit, Input
Isoslice Unit, Isoslice Unit
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>