Sensata ISOSLICE-4 4 Thermocouple Input Isoslice Unit User Manual
- June 3, 2024
- Sensata
Table of Contents
Sensata ISOSLICE-4 4 Thermocouple Input Isoslice Unit
4 Thermocouple Input Isoslice Unit
Whilst every effort has been taken to ensure the accuracy of this document, we accept no responsibility for damage, injury, loss, or expense resulting from errors or omissions, and reserve the right of amendment without notice. This document may not be reproduced in any way without the prior written permission of the company The ISOSLICE-4 unit has 4 thermocouple inputs. It can be configured to accept a variety of different thermocouple types and temperature ranges as shown in the table below. Switch 1 selects the thermocouple type for Inputs 1 & 2 and Switch 2 selects the thermocouple type for Inputs 3 & 4.
Input Type| Input Range °C| Switch 1 ON
Input 1
| Switch 1 ON
Input 2
| Switch 2 ON
Input 3
| Switch 2 ON
Input 4
---|---|---|---|---|---
Type K| 0 -1200| 4| 8| 4| 8
Type J| 0 -1200| 3,4| 7,8| 3,4| 7,8
Type N| 0 -1000| 2,4| 6,8| 2,4| 6,8
Type E| 0 -1000| 2,3,4| 6,7,8| 2,3,4| 6,7,8
Type R| 0 -1400| 1| 5| 1| 5
Type S| 0 -1400| 1,3| 5,7| 1,3| 5,7
Type B| 400 -1800| 1,2| 5,6| 1,2| 5,6
Type T| -200 – 400| 1,2,3| 5,6,7| 1,2,3| 5,6,7
Channel Number
The channel number is set up using the 8-way dipswitch shown in the diagram
below. If all switches are off, the channel number is 1 (invalid, indicated by
the led flashing red):
Switches Switches 1 = On, 0 = Off
Channel | 2 | 3 | 4 | 5 | 6 | 7 | 8 | Channel | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
1 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 9 | 0 | 0 | 0 | 1 | 0 | 0 | 0 |
2 | 0 | 0 | 0 | 0 | 0 | 0 | 1 | 10 | 0 | 0 | 0 | 1 | 0 | 0 | 1 |
3 | 0 | 0 | 0 | 0 | 0 | 1 | 0 | 11 | 0 | 0 | 0 | 1 | 0 | 1 | 0 |
4 | 0 | 0 | 0 | 0 | 0 | 1 | 1 | 12 | 0 | 0 | 0 | 1 | 0 | 1 | 1 |
5 | 0 | 0 | 0 | 0 | 1 | 0 | 0 | 13 | 0 | 0 | 0 | 1 | 1 | 0 | 0 |
6 | 0 | 0 | 0 | 0 | 1 | 0 | 1 | 14 | 0 | 0 | 0 | 1 | 1 | 0 | 1 |
7 | 0 | 0 | 0 | 0 | 1 | 1 | 0 | 15 | 0 | 0 | 0 | 1 | 1 | 1 | 0 |
8 | 0 | 0 | 0 | 0 | 1 | 1 | 1 | 16 | 0 | 0 | 0 | 1 | 1 | 1 | 1 |
Connections
- Input 4 +
- Input 4
- NC
- Input 3+
- Input 3
- NC
- Input 1+
- Input 1
- NC
- Input 2+
- Input 2
- NC
Calibration
The ISOSLICE 4 has been factory calibrated to the values in the table. User
calibration is not possible.