ALORAIR Storm Ultra Commercial Dehumidifier User Manual

June 5, 2024
Alorair

ALORAIR Storm Ultra Commercial Dehumidifier Introduction

Identification Congratulations on purchasing a Storm Pro / Storm Ultra dehumidifier! The Storm Pro / Storm Ultra comes with an extensive warranty plan. To ensure you are eligible, be sure to note the serial number and date of purchase. The serial number can be found on the data on the back of the unit.
Model Name: Storm Pro
Serial Number: Date of Purchase:
Customer Service
For additional questions concerning the operation fo your dehumidifier, please
Contact your installing contractor.
Contact AlorAir Solutions: 1-888-990-7469
sales@alorair.com

Features

  • Storm Pro:85 pints per day at AHAM
  • Storm Ultra:90 pints per day at AHAM
  • Only 58 dBA
  • Automatic Humidistat
  • Built-in Pump with Overflow Protection
  • Self Monitoring System
  • Eco-Friendly R410A Refrigerant
  • Easy Access to Internal Components
  • Auto Restart After a Power Outage.
  • The Unit can be Ducted on the Supply/Outlet, if Necessary
How Your Storm Dehumidifier Works

The Storm Pro dehumidifier /The Storm Ultra dehumidifier utilize its integral humidistat to monitor the conditioned space. Once conditions are outside the desired setpoint, the compressor energizes and air is drawn across an evaporator coil. The evaporator coil is cooler than the dew point of the air so water vapor will turn into liquid condensation. The air is reheated through the condenser coil and distributed back into the room.

Electrical Supply
WARNING Volts may cause serious injury from electric shock.
Power Supply:
Outlet Requirement:
Circuit Protector:
115V, 60 Hz AC Only 1Phase 3-Prong, GFI 15Amp TimeD elayF useo r Circuit Breaker

  1. Disconnect electrical power before servic3i.n gDo not use an extension cord
  2. Only plug unit into grounded electrical o4u.t lDeot not use a plug adapter

Installation

Place the Pro in your desired location. The inlet of the machine should be at least 8″ from any obstructions. If the unit has been transported in a horizontal position, allow it sit in an upright position for at least 30 minutes before operating.
WARNING
Do not use dehumidifiers in an environment where corrosive or high VOC materials are applied.

Unit Overview

Storm Pro Dehumidifier

ALORAIR Storm Ultra Commercial
Dehumidifier-1Storm Ultra Dehumidifier ALORAIR Storm
Ultra Commercial Dehumidifier-2

LCD Display Instructions

  1. When the machine is powered on but not working: (After power on, the buzzer makes a sound)

  2. Main interface display of dehumidification state: The following information is displayed when the machine is working: Refers to the working time, which is defined as the time from starting up to shutting down, including the defrost time during the period, and the standby time after the humidity. The submenu has a reset function. If not, the working time shall be accumulated.
    Total time 9999 hours, the largest cumulative to the largest automatically reset after restart, and display units for hours. (round off).

    • 000 LIFE HRS:
      Refers to the total working time, i.e. the total working time (hours), which is in hours. (Press the mode key + select the confirmation key, and the total working time will be cleaned after 3 seconds.)

    • IN/OUT 00℉ 00% 00 gr / lb:
      Indicates the temperature, humidity and moisture content of the air inlet and outlet {GPP – grain per pound (gr/lb)}.

    • Set 00%:
      Indicates set humidity. If the main interface does not operate for 10 minutes, the screen will go out.Press any key to wake up. Other icons light up or flicker when opened The total working time is the accumulation of each working time (hours) in hours. (Press the mode key + select to confirmation key, and the total working time will be cleaned after 3 seconds.

Dehumidification status submenu interface display

  • Device name displayed on the screen: You can change the device name on the APP application
  • “Indicates”:Do I need to clear out this time?”, press “>”if you need to clear. When the operation is completed, the working time of the main interface and the working time of this interface will be reset and started to be instant again. After accumulation (9999), clean up and round.
  • “Coil Temp 000℃ ”: Used to display the current temperature of the coil.When it is below zero, the “-” symbol is displayed in front. “-” is not required on zero
  • Wifi hotspot: Factory setting is “OFF”, press > to enable wifi hotspot and switch ON/OFF.The device can transmit data and receive APP commands. The icon flickers when connected on the main interface. After successful connection, the icon displays normally.
  • The power down time is adjusted according to”>” and the power down time increases from 3 to 20 minutes (3-5-10-15-20), which is the so-called stop time of the fan after shutdown, in order to better drain the water. Factory set for 3 minutes. (the other state of the fan is still 15 seconds.)
  • The screen displays when you press shut down: Indicates: the fan is closed after a few minutes, and the standby page UNIT OFF is displayed after the fan is closed.
  • “Temp Units ‘F/’C”: Used for temperature scale switching.Press the “>” button to switch ‘F/ ‘C, after switch symbol of corresponding parts is also “MOISTURE CONTENT UNITS”: It is used to switch the unit of GPP value with moisture content.
  • Press > to switch the LB or Kg, after switch symbol of corresponding parts is also changing. changing
  • “Humidistat Setpoint 00%”: Used for setting dehumidification mode humidity. Press “>” to set the humidity. The adjustment range of humidity setting is between 25 and 80%. Each key rises or falls 5%, which can be recycled. When the setting is completed, do not operate for 5 seconds and begin to take effect. (Otherwise, the compressor will be shut down immediately after it is below ambient humidity at the time of setting.) Humidity below 25 percents “CO” mode recyclable. The main interface displays the set parameters.

Main interface frosting status display

The machine will display this after defrost when running

  • When the machine is running normally, “Defrost SHUTDOWN IN 06:00” will occurs in the interface after defrosting. It’s defrost countdown use seconds as units. This screen displays only 3 seconds. Displays the previous interface and status after restoration. If it is the home screen, the frost icon will flash.
  • When the user is operating in the submenu, the machine is in the frosting state. At this point, the frosting interface displays 3 seconds, and returns to the submenu program in the background countdown. When the user returns to the main interface without any operation, the frosting state is displayed in the main interface in the way of icon flicker.

Compressor on waiting interface display

Compressor protection time not shown: “Compressor ready IN 03:00” indicates: That the interface will be displayed when the compression is in a protected state. (including power-on and shutdown, the humidity rises immediately after the arrival of LO HI, and the shutdown resumes immediately after the emergence of LO H/). Displays the countdown in seconds. If the above situation does not occur within 3 minutes, it is not shown.

Water Pump working interface display

Compressor protection time not shown: “Pump working countdown”: Indicates: No matter in which working state and interface, as long as the pump works, this interface appears and counts down to 28 seconds.However, the interface only displays the previous working status and interface after 3 seconds. For example, after 3 seconds, there is a drainage icon on the main interface and it will flash until the drainage is finished.

Interface display in case of failure

Machine running time fault display: Make fault judgment and take corresponding actions after starting up. Regardless of the state, the fault is executed first and the fault code is displayed on the interface. If there is a fault in the sub-menu operation, immediately return to this interface display fault (including defrosting state). (The fault is judged when the pump works, and the fault is displayed as usual, but the pump needs to complete the water pumping this time). Multiple faults can be displayed at the same time.

Description of fault display:

  • Humidity sensor fault: when the humidity sensor unit fault or signal can not be transmitted, the fault is judged to be E1. The machine is out of operation (power on again after troubleshooting). The pump button can operate.
  • Ambient temperature T<2: When the sensor continuously detects the ambient temperature of inlet air T=2 degrees for 600 seconds, the fault is judged to be LO and the whole machine is stopped. Other values, correspond to the temperature region operation. (recoverable). At this time, the interface cannot be operated. The pump button can be operated.
  • Ambient temperature T>45: When the sensor continuously detects the inlet air environment temperature T=45 degrees for 15 seconds, the fault is judged to be Hl and the whole machine is stopped. Other values, correspond to the temperature region operation. (recoverable). At this time, the interface cannot be operated. The pump button can be operated.
  • When the compressor is started, if the coil temperature value detected is greater than or equal to (ambient temperature -3 degrees) for 30 minutes continuously, it is judged to be fluorine deficient (except defrosting), E5 is displayed, and the machine cannot be stopped for operation (It needs to be powered up again after troubleshooting).
  • After the power is back on, the machine runs continuously for another 30 minutes for judgment. (The temperature probe is broken, the temperature needs to be minimal). The pump button can be operated. After the pump works for 28 seconds when the high water level is switched on, E4 fault is judged when the high water level switch is switched on for 3 consecutive seconds, and E4 fault is displayed. The machine stops and cannot be operated (The pump needs to be powered up again after troubleshooting). The pump can be operated.

Preparing the Unit for Use

Setup

  1. Position the machine so there is a minimum of 8″ clearance for the back and sides. or directly toa specific location for spot dry. If the compressor didn’t remain vertical during transportation, wait a minimum of 30 minutes before turning the unit on.
  2. The included drain line attaches to the unit via a quick connection fitting that is located on the base of the unit. The drain line should be routed to a suitable drain or outside. Since the unit has an integral drain pump, the drain line may go up vertically (no more than 15′) prior to reaching the final drain location.
  3. Firmly insert the power cord into the socket on back of the unit under the air outlet.
  4. Turn on the dehumidifer and use the control panel to set up the dehumidifier as desired.

Optional Duct Installation

Ducting of the unit allows you to condition an adjacent room or focus the discharge to a specific area. The diameter for the supply/discharge ducting is 6″.Flex or layflat ducting can be used for this purpose.ALORAIR Storm Ultra
Commercial Dehumidifier-18

Maintenance and Repair

Cleaning the Machine Body
Use a soft, damp cloth to clean the exterior parts of the unit. Do not use any soap or solvents.
Procedure for filter maintenance
The dust and obstacles on the fillter should be removed regularly. You may need to clean and replace the filter. Step:

  1. Unplug the unit.
  2. Remove the filter by sliding it upward from the bottom byhand to remove it.
  3. Check for dirt and build-up.
  4. For MERV-8 or Pre-filter, wash it in warm water or vacuum it. Do not use soap or cleaners. Al so, shakes it gently and ensure the filters are dry before reinserting it.

Accessing lnternal Components

Always unplug unit prior to performing any maintenance.

  1. Remove the bottom two screws on the front of the machine.
  2. Remove the upper two screws on the back of the machine.
  3. Take off the casing/Remove the outer shell of the machineALORAIR Storm Ultra Commercial Dehumidifier-25

Integral Pump Maintenance

NOTE: This pump requires routine maintenance that is not covered by your 1 year parts warranty. Only a defective pump will be repaired or replaced under the warranty. As with all pumps, preventative maintenance is necessary to prevent issues from dirt and slime that may accumulate in the drain system. This includes the drai pan, hose to the condensate pump, pump reservo ir, pump head, float assembly, and discharge tubin The pump 1s des1gned wi th quick connection construction, making it easy to access the pump and components for service and maintenance. To Remove Pump from Reservoir:

  1. Unplug the unit.
  2. Upen the back housing as shown on page l12.
  3. Remove the condensate tube from the pump.
  4. Use the quick connect fittings to disconnect the main power and float switch electrical cable
  5. Use a flathead screwdriver to gently pry the pump off the reservoir.

At least once per year, clean your pump system. Basic Pump Cleaning:

  1. Press the pump button (PURGE) to drain any water from the reservoir.

  2. Disconnect power to the dehumidifier.

  3. Mix a 16 oz cleaning solution of one of the following: I 0z bleach / 15 oz water or 4 oz white vinegar 12 oz water. Pour the solution into the drain tray at the base of the coils.
    NOTE: If you get any cleaning solution on the coils, flush with water

  4. Allow cleaning solution to soak for 15 minutes.

  5. Reconnect power to the dehumidifier.

  6. Pour clean water into the reservoir so the pump activates twice (about 16-32 0z. water).

  7. Repeat if needed or refer to Advanced instructions.

Advanced Pump Cleaning
  1. Use the manual pump button (PURGE) , to drain any water from the reservoir.

  2. Unplug the unit, and remove pump from reservoir (see page 13).

  3. Use a wet dry vac or paper towels to remove any rema in ing water from the pump reservoir.

  4. Fill the pump reservoir with a cleaning solution (15 oz water /1 oz bleach or 12 oz water /4 oz white vinegar).

  5. Reassemble the pump and use the manual pump button to flush the mixture through the discharge tubing.

  6. Mix another batch of cleaning solution then pour it slowly into drain pan under evaporator coil and allow it to clean the hose from pan to pump. This process can be stopped when the pump energ1zes I time.
    NOTE: If you get any bleachwater mixture on coils, flush with water.

  7. Pour sufficient clean water through the drain pan so that the pump activates twice (16-32 ounces).

  8. Reassemble the unit and return it to operational status.

Cleaning the Coils

The coils on your dehumidifier also need to be cleaned once per year. To clean, simply spray with a self-rinsing, foaming coil cleaner (such as WEB Coil Cleaner).

Storing Your Dehumidifier

If you plan on storing your dehumidifier for an extended period of time

  1. Turn unit off and allow to dry.
  2. Manually drain pump reservoir.
  3. Wrap and secure the power cord.
  4. Clem the filter.
  5. Store in clean, dry environment.

Troubleshooting

Symptom Cause Solution

Display is Blank

|

Poor Connection

| Verify that both ends of the Power cord are plugged in
Power Outage| Reset power

No Airflow

| Filter is Dirty| Clean the filter
Air lnlet or Outlet is Blocked| Clear the blockage

Error Code: E1

| Humidity Sensor or Communication Error| Check to ensure that the sensor wire is connected at both ends. if no issues are visible, the sensor may be faulty.

Error Code: E4

| Problem with Pump| Verify that the pump is properly installed and functioning. If so, unplug the unit for two minutes, then restart.

Error Code: LO

| Room Temperature is below 33.8o| Increase the room temperature so it is within operating range (above 33.8o     ). If error still displays, check sensor.

Error Code: HI

| Room Temperature is above 110 o| Decrease the room temperature so it is within operating range (below 110o     ). If error still displays, check the sensor.
E5 Error Code| Refrigerant Leak| Contact Your Installer for Assistance

If an E4 code appears on the display:

  1. Reset the unit by disconnecting the power cord and then reconnecting it.
    NOTE: The unit will not function until the code has been cleared.

  2. Manually check to see if pump is operational by pressing the drain button. Verify that the pump energizes and de-energizes properly. Additionally, check to see if any water purged from the system.

  3. If you haven’t cleaned the system recently, check the discharge line for an obstrution, then clean the balance of the pump system (see “Maintenance” section for details).

  4. Replace the hoses and/or pump, if maintenance alone isn’t sufficient.

Limited Warranty

This limited warranty starts from the date of purchase. Alorair Solutions Inc. warrants to the an original purchaser that this ALORAIR product is free from manufacturing defects in material or workmanship for the limited warranty period of: Six (6) Month parts and labor. This includes the shipments charges for replacement parts or unit. One (1) year parts and labor. This does not include the shipment charge to send the defective product back to be repaired or replaced. Three (3) years parts and labor on Refrigeration System ONLY (Compressor, Condenser, and evaporator). Transportation cost, not included Five (5) years parts on Refrigeration System ONLY(Compressor, Condenser, and evaporator).
Transportation cost, not included

This limited warranty is valid only on products purchased from the manufacturer or ALORAIR authorized dealer and operated, installed, and maintained according to the instructions included in this user guide or furnished with the product. Alorair Solutions Inc will not provide in-home service during or after the warranty period. You may be responsible for the shipping charge to bring the product to the manufacturer for service. To receive warranty service, the purchaser must contact ALORAIR at 888-990-7469 or support@alorair.com.

A proof of purchase or order number is required to receive warranty service. During the applicable warranty period, a product will be repaired or replaced at the sole option of ALORAIR.

Limited Warranty Exclusions

This limited warranty covers manufacturing defects in materials or workmanship encountered in normal household, commercial or noncommercial use of this product and shall not cover the following:

  • Damage occurs in uses for which this product was not intended for.
  • Damage caused by unauthorized modification or alteration of the product.
  • dosmetic damage including scratches, dents, chips, and other damage to the product’s finishes.
  • Damage caused by abuse, misuse, pest infestation, accident, fire, floods, or other acts of nature.
  • Damage caused by incorrect electrical line current, voltage, fluctuations, and surges.
  • Damage caused by failure to perform proper maintenance of the product.
    The use of this product in SPA or a room with an OUTDOOR POOL invalidate or voids limited warranty.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals