hager JKD166TM Invicta 3 TPN Board Glazed Instruction Manual
- June 5, 2024
- hager
Table of Contents
hager JKD166TM Invicta 3 TPN Board Glazed
All product(s) must be installed by a suitably competent electrician giving
consideration to their intended use and in accordance with the current edition
of BS 7671 (IET Wiring Regulations).
The Electricity at Work regulations and the Health and Safety at Work Act
shall be complied with.
Only equipment and arrangements specified in Hager’s technical documentation /
catalogue shall be used
Install in the vertical plane only.
Notice:
To prevent potential overheating from loose connections the installer shall
check connections are tightened to the torque levels stated in these
instructions prior to energising this board. This check should include factory
made connections which may have loosened in transit.
Setup instructions
Interface Characteristics
Rated & operational voltage (Un / Ue)
415V a.c. 50Hz
Rated insulation voltage (Ui)
690V a.c. 50Hz
Rated impulse withstand voltage (Uimp)
4kV
Rated current of the Assembly (In A )
JKD1xxTM 125A
Rated current of an Outgoing circuit (In C )
MCB 0.5A – 63A (marked rated current on device)
RCBO 6A – 45A (marked rated current on device)
Rated Current of Pan Assembly
Upper Pan Inc =125A Lower Pan Inc = 125A
Rated conditional short-circuit current of the ASSEMBLY (Icc) 10kA1 with equipment and arrangements specified in Hager’s technical documentation / catalogue.
MCB/RCBO 10kA rating applied as BS EN 61439-3 is intended for use by ordinary persons.
1Current limitation characteristics specified in Hager’s technical documentation / catalogue
Protection against electric shock
DBO shall be installed in an electrical system conforming to IEC 60364 / BS 7671
Rated diversity factor (RDF)
10 way – 24 way = 0.7
Note: RDF only applies to continuously and simultaneously loaded circuits.
Rated frequency ( f n)
50 Hz
Pollution degree
2
Types of system earthing for which the ASSEMBLY is designed TNC-S, TN-S
and TT when installed in an electrical system conforming to BS 7671
Intended locations
Indoor use only
Stationary ASSEMBLY
Degree of protection
IP3XD with Door Closed
IP2XC with Door Open and compliment of outgoing devices and or blanks fitted.
Intended use
Distribution boards intended to be operated by ordinary persons (DBO)
Electromagnetic compatibility (EMC) classification
EMC Environment B
External design
Wall-mounted, surface type, enclosed assembly.
Mechanical impact protection
IK05
The type of construction
Fixed parts
DBO Type
Type B DBO
Warranty
This distribution board is offered with a 24 month warranty against defective material or manufacture. If a warranty claim is necessary, please call the technical support number given at the bottom of the page and we will be pleased to help.
Hager Technical Help Line: 01952 675 689 Hager Technical Fax: 01952 675 557
Website: www.hager.co.uk
E-mail us: info@hager.co.uk
Twitter: @hageruk
Power & Lighting Boards
Designation
|
H
|
W
|
D
---|---|---|---
JKD146TM| 1100| 465| 165.5
JKD166TM| 1100| 465| 165.5
JKD164TM| 1100| 465| 165.5
JKD168TM| 1250| 465| 165.5
JKD188TM| | 465| 165.5
JKD186TM| 1250| 465| 165.5
JKD1416TM| 1400| 465| 165.5
JKD1164TM| 1400| 465| 165.5
JKD1812TM| 1400| 465| 165.5
JKD1128TM| 1400| 465| 165.5
JKD11212TM| 1400| 465| 165.5
Accessories
JK01B| Single Pole Blank
JK222PK| JK1 / JK2 Door Lock Kit
JK1PLATEM| Gland Plate + Drill Markings
JK101SPD| Type I/2 Surge protection Kit
JK102SPD| Type II Surge Protection Kit