hager JKD166TM Invicta 3 TPN Board Glazed Instruction Manual

June 5, 2024
hager

hager JKD166TM Invicta 3 TPN Board Glazed

All product(s) must be installed by a suitably competent electrician giving consideration to their intended use and in accordance with the current edition of BS 7671 (IET Wiring Regulations).
The Electricity at Work regulations and the Health and Safety at Work Act shall be complied with.
Only equipment and arrangements specified in Hager’s technical documentation / catalogue shall be used
Install in the vertical plane only.
Notice:
To prevent potential overheating from loose connections the installer shall check connections are tightened to the torque levels stated in these instructions prior to energising this board. This check should include factory made connections which may have loosened in transit.

Setup instructions

hager-JKD166TM-Invicta-3-TPN-Board-Glazed-fig2 hager-JKD166TM-Invicta-3-TPN-Board-Glazed-fig3 hager-JKD166TM-Invicta-3-TPN-Board-Glazed-fig4 hager-JKD166TM-Invicta-3-TPN-Board-Glazed-fig5

Interface Characteristics

Rated & operational voltage (Un / Ue)

415V a.c. 50Hz

Rated insulation voltage (Ui)

690V a.c. 50Hz

Rated impulse withstand voltage (Uimp)

4kV

Rated current of the Assembly (In A )

JKD1xxTM 125A

Rated current of an Outgoing circuit (In C )

MCB 0.5A – 63A (marked rated current on device)

RCBO 6A – 45A (marked rated current on device)

Rated Current of Pan Assembly

Upper Pan Inc =125A Lower Pan Inc = 125A

Rated conditional short-circuit current of the ASSEMBLY (Icc) 10kA1 with equipment and arrangements specified in Hager’s technical documentation / catalogue.

MCB/RCBO 10kA rating applied as BS EN 61439-3 is intended for use by ordinary persons.

1Current limitation characteristics specified in Hager’s technical documentation / catalogue

Protection against electric shock

DBO shall be installed in an electrical system conforming to IEC 60364 / BS 7671

Rated diversity factor (RDF)

10 way – 24 way = 0.7

Note: RDF only applies to continuously and simultaneously loaded circuits.

Rated frequency ( f n)

50 Hz

Pollution degree

2

Types of system earthing for which the ASSEMBLY is designed TNC-S, TN-S and TT when installed in an electrical system conforming to BS 7671
Intended locations

Indoor use only

Stationary ASSEMBLY
Degree of protection

IP3XD with Door Closed

IP2XC with Door Open and compliment of outgoing devices and or blanks fitted.

Intended use

Distribution boards intended to be operated by ordinary persons (DBO)

Electromagnetic compatibility (EMC) classification

EMC Environment B

External design

Wall-mounted, surface type, enclosed assembly.

Mechanical impact protection

IK05

The type of construction

Fixed parts

DBO Type

Type B DBO

Warranty

This distribution board is offered with a 24 month warranty against defective material or manufacture. If a warranty claim is necessary, please call the technical support number given at the bottom of the page and we will be pleased to help.

Hager Technical Help Line: 01952 675 689 Hager Technical Fax: 01952 675 557
Website: www.hager.co.uk
E-mail us: info@hager.co.uk
Twitter: @hageruk

Power & Lighting Boards

Designation

|

H

|

W

|

D

---|---|---|---
JKD146TM| 1100| 465| 165.5
JKD166TM| 1100| 465| 165.5
JKD164TM| 1100| 465| 165.5
JKD168TM| 1250| 465| 165.5
JKD188TM|  | 465| 165.5
JKD186TM| 1250| 465| 165.5
JKD1416TM| 1400| 465| 165.5
JKD1164TM| 1400| 465| 165.5
JKD1812TM| 1400| 465| 165.5
JKD1128TM| 1400| 465| 165.5
JKD11212TM| 1400| 465| 165.5

Accessories

JK01B| Single Pole Blank
JK222PK| JK1 / JK2 Door Lock Kit
JK1PLATEM| Gland Plate + Drill Markings
JK101SPD| Type I/2 Surge protection Kit
JK102SPD
| Type II Surge Protection Kit

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>