hager VS312PR Golf 36 M Surface-Mounted Enclosure with Opaque Door
| A| B| C| D
---|---|---|---|---
VS104| 138| 184| 101| 68
VS108| 210| 184| 174| 68
VS112| 282| 252| 222| 136
VS212| 282| 377| 222| 261
VS312| 282| 500| 222| 386
VS412| 282| 647| 222| 491
VS118| 390| 252| 330| 136
VS218| 390| 377| 330| 261
VS318| 390| 500| 330| 386
VS418| 390| 647| 330| 491
VS122| 462| 252| 402| 136
Attention!
It is critical that any enclosure is sized and selected to accommodate and
dissipate heat rise generated from all installed devices.
The table (right) provides maximum permissible heat dissipation for each golf
enclosure size. Please ensure that you calculate internal heat generated from
your installation and select the correct enclosure accordingly.
Reference
| Admissible thermal dissipation loss for surface mounted distribution boards
at temperature rise ∆T*
---|---
10K W| 15K W| 20K W| 25K W| 30K W
VS104| 2,4| 4,0| 5,8| 7,6| 9,5
VS108| 3,1| 5,1| 7,3| 9,6| 12,0
VS112| 4,7| 7,9| 11,2| 14,8| 18,6
VS212| 6,1| 10,1| 14,5| 19,1| 24,0
VS312| 7,5| 12,5| 17,8| 23,5| 29,5
VS412| 9,2| 15,2| 21,8| 28,8| 36,1
VS118| 6,4| 10,5| 15,1| 19,9| 24,9
VS218| 8,1| 13,4| 19,1| 25,3| 31,7
VS318| 9,8| 16,2| 23,2| 30,6| 38,4
VS418| 11,8| 19,5| 27,9| 36,9| 46,3
VS122| 7,4| 12,3| 17,6| 23,2| 29,1
-
∆T is the temperature difference between the upper limiting temperature of the installed equipment and the ambient air temperature of the distribution board.
-
The Assembly (DBO) designated markings must be completed as specified in IEC/EN 61439 – 3 clause 6.1.