It is critical that any enclosure is sized and selected to accommodate and dissipate heat rise generated from all installed devices. The table (right) provides maximum permissible heat dissipation for each golf enclosure size. Please ensure that you calculate internal heat generated from your installation and select the correct enclosure accordingly.


Reference| Admissible thermal dissipation loss for surface mounted distribution boards at temperatures rise ∆T*
---|---
10K

W

| 15K

W

| 20K

W

| 25K

W

| 30K

W

VE103..|

2,4

| 4,0| 5,7| 7,5|

9,4

VE106..|

3,2

| 5,3| 7,6| 10,1|

12,6

VE110..|

4.5

| 7,4| 10,6| 10,0|

17,6

VE112..|

7,7

| 12,8| 18,3| 24,2|

30,3

VE212..|

9,5

| 15,7| 23,5| 29,7|

37,3

VE312..|

11,3

| 18,8| 26,8| 35,4|

44,4

VE412..|

13,2

| 21,8| 31,2| 41,2|

51,7

VE118..|

9,9

| 16,4| 23,5| 31,0|

38,9

VE218..|

12,3

| 20,4| 29,2| 38,6|

48,4

VE318..|

14,8

| 24,6| 35,2| 46,4|

58,2

*) ∆T is the temperature difference between the upper limiting temperature of the installed equipment and the ambient air temperature of the distribution board.

****The Assembly (DBO) designated markings must be completed as specified in IEC/EN 61439 – 3 clause 6.1.

T +34 93 842 47 30

F +34 93 842 24 64

info@hager.com

hager-02.2022

Documents / Resources

| hager VE112PN Vector IP 65 Enclosures [pdf] Instruction Manual
VE112PN, Vector IP 65 Enclosures, VE112PN Vector IP 65 Enclosures, IP 65 Enclosures, 65 Enclosures, Enclosures
---|---

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals