Altronix AL1042ADA220 NAC Power Extender Installation Guide
- June 3, 2024
- Altronix
Table of Contents
Altronix AL1042ADA220 NAC Power Extender
Overview
Altronix AL1042ADA220 is an extremely cost-effective 10A remote power supply/battery charger. It may be con-nected to any 12 or 24 volt Fire Alarm Control Panel (FACP). Primary applications include Notification Appliance Circuit (NAC such as strobes and horns) expansion support to meet ADA requirements. It also provides auxiliary power to support system accessories. The unit delivers electronically regulated and filtered 24 volt power to Class B, Style W, X, Y or Class A, Style Z NAC loop circuits. Additionally, a separate 1A auxiliary output for 4-wire smoke detectors is available. The 10A max. alarm current can be divided between the four (4) outputs for powering NAC devices. Each output is rated at 2.5A max., and can be independently programmed for Steady, Temporal Code 3 or Strobe Synchronization. All outputs may be programmed for Input to Output Follower Mode (output will follow input. i.e. March Time Input, March Time Output). In non-alarm condition independent loop supervision for Class A, Style Z and/or Class B, Style W, X, Y FACP NAC circuits is provided. In the event of a loop trouble, the FACP will be notified via the steered input (input 1 or input 2). In addition, there are common trouble output terminals [NC, C, NO] which are used to indicate general loop/system trouble. A common trouble input is provided for optional [NC] (normally closed) devices to report trouble to the FACP. Two (2) FACP signaling outputs can be employed and directed to control supervision and power delivery to any combination of the four (4) outputs.
Specifications
Input:
- Power input 220VAC (working range 198VAC – 256VAC), 50/60Hz, 2.2A.
- Two (2) Class A, Style Z or two (2) Class B, Style W, X, Y FACP inputs.
- Two (2) NC dry contact trigger inputs.
Output:
- 24VDC voltage regulated power-limited outputs.
- 10A max total alarm current.
- 2.5A max current per output.
- Two auxiliary outputs rated at 1A each (1A continuous, 1A AC disconnect).
- Programmable supervised indicating circuit outputs:
- Four (4) Class B, Style W, X, Y or
- Four (4) Class A, Style Z or
- Two (2) Class A, Style Z and Two (2) Class B,Style W, X, Y (see 42 Application Guide).
- Thermal and short circuit protection with auto reset.
Battery Backup:
- Built-in charger for sealed lead acid or gel type batteries.
- Automatic switchover to stand-by battery when AC fails.
- Zero voltage drop when switching over to battery backup.
Supervision:
-
AC fail supervision (form “C” contact, 1A/28VDC).
Factory set for 2 hours with optional 1 minute delay setting (field selectable). -
Instant local AC trouble reporting relay (form “C” contact, 1A / 28VDC).
-
Battery presence and low battery supervision (form “C” contact, 1A / 28VDC).
Visual Indicators:
-
Input and output status LED indicators.
Special Features: -
2-wire horn/strobe Sync mode allows audible notification appliances (horns) to be silencedwhile visual notification appliances (strobes) continue to operate.
-
Sync protocols include Potter/Amseco, Faraday,
Gentex®, System Sensor®, and CooperWheelock®. -
Temporal Code 3, Steady Mode, Input to Output
Follower Mode (maintains synchronization of notification appliances circuit). -
Compatible with 12 VDC or 24VDC fire panels.
-
Output loop supervision directed to Input 1 or
Input 2.
-
Signal Circuit Trouble Memory – facilitates quick identification of an intermittent/fault (short circuit, open or ground) which has previously occurred on one or more signaling circuit outputs.
LEDs indicate/identify which output the fault has occurred. -
Common trouble input and output for external trouble signals tie-in.
-
Ground fault detection.
-
Unit includes power supply, logic board, enclosure, cam lock, and battery leads.
Enclosure Dimensions (approx. H x W x D): 18” x 14.5” x 4.5”
(457.2mm x 368.3mm x 114.3mm).
WARNING: To reduce the risk of fire or electric shock, do not expose the
unit to rain or moisture.
This installation should be made by qualified service personnel and should
conform to all local codes.
Power Supply Specifications:
AC Input: | 220VAC (working range 198VAC – 256VAC), 50/60Hz, 2.2A. |
---|
Output:
| Four (4) regulated supervised NAC output circuits, 24VDC, 2.5A maximum
current. One (1) aux. special application 24VDC power output circuit 1A, non-
supervised. Total output current must not exceed current 8A in Alarm
Condition.
Battery| Use two (2) 12VDC / 7AH or two (2) 12VDC / 12AH batteries connected
in series.
Stand-by/Alarm Current Consumption:| 130mA/300mA
EOL Resistor (end of line):| 2.2K (2200 Ohm), Altronix Model # AL-EOL22
(included).
Ground fault maximum test impedance:| 1000 Ohm.
Stand-by Specifications:
Stand-by Batteries| Stand-by Time Total| Alarm Output Current (A/Minutes)|
Aux. Output
---|---|---|---
24VDC/7AH| 24 Hours| 10A/5 minutes| –
24VDC/12AH (use two 12VDC batteries in series)| 24 Hours| 10A/5 minutes| 50mA
24VDC/36AH| 24 Hours| 10A/5 minutes| 1A
Note: Unit is equipped with two (2) 1A max. auxiliary outputs: “AUX1” will automatically disconnect when AC is lost. “AUX2” will remain battery backed up during power outage. For loads connected to “AUX2” please, refer to battery “Stand-by Specifications” above for ratings. When loads are connected to 10A total alarm current (example: AUX1 = 1A, AUX2 = 1A, outputs up to 8A).
Installation Instructions
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local codes and authorities having jurisdiction. Product is intended for indoor use only.
Carefully review:
Application Guide for AL642ADA220, AL842ADA220, AL1042ADA220
- Power Supply Output Specifications pg. 3
- Stand-by Specifications pg. 3
- Output Programming Selection Table pg. 4
- Sync Mode Selection Table pg. 4
- Terminal Identification Table pgs. 5-6
- LED Diagnostics pg. 6
-
Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two upper screws, level and secure. Mark the position of the lower two holes. Remove the enclosure. Drill the lower holes and install the two fasteners.
Place the enclosure’s upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 12). -
Secure ground wire lead to earth ground lug (Fig. 1). Connect the line (L) and neutral (N) terminals to a separate unswitched AC circuit (220VAC, 50/60Hz) dedicated to the Fire Alarm System.
-
Measure output voltage before connecting devices. This helps avoiding potential damage.
-
Connect battery to the terminals marked [– BAT +] on the Power Supply Board (battery leads included).
Use two (2) 12VDC batteries connected in series. -
Set output selection switches marked [OUT1] through [OUT4] to follow corresponding input [IN1] & [IN2] and desired output signal type (Output Programming Selection Table, pg. 4).
-
Connect FACP output to the desired AL842LGK logic board inputs, and notification appliances to the desired AL842LGK logic board outputs (see Application Guide).
Note: The 2-wire horn/strobe sync mode will only synchronize horns, horn/strobes, strobes with synchronization capability. -
For connection of smoke detectors, digital dialer see Optional Hookup Diagram, pg. 7.
Output Programming Selection Table:
Outputs must be programmed independently (OUT1 – OUT4)
Function | Switch Positions | Descriptions |
---|---|---|
ON | OFF | |
Input to Output Follower Mode | 1 | 2, 3 |
the corresponding input (i.e. FACP Sync module – maintains synchronization of
notification appliance circuit).
Temporal Code 3 Mode| 3| 1, 2| Enables Temporal Code 3 signal generation
output. This mode will accept a steady or a pulsing input.
Steady Mode| | 1, 2, 3| A steady output signal will be generated.
This mode will accept steady or pulsing input.
For the above modes DIP Switch 4 determines which Input controls the corresponding output:
Switch 4 in the ON position causes output(s) to be controlled by Input 1.
Switch 4 in the OFF position causes output(s) to be controlled by Input 2.
Note: It is required to control visual notification appliances (strobes)
via Input 1 (IN1) and audible notification appliances (horns) via Input 2
(IN2).
This allows audible notification appliances (horns) to be silenced while
visual notification appliances (strobes) continue to operate. The FACP must be
capable of a visual annunciation to the silencing status of the output or
zone(s) to which the AL1042ADA220 (NAC Power Extender) is connected.
AL842LGK Board
Output DIP Switches
Sync Mode Selection Table:
Function | Switch Positions | Descriptions |
---|---|---|
ON | OFF |
Amseco Sync Mode*
|
1, 3,
4
|
2
| This mode is designed to work with the Amseco series of horns, strobes, and horn/strobes to provide a means of synchronizing the Temporal-coded horns, synchronizing the flash timing of the strobe, and silencing the horns of the horn/strobe combination over a two-wire circuit while leaving strobes active.
Faraday Sync Mode*
|
2, 4
|
1, 3
| This mode is designed to work with the Faraday series of horns, strobes, and
horn/strobes to provide a means of synchronizing the Temporal-coded horns,
synchronizing the flash timing of the strobe, and silencing the horns of the
horn/strobe combination over a two-wire circuit while leaving strobes active.
Gentex® Sync Mode*
Gentex is a registered
trademark
|
1, 2,
3, 4
| | This mode is designed to work with the Gentex® series of horns, strobes,
and horn/strobes to provide a means of synchronizing the Temporal-coded horns,
synchronizing the flash timing of the strobe, and silencing the horns of the
horn/strobe combination
of Gentex Corporation.| | over a two-wire circuit while leaving strobes
active.
System Sensor® Sync Mode*
System Sensor is a
|
1, 2, 4
|
3
| This mode is designed to work with the System Sensor® series of horns,
strobes, and horn/strobes to provide a means of synchroniz- ing the Temporal-
coded horns, synchronizing the one-second flash
registered trademark of| | | timing of the strobe, and silencing the horns of
the horn/strobe
Honeywell.| | | combination over a two-wire circuit while leaving strobes
active.
CooperWheelock® Sync Mode*
CooperWheelock is a
|
2, 3, 4
|
1
| This mode is designed to work with the CooperWheelock® series of horns,
strobes, and horn/strobes to provide a means of synchronizing the Temporal-
coded horns, synchronizing the one-second flash tim-
registered trademark of| | | ing of the strobe, and silencing the horns of the
horn/strobe combi-
Cooper Wheelock.| | | nation over a two-wire circuit while leaving strobes
active.
Note: AL1042ADA220 will only synchronize horns, horn/strobes, and strobes
that contain synchronization capability.
Contact signal manufacturer for more detailed info. The same synchronization
mode must be selected for all outputs.
Amount of Notification Appliances per NAC:
Amseco | 27 per NAC* | System Sensor® | 32 per NAC* | |
---|---|---|---|---|
Gentex® | 32 per NAC* | CooperWheelock® | 32 per NAC* |
Not to exceed a maximum of 2.5A per NAC.
Terminal Identification Table:
AL842LGK Logic Board
Terminal Legend | Function/Description |
---|
– IN1 +
– IN2 +
(Supervised)
| These terminals connect to the 24VDC FACP notification appliance circuit outputs. (Class A, Style Z or Class B, Style W, X, Y) Input trigger voltage is 8-33VDC @ 5mA min. Terminal polarity is shown in alarm condition. During an alarm condition these inputs will cause the selected outputs chosen to drive notification appliances. The designated outputs are set by output switches [OUT1 through OUT4] (Output Programming Selection Table, pg. 4). A trou- ble condition on an output loop will cause the corresponding input to trip the FACP by opening the FACP loop. An alarm condition will always override trouble to drive notification appliances.
– RET1 +
– RET2 +
(Supervised)
| For Class A, Style Z hookups these terminal pairs return to FACP NAC1 and/or
NAC2. For Class B, Style W, X, Y hookups the FACP EOL resistor from the NAC1
and/or NAC2 outputs are terminated at these terminals. Optionally, other
notification appliances or additional signaling circuit power supplies may be
connected to these terminals. If this option is chosen, the EOL resistor must
be terminated at the last device.
NC “DRY1” C NC “DRY2” C
(Dry input trigger)
| An open across these inputs, will cause the selected outputs chosen to drive
notification appliances. The designated outputs are set by output switches
[OUT1 through OUT4] (Output Programming Selection Table, pg. 4). Note these
inputs are unidirectional and will not report a trouble condition to the FACP.
– OUT1 +
– OUT2 +
– OUT3 +
– OUT4 +
(Supervised)
| Notification appliances are connected to these regulated outputs (see Application Guide pg. 2-4). Each power-limited output will supply 2.5A. Total supply current is 10A (see note below). Outputs are controlled by designated Input 1 [IN1] or Input 2 [IN2] (Output Programming Selection Table, pg. 4).
Maximum line loss or voltage drop (tested with 2.5V).
– Loop 1 +
– Loop 2 +
– Loop 3 +
– Loop 4 +
| ****
Used for Class A, Style Z hook-ups to terminate loops originating on [OUT1], [OUT2], [OUT3], and [OUT4] respectively.
C “FAULT” NC
(Common trouble input)
| An open circuit across this pair of terminals will cause [INP1 and INP2] LEDs to simultaneously signal a trouble condition back to the FACP.
Typically used to report AC or BAT Fail. (Fig. 2b, pg. 7).
NC, C, NO
(Common trouble output)
| These are dry contact trouble outputs that report any general loop/system trouble condi- tions. Typically used to trigger a digital communicator or other reporting devices.
Form “C” contact 1A / 28VDC 0.35 Power Factor (Fig. 2, pg. 7).
– AUX1 +
| This separate 1A max. auxiliary Special Application Power output circuit is typically used to power 4-wire smoke detectors.
See attached list of devices (Appendix A, pgs. 10-11).
– AUX2 +
| This separate auxiliary regulated power output circuit supplies up to 1A
during stand-by and alarm condition. Since this output is not disconnected
from its load during AC power failure use the (Battery Calculation Worksheet,
pg. 9) to determine battery size and/or allowable stand-by and alarm current.
+ DC –| 24VDC from power supply.
Note: Unit is equipped with two (2) 1A max. auxiliary outputs: “AUX1” will automatically disconnect when AC is lost. “AUX2” will remain battery backed up during power outage. For loads connected to “AUX2”please, refer to Battery Stand-by Specifications, pg. 3 for ratings. When loads are connected to the “AUX1” and or “AUX2” outputs during alarm condition, the remaining outputs may not exceed 10A total alarm current. Example: AUX1 = 1A, AUX2 = 1A, outputs up to 8A.
Terminal Identification Table:
Power Supply Board
Terminal Legend | Function/Description |
---|---|
L, N | Connect 220VAC to these terminals: L to Hot, N to Neutral. |
+ DC – | 24VDC @ 10A continuous, 10A in alarm non power-limited output. |
AC FAIL NO, C, NC | Form “C” dry contacts indicate the loss of AC, with AC |
present terminals marked [NO] and [C] are open, [NC] and [C] are closed. When
loss of AC occurs terminals marked [NO] and C] are closed, [NC] and [C] are
open.
AC LOCAL NC, NO, C| Form “C” dry contacts used to instantaneously signal the
loss AC to local annunciation devices, with AC present terminals marked [NO]
and [C] are open, [NC] and [C] are closed.
When loss of AC occurs terminals marked [NO] and [C] are closed, [NC] and [C] are open.
BAT FAIL NO, C, NC| Form “C” dry contacts indicate low battery voltage or loss
of battery voltage. Under normal conditions terminals marked [NO] and [C] are
open, [NC] and [C] are closed. During a trouble condition terminals marked
[NO] and [C] are closed, and [NC] and [C] are open (Fig. 2, pg. 7).
– BAT +| Stand-by battery input (leads provided) (Fig. 2, pg. 7).
Power Board Parameter Specifications:
-
AC Fail condition will report approximately 2 hours after loss of AC. To set AC Delay to 1 minute, power the unit down (AC supply and Battery) prior to changing switch position.
Turn “AC Delay” switch ON for 1 minute or OFF for 2 hours, respectively. -
Low battery condition will report at approximately 20VDC.
-
Battery presence detection will report within 180 seconds after battery remains undetected (missing or removed). A restored battery will report within 30 seconds.
LED Diagnostics:
Power Supply Board
Red (DC) | Green (AC) | Power Supply Status |
---|---|---|
ON | ON | Normal operating condition. |
ON | OFF | Loss of AC. Stand-by battery is supplying power. |
OFF | ON | No DC output. |
OFF | OFF | Loss of AC. Discharged or no stand-by battery. No DC output. |
AL842LGK – Logic Board
LED | OFF | ON | BLINK (LONG)* | BLINK (SHORT)** |
---|---|---|---|---|
ON | Normal | Alarm Condition | Trouble Condition | Trouble Condition Memory |
ON | Normal | Alarm Condition | Trouble Condition | Trouble Condition Memory |
OFF | Normal | Alarm Condition | Trouble Condition | Trouble Condition Memory |
OFF | Normal | Alarm Condition | Trouble Condition | Trouble Condition Memory |
Input 1 | Normal | Alarm Condition | Trouble Condition | – |
Input 2 | Normal | Alarm Condition | Trouble Condition | – |
Fault | Normal | Alarm Condition | – | – |
Indicates existing trouble condition. When a trouble condition (open, short or ground) occurs on a specific output, the corresponding red output LED [OUT1] – [OUT4] will blink. The corresponding green input LED will blink as well.
Indicates trouble condition memory. When a trouble condition restores, the
units red output LEDs,[OUT1] – [OUT4] will blink with a shorter and distinctly
different duration.
The green input LEDs will be off (normal condition).
To reset the memory depress the reset button located on the AL842LGK logic
board (Fig. 2c, pg. 7).
The LED(s) will extinguish.
Note: When indicating circuits have restored, trouble memory reset is not
required for normal operation.
Optional Hookup Diagram
Optional Hookups
-
Battery and AC monitoring: AC or Battery Fail condition will cause the common trouble input [C “FAULT” NC] to report back to the FACP via Input 1 and Input 2. The common trouble input may also be used for other optional supervisory monitoring.
To report AC and Battery Trouble connect the battery and AC fail relay output to the common trouble input (Fig. 2). -
Dry contact input [C ”DRY1” NC] [C ”DRY2” NC] can be used to alarm output from an addressable module (these inputs are unidirection and cannot report back to trigger module).
Note: If common trouble input, terminals marked [C “FAULT” NC] are not used, these terminals must be shorted (together) to remain inactive (For optional hookups see Fig. 2). -
Auxiliary outputs provide 24VDC at 1A max per output.
“AUX1” will be automatically disabled during power failure. (use this for non required backup power)
“AUX2” will remain operational during allowable power failure. Refer to stand- by chart for stand-by and alarm current.
Note: If common trouble input, terminals marked [C “FAULT” NC] are not used, these terminals must be shorted (connect jumper) to remain inactive. For optional hookups see Fig. 2b, pg. 7.
Maintenance
Unit should be tested at least once a year for the proper operation as
follows:
- Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level (26.2-26.4VDC recommended range).
- Battery Test: Under normal load conditions check that the battery is fully charged. Check specified voltage both at battery terminal and at the board terminals marked [–
- BAT +] to ensure that there is no break in the battery connection wires.
- Fuses: Check input and output fuses on the power supply board, replace if necessary.
- Input fuse rating is 6.3A @ 250V, Output fuse rating is 15A @ 32V.
Note: Maximum charging current is 1.5A.
Note: Expected battery life is 5 years; however, it is recommended changing batteries in 4 years or less if needed.
Battery Calculation Worksheet
Device | Number of Devices | Current per Device | Stand-by Current | Alarm Current |
---|---|---|---|---|
For each device use this formula: | This column x This column = Equals | Current |
per number of devices.
AL1024ADA220
(Current draw from battery)
| 1| Stand-by:| 130mA| 130mA|
Alarm:| 300mA| | 300mA
A| AL1042 Current| 130mA| 300mA
Auxiliary Devices| | Refer to device manual for current ratings.
| | Alarm/Stand-by| mA| mA| mA
| | Alarm/Stand-by| mA| mA| mA
| | Alarm/Stand-by| mA| mA| mA
B| Auxiliary Devices Current (must not exceed 1A)
| | Refer to device manual for current ratings.
| | Alarm:| mA| 0mA| mA
| | Alarm:| mA| 0mA| mA
| | Alarm:| mA| 0mA| mA
| | Alarm:| mA| 0mA| mA
C| Notification Appliances Current must not exceed 10A (10,000mA)
0mA| | mA
D| Total alarm current| mA| mA
E| Total current ratings converted to amperes (line D x .001)| A| A
F| Number of standby hours (24 for NFPA 72, Chapter 1, 1-5.2.5).| H|
G| Multiply lines E and F. Total stand-by
AH| AH|
H| Alarm sounding period in hours.
(For example, 5 minutes = 0.0833 hours.)
| | H
I| Multiply lines E and H. Total alarm
AH| | AH
J| Add lines G and I. Total stand-by and alarm
AH| AH|
K
| Multiply line J by 1.30.
(30% extra insurance to meet desired performance) Total ampere – hours required
| ****
AH
|
Units are capable of recharging 36AH battery max. If total ampere – hour required exceeds 36AH,decrease AUX current to provide enough stand-by time for the application.
Appendix A – Compatible Devices
A-1 Four (4) Wire Smoke Detectors
Table A-1 below lists four (4) wire smoke detectors compatible with
AL1042ADA220 AUX output.
Smoke Detector/Base| Detector Type| Max Standby
Current (mA)
| Alarm
Current (mA)
---|---|---|---
FenWal CPD-7021 (w/70-201000-005 Base)| Ionization| 0.10|
FenWal PSD-7125| Photoelectric| 0.10|
FenWal PSD-7125 (w/70-201000-005 Base)| Photoelectric| 0.10|
Fire-Lite BLP-12-4W| Base| |
Gentex 824| Photoelectric| 0.50|
Gentex 824T| Photoelectric| 0.50|
Gentex 824CP| Photoelectric| 0.50|
Gentex 824CPT| Photoelectric| 0.50|
Hochiki HSC-4R| Base| |
Hochiki SPB-24| Projected Beam| 0.25|
System Sensor B112LP| Base| 0.12| 36
System Sensor B114LP| Base| |
System Sensor B404B| Base| |
System Sensor DH100ACDC| Photoelectric| 0.15| 0.70
System Sensor DH100ACDCLP| Photoelectric| 0.15| 0.70
System Sensor DH100ACDCLPW| Photoelectric| 0.15| 0.70
System Sensor DH400ACDCI| Ionization Duct| 25| 95
System Sensor DH400ACDCP| Photoelectric Duct| 25| 95
System Sensor 1112/24/D| Ionization| 0.05| 50
System Sensor 1424| Ionization| 0.10| 41
System Sensor 1451 (w/B402B Base)| Ionization| 0.10| 39
System Sensor 2112/24ATR| Photoelectric| 0.50| 60/70
System Sensor 2112/24AITR| Photoelectric| 0.50| 60/70
System Sensor 2112/24/D| Photoelectric| 0.05| 50
System Sensor 2112/24R| Photoelectric| 0.50| 60/70
System Sensor 2112/24TR| Photoelectric| 0.50| 60/70
System Sensor 2112/24T/D| Photoelectric w/135o Thermal| 0.05| 50
System Sensor 2112/24TSRB| Photoelectric w/135o Thermal Supervisory Relay| 15|
45
System Sensor 2312/24TB| Photoelectric| 0.12| 50
System Sensor 2412 (12 volt)| Photoelectric| 0.12| 77
System Sensor 2412AT (12 volt)| Photoelectric| 0.12| 58
System Sensor 2412TH (12 volt)| Photoelectric| 0.12| 77
System Sensor 2424| Photoelectric| 0.10| 41
System Sensor 2424TH| Photoelectric| 0.10| 41
System Sensor 2451| Photoelectric| 0.10| 39
System Sensor 2451TH (with/B402B Base)| Photoelectric| 0.10| 39
System Sensor 2W-MOD| Loop Test/Maintence Mod.| 30| 50
System Sensor 4W-B (12/24 volt)| Photoelectric I3| 0.05| 23
System Sensor 4WT-B (12/24 volt)| Photoelectric I3 w/Therm| 0.05| 23
System Sensor 4WTA-B (12/24 volt)| I3 Photo w/Therm/Sounder| 0.05| 35
System Sensor 4WTR-B (12/24 volt)| I3 Photo w/Therm/Relay| 0.05| 35
System Sensor 4WTR-B (12/24 volt)| I3 Photo w/Therm/Sounder/Relay| 0.05| 50
System Sensor 4WITAR-B (12/24 volt)| I3 Photo w/Isolated Therm/Sounder/ Relay|
0.05| 50
System Sensor 2W-MOD2| I3 Loop Test/Maintence Mod.| 0.05|
System Sensor RRS-MOD| I3 Reversing Relay/Sync Module| 0.05|
System Sensor 6424| Projected Beam| 10| 28.4
System Sensor Beam 1224(S)| Projected Beam| 17| 38.5
Contact manufacturer for current draws
A-2 Door Holders
Table A-2 below lists door holders compatible with AL1042ADA220 AUX output.
Manufacturer | Model | Type | Current (mA) |
---|---|---|---|
Edwards | DH150A | Floor Mount | 96 |
Edwards | DH154A | Floor Mount | 96 |
Edwards | DH158A | Surface Mount | 96 |
Rixon Firemark | FM-980 | Floor Mount, single | 68 |
Rixon Firemark | FM-996 | Surface Wiring | 68 |
Rixon Firemark | FM-998 | Concealed Wiring | 68 |
A-3 Relays
Table A-3 below lists relays compatible with AL1042ADA220 AUX output.
Manufacturer | Model | Current (mA) |
---|---|---|
MR-101/C | 15 | |
MR-201/C | 35 | |
Air Products & Controls, LTD | PAM-1 PAM-2 | 15 |
15
| PAM-SD| 15
| A77-716B| 20
| PR-1| 15
| PR-2| 30
| PR-3| 30
| EOLR-1| 30
| R-10T| 23
System Sensor| R-14T R-20T| 23
40
| R-24T| 40
| R-10E| 23
| R-14E| 23
| R-20E| 40
| R-24E| 40
Enclosure Dimensions
18” x 14.5” x 4.5” (457.2mm x 368.3mm x 114.3mm)
Altronix is not responsible for any typographical errors.
140 58th Street, Brooklyn, New York 11220 USA | phone:
718-567-8181 | fax:
718-567-9056
website: www.altronix.com
e-mail: info@altronix.com
Lifetime Warranty
IIAL1042ADA220
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>