MET MANN EP-050 Industrial Solid Fuel Space Heater Instruction Manual

June 1, 2024
MET MANN

MET MANN EP-050 Industrial Solid Fuel Space Heater

MET-MANN-EP-050-Industrial-Solid-Fuel-Space-Heater-
PRODUCT

Product Information

Specifications:

  • Nominal Thermal Power (Hi): TREATED AIR
  • Useful Static Pressure: [specific value not provided]

Product Usage Instructions

  1. Recommendations :
    Follow the recommendations provided in the manual for optimal product performance and safety.

  2. General Dimensions:
    Refer to the manual for detailed information on the general dimensions of the warm air generator.

  3. Functional Features:
    Understand the functional features of the product as described in the manual to utilize them effectively.

  4. Construction Features:
    The warm air generator includes a fan group and a smoke-unloading mouth. Familiarize yourself with these features for proper operation.

  5. Packing and Transport:
    Refer to the manual for guidance on packing and transporting the warm air generator safely.

  6. Instructions for the Qualified Installer:
    Qualified installers should carefully follow the electric connection instructions and combustion gas evacuation guidelines provided in the manual.

  7. Assistance :
    Contact the provided assistance details for any product-related queries or issues.

FAQ:

  • Q: Can I print the manual for personal use?
    A: No, total or partial printing is forbidden without previous authorization from MET MANN.

  • Q: What should qualified installers pay special attention to?
    A: Qualified installers should pay special attention to electric connection and combustion gas evacuation instructions.

REF. MI-EP050-I

  • December 2014 edition
  • Rights reserved for making technical modifications to improve the product.
  • Total or partial printing is forbidden without previous authorization from MET MANN

TECHNICAL FEATURES

  MODEL
  EP-050-H
Nominal thermal power (Hi) kW

TREATED AIR

| Airflow at +20ºC| m 3/h| 1.700| 2.400| 3.400
Useful static pressure| mm.c.a| 1| 4| 5
Thermal difference| ºC| 35| 35| 35
Electric tension| V/F/Hz| 220/380V ACIII 50Hz
Installed electric power| kW| 0,16| 0,19| 0,59
Noise level at 3 meters in typical installation| dB (A)| 65| 65| 65
Weight| Kg.| 350| 350| 800
Maximum load (dry wood)| Kg.| 10| 10| 20

  • Dry wood calorific power = 4000 kcal/kg

Recommendations

  • Read carefully the warnings shown in the instructions since they give important indications concerning the installation security, their use, and maintenance.
  • Use dry wood and avoid bad combustion of the equipment.
  • The installation should be made according to the standards in force in the country in which it will be used, according to the manufacturer’s instructions, to those given by the qualified professional staff or to those given by the Assistance Centre authorised by the manufacturer. An error in the installation can be harmful to people and equipment, for which the manufacturer will not be responsible.
  • To control the packing and the integrity of the content. In case of doubt do not use the equipment and send it back to the supplier.
  • Do not leave the packing elements at children’s reach because it is a source of danger.
  • Leave free the aspiration grids.
  • In case of equipment breakdown or malfunctioning, deactivate it, do not make any intent to repair it and ask for the installer intervention.
  • Since you decide not to use the equipment any more, you must make useless the parts that can be a source of danger.
  • This machine has to be used in the application it is made for. Any other use will be considered inadequate and even dangerous.
  • Make sure that these instructions will always go with the machine.
  • If this equipment is installed in a place where there are disabled persons and/or with children, it must be installed in a difficult-access way.

GENERAL DIMENSIONS

MODEL A B C D Ø
EP-050 1396 1190 783 621 147
EP-100 2105 1682 1013 865 195

EP-050MET-MANN-EP-050-Industrial-Solid-Fuel-Space-Heater-FIG-
\(1\)

EP-100MET-MANN-EP-050-Industrial-Solid-Fuel-Space-Heater-FIG-
\(2\)

FUNCTIONAL FEATURES

The warm air generator that functions with solid combustibles is an equipment of which the system consists of heating the environmental air by using thermal energy produced by combustion.
The thermal exchange takes place when an airflow generated by the centrifugal fan goes through the heat exchanger surfaces, without help of the intermediate fluid, and through the machine radiation.
The combustion products, when completed with the thermal exchange, are expelled from inside through a chimney.
These equipment are used to heat industrial areas. (They cannot be installed in direct contact with atmospheric agents).

CONSTRUCTION FEATURES

The warm air generator is made in steel with carbon, made according to European standards and easily inspected for casual cleaning operations and maintenance. It is made of:

  1. A rectangular combustion chamber surrounded by refractory bricks.
  2. Loading mouth for solid combustibles.
  3. Big tubular exchanger.
  4. Ash collecting box.
  5. Chimney connector in which the combustion products get through is later sent through the chimney to the exterior of the enclosure.

Fan group
It is made of a helicoidal fan (EP-050) or a centrifugal one (EP-100) with a low noise level and a big airflow.

Smoke unloading mouth
The equipment has a circular neck to which a metallic chimney can be connected and fixed securely, to evacuate the combustion products.
This pipe must have the following features.

  • Diameter equal or superior to that one of the mouth and without section reductions.
  • Not making elbows superior to 45º.
  • Having an external wind-proof terminal.

The unit has a regulation system to the smokes flueMET-MANN-EP-050
-Industrial-Solid-Fuel-Space-Heater-FIG- \(3\)

PACKING AND TRANSPORT

The warm air generators are sent in a plastic bubble pack. The accessories will be packaged separately. Shipping, unloading and maintenance must be carried out with the maximum care to avoid possible harms.

INSTRUCTIONS FOR THE QUALIFIED INSTALLER
The EP series warm air generator position must be defined taking into account the following instructions:

  • Installation on the floor, regulating the equipment’s stability.
  • The equipment do not have to fit in niches.
  • Do not obstruct the fan aspiration grids.
  • Do not install it close to obstacles that can impede warm air diffusion.
  • To respect the minimum distance to the wall allowed by standards.
  • Check if the maintenance and cleaning operations can take place easily.

Electric connection
This equipment is made according to the CEE 73/23 directive and operates with 230V/AC 50Hz electric power.

INSTRUCTIONS FOR COMBUSTION GAS EVACUATION

Chimneys to be installed shall be homologated for their use and will have the statutory draft regulator. Their section will be set according to the following formula:

DRAFT
A chimney draft is set by the expression:

  • T= H (YA – YB)
  • T= Draft in mm.c.a.
  • H= Height of the vertical chimney in metres.
  • YA= Specific weight of the exterior air in kg/m³.
  • YB= Specific weight of combustion gases expelled in kg/m³.

SECTION
The chimney section for both series is set by the formula:

  • S= 8, 61 Q/H½
  • S= Chimney section in cm²
  • Q= Boiler power in kW/h.
  • H= Reduced height expressed in metres.
  • The reduced height of the chimney is set by the formula:
  • Hr = H – (N. 0, 5 + L + R)
  • Hr= Reduced height.
  • H= Chimney real height.
  • N= Number of direction changes.
  • L= Horizontal length.
  • R= Generator resistance.
  • R= 1mm up to 50.000 kcal/h.
  • R= 2mm up to 160.000 kcal/h.

These values will be increased in a 6% every 500 metres over the sea level.

HORIZONTAL PIPE

  • A= 0, 55 x S (L / H + 1) You shall check that L < H / 3
  • A= Section in cm² of the horizontal segment.
  • S= Vertical section in cm².
  • L= Horizontal segment length in metres.
  • H= Chimney height in metres.

If the chimney is rectangular, you shall check that the relation between both sides is not superior to 1, 5. The chimney will be insulated according to the rules in force.

OPERATION IRREGULARITIES – REASONS AND SOLUTIONS –
In case of anomalies in the warm air generators operation, ensure first that:

  • There is enough electric power
  • Not to give tensions superior to +10% o -15%.
  • The fuses work correctly.
  • There is enough solid combustible.

NOTE : The eventual repairs must be done by technical qualified staff which use original parts. It is forbidden to open or manipulate the generator parts except for those previewed in the maintenance.

CASUAL MAINTENANCE
For a regular operation and a good preservation of the equipment, we recommend that qualified technical staff do, at least once a year and preferably at the end of the season, the periodical maintenance operations.
Any intervention in these equipments must be done when cold.

Exchanger cleaning at the end of the winter period
For this operation proceed as follows:

  • Clean the exchange elements with a small steel brush.
  • Aspire with an aspirator the possible soot that felt from the exchange elements in the combustion chamber.
  • Replace the spoiled bricks.
  • Clean the exchanger external surface.

Unloading smokes pipe
Take out possible obstructions and/or deposits that could have been formed inside it.

Fan group
Clean it with a brush or compressed air.

INSTRUCTIONS FOR THE USER

Use
This equipment is designated to industrial use. You must not install it in direct contact with atmospheric agents.

Operation

  • Load the equipment with wood or similar.
  • Connect the fan to the electric installation.
  • Proceed to flare up the wood.
  • Do not connect the pipe to the machine outlet.
  • The fuel load must never be superior to the nominal power of the machine.
  • Never put the generator into operation without connecting the fan to the electric net. Do not disconnect the generator if its hearth is lighted.

NEVER REMOVE THE TENSION WHEN THE EQUIPMENT IS HOT NEVER TOUCH THE PARTS EXPOSED TO HEAT IRRADIATION
Since accumulated thermal energy in the exchanger can harm the fan group and the heat exchanger

Ventilation in summer
For obtaining from the generator only ventilation, proceed as follows:

  • Connect the fan to the network.
  • Disconnection at the end of the season
  • Disconnect the equipment and do the corresponding maintenance.

ASSISTANCE
You can ask directly your seller for a technical agent, or you can contact METALURGICA MANLLEUENSE, S.A., which will send you the address of the closest Assistance Service.

GENERATOR BREAKDOWN DRAWING

MET-MANN-EP-050-Industrial-Solid-Fuel-Space-
Heater-FIG- \(4\)

Position refractory bricks EP-050MET-MANN-EP-050-Industrial-Solid-Fuel-
Space-Heater-FIG- \(5\)

CODE DIMENSIONS Q
1 060622011030 220x110x30 40

Position refractory bricks EP-100MET-MANN-EP-050-Industrial-Solid-Fuel-
Space-Heater-FIG- \(6\)

CODE DIMENSIONS Q
1 060622011030 220x110x30 22
2 PL13645 220x110x30 59
3 PL12128 220x037x30 6
4 PL13646 220x110x30 4
5 PL12218 220x055x30 4
6 PL12127 110x110x30 2

ACCESSORIES GENERATOR PROTECTION (EP-050)MET-MANN-EP-050-Industrial-
Solid-Fuel-Space-Heater-FIG- \(7\)MET-MANN-EP-050-Industrial-Solid-Fuel-Space-Heater-FIG-
\(8\)

WARNING

  • The manufacturer don’t take any responsibility for beyond modifications in\ the origin machine.
  • The manufacturer don’t take any responsibility for the breakdowns caused for a bad use.
  • The manufacturer don’t take any responsibility for que working and quality of the machin if this entails implicit the no observation of the present
  • INSTRUCTIONS OF INSTALLATION, USE AND MAINTENANCE Consult to manufacturer about unexpected changes on the instructions.

FACTORY AND OFFICES
C/ Foncuberta, 32-36 – CP: 19
Tel. (34)93 851 15 99*
Fax ( 34)93 851 16 45
E-mail: metmann@metmann.com
http://www.metmann.com
08560 MANLLEU (Barcelona) SPAIN
INDUSTRIAL • COMMERCIAL • DOMESTIC CONDITIONING • DRYERS • VENTILATION • HOMOLOGATED

Get In Touch
Call : 0845 6880112
Email: info@adremit.co.uk

Our Address
Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North Yorkshire, BD24 9RH

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals