SolaXPower 320101064101 Triple Power BMS Parallel User Manual
- June 1, 2024
- SolaXPower
Table of Contents
SolaXPower 320101064101 Triple Power BMS Parallel
SolaX Power Network Technology (Zhejiang) Co., Ltd.
Add.: No. 288, Shizhu Road, Tonglu Economic Development Zone, Tonglu City,
Zhejiang Province, 310000 P.R. CHINA
Tel.: +86 (0) 571-5626 0011
E-mail: info@solaxpower.com
CHANGE HISTORY
Changes between document versions are cumulative. The latest version contains
all updates made in previous versions.
Version 01 (Oct. 26, 2023)
Updated all pictures that include the appearance and port details of the
parallel box.
Version 00 (Sept. 21, 2023)
Initial release
Note on this Manual
Scope of Validity
This manual is an integral part of the Parallel Box Series.
It describes the assembly, installation, commissioning, maintenance and
failure of the product. Please read carefully prior to operation.
Model: BMS Parallel Box- G2
NOTE! The BMS Parallel Box- Ⅱ G2 can be used with T-BAT-SYS-HV-5.8 or T -BAT-SYS- HV-3.0. Please refer to section 4 “Installation ”from page 10 to page 20 for details.
Target Group
This manual is for qualified electricians. The tasks described in this manual
should only be performed by qualified electricians.
Symbols Used
The following types of safety instructions appear in this document are
described below:
DANGER! “DANGER” indicates a hazardous situation which, if not avoided,
will result in serious injury or death.
WARNING! “WARNING” indicates a hazardous situation which, if not avoided,
could result in serious injury or death.
CAUTION! “CAUTION” indicates a hazardous situation which, if not avoided,
could result in minor or moderate injury.
NOTE! “NOTE” provides tips that are valuable for the optimal operation of
your product.
Safety
Appropriate Usage
For safety reasons, installers are responsible for familiarizing themselves
with the contents of this manual and all warnings before performing
installation.
Important Safety Instructions
DANGER Danger to life due to high voltages in the parallel box!
- All work must be carried out by qualified electrician.
- The appliance is not to be used by children or persons with reduced physical sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction.
- Children should be supervised to ensure that they do not play with the appliance.
CAUTION
- Danger of burn injuries due to hot enclosure parts!
- During operation, the upper lid of the enclosure and the enclosure body may become hot.
- Only touch the lower enclosure lid during operation.
- Possible damage to health as a result of the effects of radiation!
- Do not stay closer than 0.66 ft/20 cm to the parallel box for any length of time.
WARNING
- Do not operate the parallel box when the device is running.
- Authorized service personnel must disconnect the cables before attempting any maintenance or cleaning or working on any circuits connected to the box.
- Prior to the application, please read this section carefully to ensure correct and safe application.
- Please keep the user manual properly.
- Use only attachments recommended or sold by our company. Otherwise, it may result in a risk of fire, electric shock, or injury to person.
- Make sure that the existing wiring is in good condition and that the wire is not undersized.
- Do not disassemble any parts of the box which are not mentioned in the user manual. The parallel contains no user-serviceable parts.
- See Warranty for instructions on obtaining service. Attempting to service the box yourself may result in a risk of electric shock or fire and will void your warranty.
- Keep the parallel box away from flammable, explosive materials to avoid fire disaster.
- The installation place should be away from humid or corrosive substance. Authorized service personnel must use insulated tools when installing or working with this equipment.
Qualified Installer
WARNING! All operations of box relating to electrical connection and
installation must be carried out by qualified personnel.
A skilled worker is defined as a trained and qualified electrician or installer
who has all of the following skills and experience:
- Knowledge of the functional principles and operation of grid-tied systems
- Knowledge of the dangers and risks associated with installing and using electrical devices and acceptable mitigation methods
- Knowledge of the installation of electrical devices
- Knowledge of and adherence to this manual and all safety precautions and best practices
Explanation of Symbols
This section gives an explanation of all the symbols shown on the warning
label.
Product Introduction
Product Overview
For safety reasons, installers are responsible for familiarizing themselves
with the contents of this manual and all warnings before performing
installation.
Dimension
Appearance
Terminals of the BMS Parallel Box-Ⅱ G2
NOTE! The cable connection between the BMS Parallel Box-Ⅱ G2 and T-BAT- SYS-HV-5.8 is different from that between the BMS Parallel Box-Ⅱ G2 and T-BAT- SYS-HV-3.0.
Features
The box has advanced technology, high reliability and convenient control functions, as shown below:
- Interact with inverter
- According to the interactive information, judge and control the running state of the battery system
- BMS related control processing
- Realize the corresponding fault identification and processing
- Ensure the safe operation of the battery system.
- Secondary protection by hardware
- IP65 protection level
- Safe and reliable
- Small occupied area
- Wall mounting
Technical Data
Installation
Installation Prerequisites
When assembling the system, avoid touching the terminal with any metal objects
or bare hands. The box provides a safe source of electrical energy when
operated as designed.
The previous safety precautions and the warning messages described in this
section must be observed. If any of the previous precautions are not fully
understood, or if you have any questions, contact customer service for
guidance. The Safety Section may not include all regulations for your region.
Ensure that the installation location meets the following conditions:
- The building is designed to withstand earthquakes.
- The location is far from the sea to avoid salt water and humidity, over 0.62 miles/997.79 meters.
- The floor is flat and level.
- No inflammable or explosive materials within a range of at least 3 ft/0.91 m.
- The ambiance is shady and cool, away from heat and direct sunlight.
- The temperature and humidity remain at a constant level.
- There is minimal dust and dirt in the area.
- There are no corrosive gases present, including ammonia and acid vapor
In practice, the requirements of the parallel box installation may be different due to enviroment and locations. In that case, please follow up the exact requirements of the local laws and standards.
Safety Gear
Installation and maintenance personnel must operate according to applicable
federal, state, and local regulations as well as industry standards regarding
product installation. Personnel must wear safety gear as indicated below in
order to avoid short circuit and personal injury.
Tools
The following tools are required to install the box.
Installation
Check for Transport Damage
Ensure the box is intact during and after transportation. If there are visible
damages such as cracks, contact your supplier immediately.
Unpacking
Unpack the box package by removing the packing tape. Ensure the box modules
and relevant items are complete. See the package items on section 4.4.3 and
check the packing list carefully. If there is any items missing, please
contact our company or your distributor directly.
CAUTION! According to regional regulations, it may require several people to move the equipment.
Accessories
Mounting Steps
Wall Mounting:
Step 1: Fix the wall bracket on the wall
- The bracket needs to be removed from the box. Measure it and mark the position of the two holes. The bubble of the spirit level should be centered.
- Drill holes at the depth of at least 2.36 inches/60 mm by a drill.
- Install the expansion screw tubes on the wall, and screw the wall bracket by a torque wrench.
Step 2: Match the box with the wall bracket
Hang the box over the wall bracket, move the box close to it and match it
on the wall bracket. Clip the buckle on the back of the box into the
threeslots of the back plate accurately. (Torque: 1.0-1.2 N·m)
CAUTION! Ensure that the system is always exposed to ambient air. The system is cooled by natural convection. If the system is entirely or partially covered or shielded, it may cause the system to stop operating.
Overall Installation
Depending on the connection with different battery systems, there are two parallel options, with details as follows
Connect with T-BAT-SYS-HV-3.0
NOTE
The recommended installation distance between the box and the battery group
(including slave group and master group) is 11.81-23.62 inches /300-600 mm,
and the distance between the modules is 9.84 inches/250.00 mm.
Before installation, please make sure that the wall can bear the weight of the
batteries installed. If not, please take the mode of floor installation.
Cable Connection
Connecting Cables to Inverter
Cable connection from the parallel box to the inverter:
NOTE
- It is recommended to protect the cables by using corrugated pipe.
- If you plug the cable into the wrong port, you can insert the power cable disassembling tool into the gap on the side of the joint to unplug the cable easily.
- Please refer to “battery connection” section of the inverter’s user manual/quick installation guide for details about inverter connection.
- If the connector of the T-BAT-SYS-HV-3.0 controller does not match the connector provided with the accessory cable, you can trim the blue connector and replace it with a black connector. The replacement should follow the rule of male-to-male and female-to-female connections. The Installation mode of black connector is as follows:
The wire order of the communication cable is as follows:
- Orange stripes on white
- Orange
- Green stripes on white
- Blue
- Blue stripes on white
- Green
- Brown stripes on white
- Brown
Connecting Battery Modules
For BMS Parallel box-Ⅱ G2 + T-BAT H 5.8 + 1/3/5/7 HV11550 battery pack(s)
From BMS Parallel box-Ⅱ G2 to T-BAT-SYS-HV-5.8:
If there is(are) a port(s) that is(are) not wired after wiring is completed,
please don’t forget to put the waterproof cap(s) on the port(s).
To form a complete circuit, connect “-” and “YPLUG” with series-connected
cable on the right side of the last battery module. Please check T-BAT-SYS-
HV-5.8 User Manual/Quick installation guide for detailed tutorial on cable-
connecting between T-BAT H 5.8 and HV10230 battery modules.
For BMS Parallel box-Ⅱ G2 + MC0600 + 2/4/6/8 HV10230 battery modules
From BMS Parallel box-Ⅱ G2 to T-BAT-SYS-HV-3.0:
Connecting Communication Cables
There is a protection cover for the RS485 connector. Unscrew the cover and
plug one end of the RS485 I communication cable to the RS485 I connector.
Tighten the plastic screw nut which is set on the cable with a rotation
wrench. The operation is the same as above if connecting to the COM1/BMS
connecter.
For T-BAT-SYS-HV-5.8 (RS485 I, BMS): For T-BAT-SYS-HV-3.0 (COM1, BMS):
Connect the communication cable from the parallel box to the COMM/BMS/RS485 I communication port that is on the left side of the battery module.
Connecting the Ground Wire
Remove the M5*10 screw from the bottom of the BMS Parallel box-Ⅱ G2 with a
screwdriver, and then screw the groung wire(10 AWG/6 mm) to the corresponding
grounding port
Commissioning
Configuring the Box
-
The DIP switch is used to configure the communication between battery module(s) and the device. By default, only two groups of batteries can be matched for use.
-
The black-start function is only used in an off-grid application and when there is no other power supply. To Black-start, hold down the button for 20 seconds until the soc light starts flashing blue to indicate successful black-start. If the box is started in the black-start mode, remind that even when there is no BMS communication, the port still contains high voltage with risk of electric shock.
If the BMS communication has still not been established within 3 minutes after starting the black-start mode, it indicates that the black start fails to start. -
After the BMS Parallel box-Ⅱ G2 is powered on, if the indicator lights alternate flashing red and green for more than two minutes, and then change to green flashing with the inverter reporting “Batt_ClusterCommuCount Mis-Match”, please check the communication connection of the second group of BMS Parallel box-Ⅱ G2, as well as the power-on status of T-BAT H 5.8 or MC0600 connected to the second group.
-
After the BMS Parallel box-Ⅱ G2 is powered on, if the indicator lights alternate flashing red and green for more than three minutes, and then change to flashing red for one second and off for three seconds, with the inverter reporting “BMS_Internal_Err 1”, it indicates that the corresponding slave at position 1 failed to connect to the communication successfully. According to the error number, please check if the communication line of the slave at the corresponding position is properly connected.
-
The BMS Parallel box-II G2 must be connected to two groups of batteries simultaneously in order to function properly, and the number of slaves in both groups must be the same. The second group of BMS Parallel box-II G2 must contains a T-BAT H 5.8 or Mc0600. And the two battery circuits connected to the BMS Parallel box-Ⅱ G2 must be all HV11550 or all HV10230, and it is not allowed to connect one group with HV11550 batteries and the other group with HV10230 batteries.
-
It is prohibited to plug or unplug the power line during the operation of the BMS Parallel box-Ⅱ G2.
Commissioning
After all battery modules are installed, please follow the following steps
to start the box:
- Open the waterproof cover board of the box;
- Move the circuit breaker switch to “ON”;
- Press the POWER button to start the box;
- Reinstall the cover board to the box;
- Turn on the inverter DC switch;
- After starting the box, please confirm that the waterproof cover board is closed again.
Status Indicators
The LED indicators on the front panel of the BMS and the battery modules
indicate the operating status.
Description of the status indicators of BMS is shown as follows:
The capacity indicators show the state of charge (SOC):
When the battery module is neither charging nor discharging, the indicator
lights are off.
When the battery module is charging, a part of the blue LED flashes once every
5 seconds, and a part of the blue LED is on. Take SOC 60% for instance, when
in charging state:
- The last two blue LED indicators are on
- The third blue LED indicators flash once evey 5 seconds When the battery module is discharging, the blue LED indicators flash once every 5 seconds. Take SOC 60% for instance, when in discharging state:
- The last three blue LED indicators flash once every 5 seconds
Troubleshooting
Check the indicators on the front to determine the state of the box.
A warning state is triggered when a condition, such as voltage or temperature,
is beyond design limitations. Box periodically reports its operating state to
the inverter.
When the box falls outside the prescribed limits, it enters into a warning
state When a warning is reported, the inverter immediately stops its
operation.
Use the monitoring software on the inverter to identify what caused the
warning.
The possible warning messages are as follows:
Decommissioning
To shut down the system and dismantling the box, please follow the steps below:
- According to the actual situation, please turn off the breaker located between the inverter and the parallel box.
- Press the POWER button to shut down the box.
- Move the circuit breaker switch to the OFF position.
- Ensure that every indicator on the box is off.
- Disconnect the cables between the box and inverter.
- Disconnect the series wiring terminal on the box.
- Disconnect the rest of cables.
- If needed, unmount the box from the wall bracket to remove it from the wall.
Packing
Pack the box in the original packaging. If the original packaging is no longer
available, use an equivalent carton or box that meets the following
requirements:
• Suitable for loads over 154.32 lbs/69.94 kg
• Properly closed and sealed
Maintenance
- If the ambient temperature for storage is 86°F~122°F/30 C ~50 C, recharge
- the batteries at least one time every 6 months.
- If the ambient temperature for storage is -4°F~-86°F /-20C ~30 C, recharge the batteries at least one time every 12 months.
- If the batteries have not been used for more than 9 months, these batteries must be charged to at least SOC 50 % each time.
- For the first installation, the interval among manufacture dates of battery modules shall not exceed 3 months.
- If a battery is replaced or added for capacity expansion, each battery’s SOC should be consistent. The max. SOC difference should be between +5%.
- If users want to increase their battery system capacity, please ensure that the SOC of the existing system capacity is about 40%. The manufacture date of the new battery shall not exceed 6 months; in case of exceeding 6 months, please charge the new battery to around 40%.
- Maintain periodically Only qualified person may perform the following works. During the process of using the box,the manage person shall examine and maintain the machine regularly.
The concrete operations are as follows.
- Check that if the cooling fans on the rear of house are covered by dirts, and the machine should be cleaned and absorbed dust when necessary. This work shall be check time to time.
- Check that if the indicators of the box are in normal state, check if the keys of the box are in normal state,check if the display of the system is normal. This check should be performed at least every 6 months.
- Check that if the input and output wires are damaged or aged. This check should be performed at least every 6 months.
- Check whether the ground terminal and ground cable are securely connected and all terminals and ports are properly sealed every 12 months.
- You should get the box panels cleaned and their security checked at least every 6 months.
Warranty
Triple Power protects this product under warranty when it is installed and
used as listed in this manual.
Violation of the installation procedure or use of the product in any way not
described in this manual will immediately void all warranties on the product.
Triple Power does not provide warranty coverage or assume any liability for
direct or indirect damages or defects that result from the following causes:
- Force majeure (flooding, lightning strike, overvoltage, fire, thunderstorm, etc.)
- Improper or noncompliant use.
- Improper installation, commissioning, start up or operation (contrary to the guidance detailed in the installation manual supplied with each product)
- Inadequate ventilation and circulation resulting in minimized cooling and natural air flow.
- Installation in a corrosive environment.
- Damage during transportation.
- Unauthorized repair attempts .
- Failure to adequately maintain the equipment. An on-site inspection by a qualified technician is possible following 120 months of continuous use.
- Warranty claims made beyond 120 months from date of commissioning may be declined if it cannot be demonstrated that the equipment has been adequately maintained.
- External influence including unusual physical or electrical stress (power failure surges, inrush current, etc.)
- Use of an incompatible inverter or devices.
- Connect to other brands of inverter without authority from our company.