HOYLES EX200 Series Door Alarm With Integral Keypad Control Instruction Manual
- June 1, 2024
- HOYLES
Table of Contents
HOYLES EX200 Series Door Alarm With Integral Keypad Control
EXITGUARD EX200 Series Installation Instructions
EX204 Battery powered for use where a separate supply of power is not available, and the protected door is opened infrequently or there is no requirement to sound the sounder for long periods. Can be powered from 12vdc if necessary.
(Discard batteries)
EX205 12vdc powered for use where the protected door may be opened frequently,
or the integral sounder needs to sound for protracted periods. This version
can also be interfaced with other equipment. There are volt free relay
contacts to separately signal ON/OFF status and alarm conditions at remote
points. Cannot be powered from batteries.
EX206 230vac powered version where the protected door may be opened frequently
or the sounder needs to sound for protracted periods. There is a volt free
alarm relay contact. This version is supplied with 6 x AA alkaline batteries
for standby purposes. Note: the batteries will not power the alarm relay.
All versions have keypad control, integral sounder with programmable tones, 5 mode LEDs, a front/back acting tamper switch and a logic output to signal to a MULTIGUARD indicator from HED. All are supplied with a door contact, fixing screws and door warning label.
Quick Install
Exitguards are NOT intended for external use and to avoid damage should not be
fixed to the protected door itself.
- The door contact is in two parts; the magnet should be fixed to the door and the contact with its cable fitted to the frame. The cable should be taken to the EXITGUARD and connected as shown. A is the alarm input for the switch element (RD/YL) of the contact and T is from the tamper loop (BL/BK) of the contact.
- Make all connections, apply power, a double bleep will be heard and the four mode LEDs will illuminate.
- When the EXITGUARD leaves the factory there are no codes in memory. The four illuminated red LEDs are inviting you to enter a User Code. This must be a four-digit memorable code. As the code is entered acknowledge bleeps are heard and each of the mode LEDs will extinguish. The code is now stored in memory and the EXITGUARD will emit a double bleep and should be in the OFF mode.
- OUT OF THE BOX factory default settings are suitable for most applications. On first use we recommend that you use these settings to test the EXITGUARD. They can be changed later to suit local requirements. Test by entering the user code and pressing I for Chime Mode. A chime will be heard each time the door is opened.
Advanced Installation
The following parameters can be changed through the keypad:
- User Code
- Select one of six different alarm tones
- Change auto re-arm delay 0 – 88 seconds
- Change Door Open Too Long (DOTL1) delay for keypad reset mode 0 seconds – 88 mins.
- Change DOTL2 delay for auto reset mode 0 seconds – 88 mins.
- Switch Bleep In Off (BIO) on or off.
- Add or change a Reset/Pass Code
- Add or change a Manager Code.
OUT OF THE BOX User Operation.
There are four possible modes:
Off Mode 0 Chime Mode I Keypad Reset Mode II Auto re-arm Mode III
When the User Code is entered the EXITGUARD is interrogated and one of the
mode LEDs illuminates to indicate the current status.
After the User Code is entered there is a 5 second window to change the mode,
e.g. If the current mode is OFF and it is desired to switch to the Keypad
Reset mode, just enter II i.e. number 2 on the keypad. Within 5 seconds the
LED will extinguish. If a mistake has been made this can be rectified before
the LED Extinguishes by simply selecting the desired mode, the
LED indication will change to the new mode.
If the Auto re-arm mode is selected, then the factory default period of 30
seconds will be used unless set up differently.
(see programming instructions to change the Auto re-arm period and other
functions)
EXITGUARD Set-up
The EXITGUARD contains a non volatile memory (NVM). The User Code and any
programmed functions are stored in this NVM even if power is lost for long
periods. If you have forgotten the User Code (or manager code if used) it will
be necessary to reset to the factory default settings. Any functions that you
have programmed will be lost. Before altering any functions such as the re-arm
period or door open too long delays (DOTL) etc.. consider if the factory
defaults will meet your requirements. The following scenarios are quite
typical. The first four involve no programming other than setting the User
Code. The remaining scenarios require a little programming.
-
Scenario 1. Typical Fire Exit Door.
An audible alarm is required when the door is opened. Use the factory default settings and arm the EXITGUARD for either Keypad reset II or Auto re-arm III mode. ie. the EXITGUARD silences and re-arms after a 30 second delay if the doorhas been closed. -
Scenario 2. Shop or Reception Door. A chime is required each time the door is opened Use the factory default settings and arm the EXITGUARD for Chime I mode.
-
Scenario 3. Fire Door Checker. The EXITGUARD can be used to verify that all Fire Exit Doors are available for use when a building is occupied. The R terminal of each EXITGUARD is connected to a switched +ve 12vdc of the building’s intruder alarm. When the alarm is set this signal is applied to the EXITGUARDs. When the intruder alarm is un-set the signal is removed and the EXITGUARDs will strobe and double bleep every 30 secs. Opening and re-closing the door causes the strobing and the periodic bleeps to cease. The EXITGUARD then automatically reverts to the mode it was set to during the previous period of occupancy; O, I, II or III. If the intruder alarm has been set in error it can be un-set and re-set without the necessity to onen and re-close all doors for checking.
-
Scenario 4. Loading Bay Door.
Invoke the Bleep In Off facility (see programming below). Arm the EXITGUARD in Keypad reset II mode. Switch Off with keypad for deliveries. The Bleep In Off will remind staff to re-arm the EXITGUARD after each delivery. -
Scenario 5. Fire Stop Corridor Door. Staff are able to pass through the door without generating an alarm but if left open then an alarm will be generated. Set the Auto re-arm period at 00 and DOTL2 delay at 10. Door must be closed within 10 seconds. It is recommended that a door closer spring is fitted. Arm the EXITGUARD in III mode. Scenario 6. Temporary Pass Through In this scenario a Pass Code is used to allow passage through to say a storeroom without the necessity to switch the EXITGUARD Off. When using a pass code there is a 10 sec window to open the door and a further time period to pass through and close the door. This time is specified by either DOTL1 or DOTL2, depending on which mode the EXITGUARD is armed in. To use a pass code DOTL1, DOTL2 or both must be set depending on whether you wish to use mode ll or Ill. See later instructions for setting DOTL1 and DOTL2. To return through the door a momentary +ve must be applied to the R terminal, this will bleep the unit and strobe the LEDs to warn that the door is about tonnon Armtho SXITClIARNin modoll or IIII.
High Level Security.
In some applications, it may be necessary to allow only selected persons to
change the various parameters. A Manager Code gives an extra level of security
by only allowing a managerto change:
- A. User and Pass & Manager Codes
- B. Bleep In Off (BIO)
- C. Auto re-arm delays
- D. Door Open Too Long delays (DOTL)
Programming. Before the EXITGUARD can be programmed a User Code must have been set up as detailed overleaf. The following functions can be programmed into the NVM:
- Fourdigit User Code.
- Select one of six different alarm tones
- Change auto re-arm time 0 – 88 seconds
- Change DOTL1 delay for keypad reset mode 0 seconds – 88 minutes.
- Change DOTL2 delay for auto reset mode 0 seconds -88 minutes.
- Switch Bleep In Off (BIO) on or off.
- Add or change a four-digit Reset/ Pass Code.
- Add or change a four-digit Manager Code. Prora mmina is carried out in Set-unmode
To Enter Set-up Mode. To enter this mode type the User Code and hold down the 7 key until two beeps are heard. The Set-up LED flashes. To leave this mode type 0. The system always reverts to the OFF when leaving Set- up. See also Manager Code later.
Changer User Code. In Set-up mode enter 1, a double bleep is heard and the four mode LEDs will illuminate inviting you to enter a new four-digit User Code UUUU. As each digit of the code is pressed an LED will extinguish. When the code is complete a double bleep is heard. The unit remains in the SET-UP mode and further programming can be carried out following the instructions below.
Tone Select.
In Set-up mode enter 2. A bleep is heard and a single-mode LED illuminates to indicate that a one digit number in the range 1 – 6 is needed.
The tones are:
1 & 2. High (Factory default setting is 1) Ear defenders are recommended!!!!!
3 & 4. Normal 5 & 6. Low If an incorrect digit is entered a ‘Barp’ will be
heard and the LED continues to indicate that a single digit is still required.
When a correct digit is entered the a short sample of the tone is played with
the strobing LEDs to indicate the selected tone. The Set-up LED flashes to
indicate that you are still in Set-up mode. Enter 0 to leave ifset-un is
comolete.
Auto re-arm period.
In Set-up mode enter 3. A bleep
is heard and two mode LEDs will illuminate to indicate that a two digit number
corresponding to the required period eg. 00 for instant re-arm, 05 for 5secs,
88 for 88secs etc… As the digits are entered the LEDs extinguish and a double
bleep is heard when both digits have been entered. The Set-up LED continues to
flash to indicate that vou are still in the Set-un model.
Door Open Too Long Delay for Keypad reset mode (DOTL1.)
In Set-up mode enter 4. A bleep is heard and the bottom two mode LEDs illuminate to request a two digit number for minutes eg. 00 for zero mins 05 for 5mins, 88 for 88 mins etc.. As the digits are entered the LEDs extinguish and a single bleep is heard when both digits have been entered. The top two mode LEDs now illuminate requesting a two digit number for seconds eg. 00 for zero secs, 15 for 15secs up to a maximum of 58secs. The maximum is therefore 88m58s. A double bleep is heard when all digits have been entered correctly. The Set-up LED continues to flash to indicate that you are still in the Set-up mode.
Door Open Too Long Delay for Auto re-arm Mode (DOTL2.)
In Set-up mode enter 5. The procedure is identical to the procedure for DOTL 1 above
Bleep In Off (BIO).
In Set-up mode BIO can be toggled On and Off . The default factory setting is Off, In Set-up mode enter 6. If one bleep is heard then BIO is off, if two bleeps are heard then BIO is on. Successively pressing 6 will toggle BIO on and off.
In Set-up mode BIO can be toggled On and Off. The default factory setting is Off, In Set-up mode enter 6. If one bleep is heard then BIO is off, if two bleeps are heard then BIO is on. Successively pressina 6 will toaale BIO on and off.
Add or change a Reset/Pass Code.
In set-up mode enter 7. A single bleep is heard and four mode LEDs illuminate inviting you to enter a four digit Reset/Pass Code PPPP. As each digit is entered an LED will extinguish. When the code is complete a double bleep is heard. The Set-up LED continues to flash to indicate that you are still in the Set-up mode. Ensure DO TL 1 and DOTL2 are set.
Add or Change a Manager Code.
In set-up mode enter 8. a triple bleep is heard and four mode LEDs illuminate inviting you to enter a four digit Manager Code MMMM. As each digit is entered an LED will extinguish. When the code is complete a double bleep is heard. To change any further settings in future you will need to use the Manager Code in order to enter the set-up mode ratherthan the User Code. Note: If the EXITGUARD has been set up with a Manager Code then both the User Code and Manager Code must be used to enter the set-up mode and change any settings. Proceed as follows: Enter the User Code UUUU, Press and hold 7. The LED illuminates steady Enter the Manager Code M MM M, the LEDflashes. To delete a Pass or Manager Code use the User Code for either or both.
Leave Set-up Mode.
In Set-up mode enter 0, a double bleep is heard as the EXITGUARD leaves set-up mode. The EXITGUARD will now be in the OFF mode as indicated by the OFF LED. Whilst this LED is illuminated the EXITGUARD can be switched to any other mode I, II or III or even back to Set- up mode by pressing and holding 7.
Hoyles Electronic Developments Ltd
Sandwash Close, Rainford, St Helens, WA11 8LY, UK
www.hoyles.com
sales@hoyles.com
+ 44 (0) 1744 886600
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>