Honeywell 2306M5001 Unipoint Flammable Toxic Gas Detection Controlle Instruction Manual

June 15, 2024
Honeywell

Honeywell 2306M5001 Unipoint Flammable Toxic Gas Detection Controller

Honeywell 2306M5001 Unipoint Flammable Toxic Gas Detection
Controlle

Safety

Ensure that this manual is read and understood BEFORE installing / operating / maintaining the equipment.

WARNINGS

Unipoint is designed for installation and use in indoor safe area non- explosive atmospheres. Installation must be in accordance with the recognized standards of the appropriate authority in the country concerned.

Unipoint should be installed inside a lockable enclosure or in a secure location to prevent unauthorized access.

Before carrying out any work ensure local regulations and site procedures are followed. Work must only be conducted by trained personnel. Take any necessary precautions to prevent false alarms. The detectors/sensors that the controller connects to may be used for gas detection in hazardous atmospheres. Refer to the individual detector/sensor instructions for their details.

The fault and alarm relay outputs may be used to switch voltages in excess of 50Vac. Ensure circuits have DOUBLE or REINFORCED insulation and are segregated in accordance with the voltage being switched and access is restricted to authorized personnel only.
Unipoint must be zero and span calibrated with the detector before operation.
Disposal should be according to local waste management requirements and environmental legislation. Alternatively contact your local Honeywell Analytics representative.

Honeywell Analytics can take no responsibility for installation and/or use of its equipment if this is not done in accordance with the appropriate issue and/or amendment of the manual. The reader of this manual should ensure that it is appropriate in all details for the exact equipment to be installed and/or operated. If in doubt, contact Honeywell Analytics for advice.
Every effort has been made to ensure the accuracy of our documents; however, Honeywell Analytics can assume no responsibility for any errors or omissions in our documents or their consequences.
Honeywell Analytics greatly appreciates being informed of any errors or omissions that may be found in the contents of any of our documents. For information not covered in this document, or if there is a requirement to send comments/ corrections about this document, please contact Honeywell Analytics.
Honeywell Analytics reserve the right to change or revise the information supplied in this document without notice and without obligation to notify any person or organization of such revision or change. If information is required that does not appear in this document, contact the local distributor/agent or Honeywell Analytics.

Introduction

Unipoint is a self-contained single channel gas detection controller for use in indoor safe areas.
It is designed for use with any mV flammable gas detector as well as any 2 wire or 3 wire 4-20mA source gas detector. Unipoint is DIN rail mounted and displays gas concentration, alarm, fault and status information via its backlit LCD and LEDs, as well as providing a built in audible alarm. A keypad located below the display provides the facility to make changes to the system configuration. Unipoint is powered from 24VDC via the DIN rail. The detectors are connected to the controller via terminals on the side of the controller where terminals for remote inhibit/reset and output relays are also located.
There are two versions of Unipoint controller available. The mV version is for use with 3 wire mV flammable gas detectors such as the Signalpoint or Sensepoint range of flammable detectors. The 4-20mA version is for use with 2 wire and 3 wire 4-20mA source detectors such as the Signalpoint or Sensepoint range of toxic and oxygen detectors. It has 4 buttons: up, down, ‘x’ reset and OK, that are used navigate through the menus and change the configuration settings.
All Honeywell Analytics gas detectors and third party detectors subject to overall power requirements.

Installation

WARNING

Unipoint is designed for installation and use in indoor safe area non- explosive atmospheres. Installation must be in accordance with the recognised standards of the appropriate authority in the country concerned. Prior to carrying out any installation ensure local regulations and site procedures are followed. The detectors used with Unipoint are often designed for use in hazardous atmospheres. Refer to the individual detector instructions for details of their installation.

Mechanical Installation

  • Outline Dimensional Drawing
    Outline Dimensional Drawing

The Unipoint controller is mounted on standard symmetrical ‘top hat’ DIN Rail (35 x 7.5mm).
To attach the Unipoint controller to the DIN rail follow the procedure below use the Installation Diagram as reference.

  1. Clip the Unipoint controller socket on to the DIN rail (note the correct orientation from the diagram below).
  2. Clip the power connector on to the DIN rail beside the controller socket.
  3. Slide the connector and socket together until clip engages.
  4. Attach the Unipoint Controller on to the socket by gently but firmly pushing it down onto the socket until it clips in place.
  5. Additional Unipoint Controllers can be added to the DIN rail on the right hand side of the first unit. Clip additional controller sockets to rail and slide together until clips engage. Then attach the additional Unipoint Controllers.

Note : If mounting the Unipoint controller(s) inside an enclosure, ensure that the temperature inside the enclosure does not exceed the specified operating temperature.

  • Installation Drawing
    Installation Drawing

  • DIN Rail Drawing

Electrical Installation

Unipoint Controller Selection

Detector| Gas Type| Nº Wires| Unipoint Controller Required
---|---|---|---
Signalpoint| Flammable Toxic| 3
2| mV mA
Sensepoint| Flammable Toxic| 3
2| mV mA
Sensepoint Plus| Flammable Toxic| 3
3| mA mA

Power Connection

Max number of Unipoint controllers on one DIN Bus

Detector Type Max number of controllers
3 wire mV 8
2 wire mA 8
3 wire mA 4

Unipoint Controller Maximum Power Consumption.

Unipoint version Controller status Relays Power
Fault Alarm
mV Normal operation, no faults, no alarms. Zero cable resistance. Energised
De energised 2.4W1
mV Normal operation, no faults, no alarms. Max loop cable resistance (28
ohms) Energised De energised 3.6W1
mV All alarms, no faults. Max cable resistance (28 ohms) Energised
Energised 4.8W1
mA Normal operation, no faults, no alarms. Inclusive of 2 wire signal loop
current. Energised De energised 1.8W2
mA All alarms, no faults. Inclusive of 2 wire signal loop current.
Energised Energised 3.0W2
  1. includes power to detector
  2. excludes power to 3 wire mA detector.
    All controllers with default configuration.

Terminal Detail

All electrical connections except power are made via removable terminals located on the top and bottom of the controller. The power connection is made via the power connector attached to the DIN rail.
Terminal Detail

For security we recommend the use of Key Switches for the remote reset and inhibit inputs mounted on the front of the enclosure in which the Unipoint is mounted.

Detector Types

Unipoint can accept signals from three types of detector. The table below summarizes the types of detector compatible with Unipoint.

Type of detector Output to detector Recommended detector
2 wire 4-20mA Controller Input (18-32Vdc)-1.5*Vdc, 30mA (max). Sense resistor
33 Ohms. Signalpoint or Sensepoint Toxic and Oxygen
3 wire 4-20mA source Controller Input (18-32Vdc)-1.5*Vdc, 0.5A (max). Sense
resistor 33 Ohms. Sensepoint Plus
3 wire mV bridge 2.4-8.6V, 200mA constant current. Max cable loop resistance
28 Ohms. Signalpoint or Sensepoint Flammable
  • Voltage drop in Unipoint Controller

Generic Detector Wiring Schematics

To connect the detector to the Unipoint use a 2 or 3 wire cable (as appropriate) that is suitably armoured (e.g. Steel Wire Armour) or conduit according to local requirements. Acceptable wire cross sectional area is from 0.5 to 1.5 mm2 with overall screen. Connect the screen to ground at the enclosure that the Unipoint is mounted in.

  • 3 Wire mV Bridge
    3 Wire mV Bridge

  • 2 Wire 4-20mA
    2 Wire 4-20mA

  • 3 Wire 4-20mA Source
    3 Wire 4-20mA Source

Maximum Cable Lengths

mA Detectors

To calculate the maximum cable run length from power source to the detector refer to the following example diagram and formula.

Rloop = (Vcontroller – 1.5V – Vdetector min) / Idetector

Maximum cable run length = Rloop / cable per metre resistance where:

  • Rloop = maximum working cable loop resistance
  • Vcontroller = maximum available supply voltage at controller
  • Vdetector min = minimum voltage at which the connected sensor can operate (sensor dependent, see individual sensor technical manual/ data sheets)
  • Idetector = sensor maximum drawn current. 30mA for 2 wire mA detectors. See individual detector technical manual/data sheets for max power consumption of 3 wire detectors.

mV Detectors

To calculate the maximum cable run length to the detector refer to the following typical example cable resistances. Max cable loop resistance = 28 ohms.

Solid Copper Conductor

Cross Sectional Area| Maximum resistance at 20ºC (ohm/bucle/km)
(mm2)| AWG
0.50| 21| 72
0.75| 19| 50
1.00| 18| 36
1.50| 16| 24
Stranded Copper Conductor
Cross Sectional Area| Maximum resistance at 20ºC (ohm/bucle/km)
(mm2)| AWG
0.50| 21| 73.6
0.75| 19| 49
1.00| 18| 35.2
1.50| 16| 23.4

Default Configuration

Unipoint has user configurable settings that allow the set up of the system to individual application requirements. Unipoint is supplied from the factory with a default configuration. These configurations are based on settings typically used in gas detection systems. Details of how to reconfigure Unipoint are given in section 7.

Unipoint mV Input Version

Function Default configuration
Password 000 (Disabled)
Display range and units 0-100%LEL
Alarm Relay 1 Alarm level 1 10%LEL (Rising)

Non-latching, normally de energized, energizes on alarm. Relay activation delay=0 seconds
Relay de-activation hold=0 seconds
(Single Pole change over, 240Vac/30Vdc, 3A max)
Alarm Relay 2| Alarm level 2 25%LEL (Rising)
Non-latching, normally de energized, energizes on alarm. Relay activation delay=0 seconds
Relay de-activation hold=0 seconds
(Single Pole change over, 240Vac/30Vdc, 3A max)
Alarm Relay 3| Alarm level 3 50%LEL (Rising)
Latching, normally de energized, energizes on alarm. Relay activation delay=0 seconds
Relay de-activation hold=0 seconds
(Single Pole change over, 240Vac/30Vdc, 3A max)
Fault Relay| Non-latching, normally energized, de-energizes on fault. (Single Pole change over, 240Vac/30Vdc, 3A max)
Inhibit| Controller inhibit activates fault relay.

Unipoint 4-20mA Input Version

Function Default configuration
Password 000 (Disabled)
Display range and units 0-100ppm
Current input 0 mA                  Fault (open circuit)

4.0 to 20.0mA     Gas reading (normal operation)

1.5 to 2.5mA       Inhibit from sensor (configuration mode)

20.0mA            Overrange

Alarm Relay 1| Alarm level 1 10% of full scale (Rising)
Non-latching, normally de energized, energizes on alarm. Relay activation delay=0 seconds
Relay de-activation hold=0 seconds
(Single Pole change over, 240Vac/30Vdc, 3A max)
Alarm Relay 2| Alarm level 2 25% of full scale (Rising)
Non-latching, normally de energized, energizes on alarm. Relay activation delay=0 seconds
Relay de-activation hold=0 seconds
(Single Pole change over, 240Vac/30Vdc, 3A max)
Alarm Relay 3| Alarm level 3 50%LEL (Rising)
Latching, normally de energized, energizes on alarm. Relay activation delay=0 seconds
Relay de-activation hold=0 seconds
(Single Pole change over, 240Vac/30Vdc, 3A max)
Fault Relay| Non-latching, normally energized, de-energizes on fault. (Single Pole change over, 240Vac/30Vdc, 3A max)
Inhibit| Controller inhibit activates fault relay and de-activates alarm relays. Field inhibit active (1.5 to 2.5mA on detector input).
Detector Type| 2 Wire 4-20mA

Switch On

After connecting power, the controller enters a self test routine: All LCD segments flash, the fault and alarm LED flash, the sounder operates three times, the RAM, ROM and EEPROM are checked and the software version is displayed. If no faults are found (see section 7.5 for fault codes) the unit enters a detector warm up period indicted by a count down from 60 to 0 on the display. During this time the controller is inhibited (‘Inh’) so all alarms and faults are inactive.
At the end of the warm-up period the controller checks for detector and field wiring faults. If a fault is found, the fault code is displayed (see section 7.5 for fault codes). If no fault is found the controller enters normal operation and will display current gas reading and alarm(s) if appropriate.

Initial Configuration

WARNING

Unipoint must be zero and span calibrated with the detector before operation.

If the default configuration shown in section 5.1 (mV type controller) or 5.2 (mA type controller) does not match the application requirements, follow the procedures below to reconfigure the controller.
Notes : If using a mA version controller with a 3 wire mA type detector, carry out the procedure in section 7.1 first to set the correct detector type.
If configuring the controller for use with an Oxygen detector, skip the ‘Set zero’ instructions (steps 7-14) and use 20.9% (background air oxygen level) as the span calibration point.
After completing all the steps in a menu, the 3 button must be pressed to save the changes.
Press x at any time to ignore the changes made in the current menu.

  1. Press the buttons together to enter the configuration mode.

  2. Press to enter the ‘Set Range and Units (FS)’ menu.

  3. The default range flashes. Press the buttons to select the required range.

  4. Press 3 to set the new range.

  5. The default units start flashing. Press the buttons to select the required units.

  6. Press to set the new units. (See section 9 for available ranges and units).

  7. Press the button to select the ‘Set Zero (0)’ menu.

  8. Press to enter the ‘Set Zero (0)’ menu.

  9. The current zero gas reading is displayed.

  10. Apply zero gas to the detector.

  11. Press when the reading is stable.

  12. The display will show ‘—’ while calculating the zero point and then ‘0’ when complete. If the zero fails ‘FFF’ is displayed.

  13. Remove the zero gas from the detector.

  14. Press to complete the zero calibration.

  15. Press the t button to select the ‘Set Span (S)’ menu.

  16. Press to enter the ‘Set Span (S)’ menu.

  17. 50% of the set range flashes.

  18. Press buttons to set the concentration of the span calibration gas concentration being used.

  19. Press to set the span calibration concentration.

  20. Apply the span calibration gas to the detector.

  21. The ‘live’ gas reading is displayed.

  22. If the reading is too low ‘S-L’ is displayed, if too high ‘S-H’ is displayed.

  23. 23. When the reading is stable press .

  24. ‘—’ is displayed while calculating the new span.

  25. The display then shows the new span value. If span fails ‘FFF’ is displayed.

  26. Remove the span gas from the detector and allow the display to return to zero.
    Note : Allowing the reading to return to zero before exiting ensures no accidental alarms are triggered.

  27. Press to return to the menu.

  28. Press the button to select the ‘Set Alarms (A1)’ menu.

  29. Press to enter the ‘Set Alarms (A1)’ menu.

  30. The current alarm 1 set point flashes.

  31. Press buttons to change the A1 set point.

  32. Press to confirm.

  33. The display shows the current alarm relay on delay in seconds.

  34. Press buttons to change the alarm relay on delay.

  35. Press to confirm.

  36. The display shows the current alarm relay off (hold) delay in seconds.

  37. Press buttons to change the alarm relay off delay.

  38. Press to confirm.

  39. The display shows the current alarm 1 relay configuration.

  40. Press buttons to select either ‘F’ for falling or ‘r’ for rising alarm point.

  41. Press to confirm.

  42. Press buttons to select either ‘E’ for normally energized or ‘d’ for normally de-energized relay.

  43. Press to confirm.

  44. Press buttons to select either ‘L’ for latching or ‘n’ for non-latching relay.

  45. Press to confirm.

  46. The display now shows the current alarm 2 level.

  47. Repeat steps 31 to 46 for alarm 2 and then alarm 3.

  48. Press ‘x’ to return to normal operation.

Note : For details of other settings in the configuration menu refer to section 9

Setting Detector type (mA version only)

The default detector type setting for a mA version controller is 2 wire. If using a 3 wire mA type detector carry out the procedure below:

  1. Press the buttons together to enter the configuration mode.
  2. Press  or   buttons to select the ‘Detector Type (IP)’ menu.
  3. The current detector input type flashes (2L=2 wire mA).
  4. Press the buttons to select 3L=3 wire mA).
  5. Press to confirm.
  6. Press x to return to normal operation.
  7. Follow the procedures in section 7 to complete the initial configuration.

Normal Operation

In normal operation the green Power LED is illuminated and the 1st line of the LCD shows the current gas reading. The 2nd line is used to display text codes that provide additional information about the type of event that has occurred. An alarm, fault/inhibit LED and built in sounder are also used when signaling events.

Display and Push Button Layout

Display and Push Button Layout

*A packet of stick on gas labels are supplied with each Unipoint Controller.

Normal Operation LCD Event Codes

The display event codes are shown below:

NORMAL OPERATION DISPLAY TEXT CODES

CODE| EVENT TYPE
A| –| 1| Alarm point 1 exceeded
A| –| 2| Alarm point 2 exceeded
A| –| 3| Alarm point 3 exceeded
O| F| F| All outputs disabled
F| X| X| Fault. XX=Fault code
I| n| h| Remote or field* inhibit

Display, Sounder and Relay Operation

The table below shows the default operation of the display, sounder and relays for given events.

EVENT LCD **LEDS*** SOUNDER RELAY
ALARM FAULT/INH A1 A2 A3
Alarm 1 threshold exceeded A-1 flashing off on
Alarm 2 threshold exceeded A-2 flashing off on
Alarm 3 threshold exceeded A-3 flashing off on
Fault FXX off flashing on
Inhibit Inh off flashing off
Overange Or/A3 flashing off on

*LED flash frequency: Alarm = 2Hz, Fault = 1Hz and Inhibit = 0.5Hz.

Accept/Resetting Alarms

In normal operation, the X button on the controller front panel or a switch connected to the remote reset terminal is used to reset/accept alarm events. The effect of reset/accept dependent on gas reading and alarm latching setting is described below:

| Gas reading still exceeds alarm threshold| Gas reading below alarm threshold
---|---|---
Latched alarm| Sounder stops. Flashing alarm LED changes to steady. Gas reading and alarm code displayed on LCD. Alarm relay remains in alarm state.| Sounder stops. Alarm LED is turned off. The LCD alarm code clears. Alarm relay returns to original state.
Unlatched alarm| Sounder stops. Flashing alarm LED changes to steady. Gas reading and alarm code displayed on LCD. Alarm relay remains in alarm state.| Alarm indications and relay operation reset automatically without need for reset/accept.

Note : If the controller is in inhibit when an alarm threshold is exceeded the alarm LED only will operate. See section 10 for details of how the relay delay and hold function effects the operation of the unit.

Fault Codes

Below are the fault codes and recommended action to clear the fault.

FAULT CODE DESCRIPTION TROUBLE SHOOT
F S
F N D
F I F
F R
F C
F E

Inhibit

The controller is put into inhibit via a normally open switch connected to the inhibit terminal or when entering configuration mode. The inhibit is maintained until the switch is opened again or on return to normal operation mode.
Additionally, an inhibit signal of between 1.5mA to 2.5mA can be signaled to the controller from a field device. This facility is only available on mA version controllers (see section 9).
When in inhibit the alarm relay and sounder do not operate. The alarm LED will operate if the alarm threshold is exceeded. The 2nd line of the LCD will show Inh (except in configuration mode where a slow flashing fault LED indicates the inhibit).
The controller can also be disabled using the disable function in the configuration mode (see section 9).
See section 10 for details of how the relay delay and hold function is affected by inhibit.

Overrange

When the gas reading exceeds full scale ‘Or’ replaces the gas reading to indicate an over range condition. The 2nd line of the LCD continues to show the alarm state. If alarm level 3 is configured latching then the over range condition will also latch (default for 3 wire mV version).

Self Test

The controller enters a self test routine at power on. It can also be forced into a self test by pressing the button in normal operation. The controller automatically conducts a self test at regular intervals.

Configuration

From normal mode press the buttons together to enter configuration mode. If no password has been set the display will go directly to the menu selection. If a password has been set then the display will show ‘OOO’ and the 1st digit will flash. Press to change the first digit of the password.
Press to move to the next digit. Repeat to set the 2nd and 3rd digits of the password. Press x at any time to exit and return to normal mode. Press after setting the 3rd digit to confirm the password and enter the menu selection. If the password entered is incorrect the display will return to normal mode. Use the table below to help navigate the menu and make configuration changes.

| OK| | OK| | OK| | OK| | OK|
---|---|---|---|---|---|---|---|---|---|---
RANGE AND **UNITS (FS)*| | RANGE FLASHES. PRESS TO SELECT NEW RANGE| | UNITS FLASH. PRESS TO SELECT NEW UNITS.| | NEW RANGE AND UNITS SETTINGS CONFIRMED. RETURNS TO MAIN MENU| | | |
SET ZERO**

(0)**

| | CURRENT ZERO GAS READING DISPLAYED. APPLY ZERO GAS.| | ‘—‘ DISPLAYED WHILE MEASURING THEN ZERO READING DISPLAYED. IF ZERO FAILS ‘FFF’ IS DISPLAYED. REMOVE GAS.| | NEW ZERO SETTING CONFIRMED. RETURNS TO MAIN MENU| | | |
SET SPAN

(S)**

| | 50% OF RANGE FLASHES. PRESS

TO SET CAL GAS CONCENTRATION

| | APPLY CALIBRATION GAS. LIVE GAS READING DISPLAYED. ‘S-L’ IF TOO LOW, ‘S-H’ IF TOO HIGH.| | ‘—‘ DISPLAYED WHILE MEASURING THEN NEW SPANNED READING. IF SPAN FAILS ‘FFF’ IS DISPLAYED. REMOVE GAS| | NEW SPAN SETTING CONFIRMED. RETURNS TO MAIN MENU| |
SET ALARMS (A1, A2, A3)| | CURRENT ALARM 1 SET POINT FLASHES. PRESS 56 TO CHANGE.| | PRESS TO SELECT ALARM ON DELAY

(0 to 900 secs)

| | PRESS TO SELECT ALARM OFF DELAY (0 to

900 secs)

| | ALARM 1 RELAY CONFIGURATION DISPLAYED. PRESS 56 TO SELECT ‘F’=FALLING OR ‘r’=RISING| |
| PRESS TO SELECT ‘E’=ENERGIZED OR ‘d’=DE-ENERGIZED.| | PRESS TO SELECT ‘L’=LATCHING OR ‘n’=NON- LATCHING| | NEW ALARM SETTINGS CONFIRMED. RETURNS TO MAIN MENU. REPEAT FOR ALARM 2 & 3.| | | |
SET FAULT RELAY (F)| | FIRST FAULT RELAY SETIING FLASHES. PRESS

56 TO SELECT ‘E’=ENERGIZED OR ‘d’=DE- ENERGIZED.

| | PRESS TO SELECT ‘IF’=FAULT RELAY ACTION ON INHIBIT OR ‘In’=NO ACTION ON INHIBIT.| | NEW FAULT RELAY SETTINGS CONFIRMED. RETURNS TO MAIN MENU| | | |
SET PASS WORD (PAS)| | FIRST DIGIT OF CURRENT PASSWORD FLASHES. PRESS   TO CHANGE FIRST DIGIT.| | SECOND DIGIT OF PASSWORD FLASHES. PRESS TO CHANGE SECOND DIGIT.| | THIRD DIGIT OF PASSWORD FLASHES. PRESS TO CHANGE THIRD DIGIT.| 3| NEW PASSWORD CONFIRMED. RETURNS TO MAIN MENU| |
DISABLE (dIS)| | DISPLAY SHOWS ‘dIS’| | LOWER LINE OF DISPLAY SHOWS ‘OFF’. PRESS X AND 3 SIMULTANEOUSLY FOR >1 SECOND TO TAKE UNIT OUT OF INHIBIT.| | | | | |
FIELD INHIBIT

**(FIh)*****

| | PRESS TO SELECT ‘Inh’= DETECTOR IN- HIBIT ON OR ‘FAL’ FOR DETECTOR INHIBIT OFF| | DETECTOR INHIBIT SETTING CONFIRMED. RETURNS TO MAIN MENU.| | NOTES:

Detector inhibit signal range = 1.5mA to 2.5mA.

All steps in the respective menu option must be completed and 3 pressed for the changes to be saved. Pressing X before confirmation of new settings returns to main menu with no changes to configuration.

*See section 9 for available ranges and units.

**If configuring the controller for use with an Oxygen detector, skip the ‘Set zero’ instructions and use 20.9% (background air oxygen level) as the span calibration point.

***Only available on mA input version

DETECTOR **TYPE (IP)*****| | CURRENT DETECTOR INPUT TYPE FLASHES. PRESS TO SELECT ‘2L’= 2 WIRE mA OR ‘3L’=3 WIRE mA| | DETECTOR INPUT SETTING CONFIRMED. RETURNS TO MAIN MENU.|
| OK| | OK| | OK| | OK| | OK|

Ranges and Units

Below are the possible combinations of range and units for the two Unipoint Controller types:

Unipoint Controller Units Available Full Scale Ranges
mV or mA version %LEL
%VOL 2.00; 3.00; 5.00; 10.0; 15.0; 20.0; 25.0; 50.0 of 100
PPM 2.00; 3.00; 5.00; 10.0; 15.0; 20.0; 25.0; 50.0; 100; 150; 200; 300; 400;

500 of 1000

Alarm Relay On/Off Delay

Part of the ‘Set Alarms’ configuration allows a user programmable delay for each alarm threshold between the detection of an alarm and the activation of the alarm relay output, and a programmable hold between the clearing of an alarm and the release of the relay output. The delay times are adjustable over the range 0 to 900 seconds (900 sec equals 15 mins). The default delay times are 0 (no delay).

WARNING

If an alarm relay activation delay is set to greater than 0 secs the presence of a gas concentration in excess of the alarm threshold will not be immediately signaled.

Alarm Relay On Delay

The programmable alarm relay delay operates in the following manner:

  • If the delay is set, then in the event of the GAS CONCENTRATION EXCEEDING the alarm threshold the following occurs:
  • The LCD, LED, and buzzer signal the alarm.
  • The alarm relay output does not signal the occurrence of the alarm immediately.
  • The delay counts down.
  • When the delay has expired, the relay output then signals the alarm.
  • If during the delay the GAS CONCENTRATION FALLS below the alarm threshold and the alarm is configured as NON-LATCHING, the indication of the alarm on the LCD, LED, and buzzer is removed and the delay reset.
  • If during the delay the gas CONCENTRATION FALLS below the alarm threshold and the alarm is configured as LATCHING, the indication of the alarm on the LCD, LED, and buzzer remains, the delay continues to run and the relay output is updated when the delay time has expired.
  • If during the delay the GAS CONCENTRATION IS ABOVE the alarm threshold and the ACCEPT/RESET INPUT/KEY is activated to accept the alarm, the LCD, LED, and buzzer will respond as per section 7.4, the delay continues to run and the relay output is updated when the delay time has expired.
  • If during the delay the GAS CONCENTRATION FALLS BELOW the alarm threshold, the alarm is configured as LATCHING, and the ACCEPT/RESET EXTERNAL INPUT/KEY is activated to reset the alarm, the LCD, LED, buzzer and the delay time reset.
  • If during the delay the unit is placed into INHIBIT by either the external inhibit or by entering the configuration mode, the delay will be reset. On exiting the inhibit mode the relay output will be updated.
  • If during the delay a FAULT is signaled, the delay will continue and the relay output updated when the delay time has expired. (The alarm will continue to be signaled on the sounder, LED, and LCD after the fault occurs. The relay output will be updated to reflect the alarm when the time expires.)

Alarm Relay Off Delay

The programmable alarm relay hold operates in the following manner

  • If the hold time is set, then in the event of the GAS CONCENTRATION FALLING below the alarm threshold after previously exceeding the alarm threshold for a period of time greater than the delay time (i.e. the relay output is reflecting the active alarm) and the alarm threshold is configured as NON-LATCHING the following occurs:
    • The LCD, LED, and buzzer will stop signaling the alarm.
    • The alarm relay does not signal the absence of the alarm immediately.
    • The hold time counts down.
    • When the hold time expires, the relay output is updated to signal the absence of the alarm.
  • If during the hold time the gas CONCENTRATION RISES back above the alarm threshold, the LCD, LED, and buzzer signal the re-occurrence of the alarm and the hold time is reset.
  • If during the hold time the ACCEPT/RESET EXTERNAL INPUT/KEY is activated, the relay output is updated immediately.
  • If during the hold time the unit is placed into INHIBIT by either the external inhibit or by entering the configuration mode, the hold time is reset. On exiting the inhibit mode the relay output is updated immediately.
  • If during the hold time a FAULT is signaled, the hold time is reset and the relay output is updated immediately.
  • If the alarm is configured as LATCHING, the hold time has no effect upon the operation of the unit. i.e. The signaling of a latched alarm via the relay output will removed immediately the accept/reset external input/key is activated.

Maintenance

The Unipoint controller has no user serviceable parts. Honeywell Analytics recommend that the controller’s configuration and operation are checked annually.
The gas detectors connected to the controller should be checked and if necessary zero and span calibrated by following the procedures detailed in their user guides.

Ordering Information

Unipoint Controllers

Unipoint Controller (mV input version) 2306B2000
Unipoint Controller (mA input version) 2306B1000

Spares

Unipoint Terminal Block Plug (x2) 2306B3010
Unipoint DIN rail socket kit 2306B3020
Unipoint power connector kit 2306B3030

Warranty Statement

All products are designed and manufactured to the latest internationally recognized standards by Honeywell Analytics under a Quality Management system that is certified to ISO 9001.
As such Honeywell Analytics warrants its products against defective parts and workmanship and will repair or (at its option) replace any instruments which are or may become defective under proper use within 12 months from date of commissioning by an approved Honeywell Analytics representative or 18 months from date of shipment from Honeywell Analytics, whichever is the sooner. This warranty does not cover disposable batteries or damage caused by accident, abuse, abnormal operating conditions or poisoning of sensor.
Defective goods must be returned to Honeywell Analytics premises accompanied by a detailed description of any issue. Where return of goods is not practicable Honeywell Analytics reserves the right to charge for any site attendance where any fault is not found with he the equipment. Honeywell Analytics shall not be liable for any loss or damage whatsoever or howsoever occasioned which may be a direct or indirect result of the use or operation of the Contract Goods by the Buyer or any Party.
This warranty covers instrument and parts sold to the Buyer only by authorized distributors, dealers and representatives as appointed by Honeywell Analytics. The warranties set out in this clause are not pro rata, i.e. the initial warranty period is not extended by virtue of any works carried out there under.

Appendix A- Specification

Specification

Use| The Unipoint controller provides integrators with a flexible and low cost solution to the many applications requiring flammable, toxic or oxygen gas detection to be incorporated into their control systems. Unipoint is designed to use industry standard DIN rail allowing it to be easily installed into many different types of plastic or metal, indoor or outdoor, hazardous or non hazardous area enclosures. It is designed for use with any mV flammable gas detector as well as any 2 or 3 wire 4-20mA gas detector (subject to overall power requirements).
User interface
Operation| Two push buttons for normal operation of resetting alarms and initiating self diagnostic test of system. Four buttons for user programmable functions via intuitive menu
Backlit display| Units of measure, digital gas reading and event code
Other indication| Ultra-bright steady/flashing LEDs subject to condition; alarm (red), power (green), fault (amber). In-built

audible alarm 63dB at 0.3 meters.

Termination| Easily accessible plug in screw type terminals. Terminals accept maximum wire diameter 1.5mm2
Environmental
IP Rating| IP30 (Install in suitable enclosure)
Weight| 225g (Controller only)
Operational

Temperature Humidity Pressure

| -10oC to +55oC / 14oF to 131oF (Performance approval -10°C to +40°C / 14°F to 104°F) 10 to 90%RH (non condensing) 90-110 kPa
Storage| -25°C to +60°C / -13°F to +140°F, 20 to 80%RH (non condensing)
Inputs
Supply| Nominal 24Vdc (18-32Vdc). Max power mV = 4.8W (including power to detector), mA= 3.0W (excluding power to 3 wire detector).
Detector type| 3 wire mV bridge e.g. Sensepoint or Signalpoint flammable gas detectors| 2 wire, 4-20mA, loop powered e.g. Sensepoint or Signalpoint toxic or oxygen gas detectors| 3 wire, 4-20mA, source output e.g. Sensepoint Plus

and Pro flammable, toxic and oxygen gas detectors

Detector supply| 2.4-8.6V, 200mA constant current. Maximum loop resistance: 28 Ohms| Input (18-32Vdc)-1.5Vdc, 30mA max.| Input (18-32Vdc)-1.5Vdc, 0.5A max.
Outputs
Relays| Alarm 1| Alarm 2| Alarm 3| Fault
Rating| SPCO / 3A, 240Vac/30Vdc (non inductive load)| SPCO / 3A,

240Vac/30Vdc (non inductive load)

| SPCO / 3A,

240Vac/30Vdc (non inductive load)

| SPCO / 3A,

240Vac/30Vdc (non inductive load)

Default setting| Non Latching Normally de-energized Energize on alarm
Factory setting 10%FSD| Non Latching Normally de-energized Energize on alarm
Factory setting 25%FSD| Latching (mV)
Non Latching (mA) Normally de-energized Energize on alarm Factory setting 50%FSD| Non Latching Normally energized De-energize on fault/ power loss
User configurable options| Latching/non-latching Energized/de-energized Alarm trip point Rising/falling
Alarm on / off delay (0 to 900 seconds)| Latching/non-latching Energized/de- energized Alarm trip point Ris- ing/falling
Alarm on / off delay (0 to 900 seconds)| Latching/non-latching Energized/de- energized Alarm trip point Rising/falling
Alarm on / off delay (0 to 900 seconds)| Latching/non-latching Energized/de- energized
Approvals
EMC/RFI| EN50270
Electrical safety| EN61010
Performance| ATEX measuring function EN60079-29-1 SIRA10ATEX8243X
Other| CE, TUV.

Approvals

Unipoint is performance approved to EN60079-29-1 (measuring function) for use with Signalpoint, Sensepoint (Combustible) and any 4-20 mA device.

Caution: Unipoint is a safe area device. It must not be installed in hazardous areas.

Special Conditions of Use

  1. The user/installer shall comply with the following environmental restrictions that apply to the use of this equipment, as stated in the product manual.
    Temperature (Equipment): -10°C to 40°C
    Temperature (Standard combustible sensor): -40°C to 80°C
    Temperature (High temperature sensor): -55°C to 150°C
    Humidity: 10% to 90%
    Pressure: 90 kPa to 110 kPa

  2. The user/installer shall install these products taking into account any restrictions or special conditions for safe use that are applicable to the previously certified devices that are used in their construction.

  3. When used, the Sensepoint and the Signalpoint Gas detectors shall be powered from Unipoint DIN controller.
    Special Conditions of Use

EC Declaration of Conformity

EC Declaration of Conformity
The undersigned of
Honeywell Analytics Ltd
4 Stinsford Road
Poole, Dorset
BH17 0RZ
UK
Declares that the products listed below

Unipoint Controller (mA input version) 2306B1000
Unipoint Controller (mV input version) 2306B2000

The Unipoint is a simple DIN rail mounted controller offering integrators a flexible and low cost solution to incorporate flammable, toxic or oxygen gas detection into their control systems.

are in conformity with the provisions of the following European Directive(s), when installed, operated, serviced and maintained in accordance with the installation/operating instructions contained in the product documentation:
2004/108/EC EMC Directive
2006/95/EC Low Voltage Directive
94/9/EC ATEX Directive ñ Equipment for use in Potentially Explosive Atmospheres

and that the standards and/or technical specifications referenced below have been applied or considered:

Harmonised Standard Description
EN 50270:2006 Electromagnetic Compatibility – Electrical apparatus for the

detection and measurement of combustible gases, toxic gases or oxygen
BS EN 50271:2002| Electrical apparatus for the detection and measurement of combustible gases, toxic gases or oxygen.
Requirements and tests for apparatus using software and/or digital technologies
EN 60079-29-1:2007| Explosive atmospheres. Gas detectors. Performance requirements of detectors for flammable gases
EN 61010-1:2001| Safety requirements for electrical equipment for measurement, control and laboratory use.

Notified Body for ATEX: Certificate Number Quality Assurance Notification Number
Sira Certification Service Sira 10ATEX8243X Baseefa ATEX 5192
Rake Lane
Eccleston Type Approval
Chester II (2)/2 G D
CH4 9JN
Notified Body Number: 0518

Signature:
Name: Steve Hamilton
Position: Senior Regulatory Compliance Engineer
Date: 9 September 2010
Declaration Number: 2004Y0014_01/A03209
Declaration of Conformity in accordance with EN ISO/IEC 17050-1:2010

Customer Support

Find out more
www.honeywellanalytics.com
Europe, Middle East, Africa, India
Life Safety Distribution AG
Weiherallee 11a
CH-8610 Uster
Switzerland
Tel : +41 (0)44 943 4300
Fax : +41 (0)44 943 4398
gasdetection@honeywell.com
Americas
Honeywell Analytics Inc.
405 Barclay Blvd.
Lincolnshire, IL 60069
USA
Tel : +1 847 955 8200
Toll free : +1 800 538 0363
Fax : +1 847 955 8210
detectgas@honeywell.com

Asia Pacific
Honeywell Analytics Asia Pacific

508, Kolon Science Valley (I)

187-10 Guro-Dong, Guro-Gu
Seoul, 152-050
Korea
Tel : +82 (0)2 6909 0300
Fax : +82 (0)2 2025 0329
analytics.ap@honeywell.com

Technical Services
EMEAI : HAexpert@honeywell.com
US : ha.us.service@honeywell.com
AP : ha.ap.service@honeywell.com

Please Note:
While every effort has been made to ensure accuracy in this publication, no responsibility can be accepted for errors or omissions.
Data may change, as well as legislation, and you are strongly advised to obtain copies of the most recently issued regulations, standards, and guidelines. This publication is not intended to form the basis of a contract.
Issue 7 01/2011
H_MAN0638_V7
2306-M-5001 ECO A03469
© 2011 Honeywell Analytics