lae ELECTRONIC CD5-100-240V Refrigeration Defrost Controller User Manual
- June 1, 2024
- Lae ELECTRONIC
Table of Contents
lae ELECTRONIC CD5-100-240V Refrigeration Defrost Controller
Specifications:
- Model: CD5 SERIES
- Manufacturer: LAE Electronic
- Installation: First configuration
Product Usage Instructions
Installation:
Before installing the instrument, please read the instruction booklet
carefully for safe installation and optimum performance.
Display Information:
The display provides information on various aspects including alarm status,
compressor output, fan output, defrost output, and more. In case of an alarm,
press any key to mute the buzzer sound.
Operation Setting:
Configure the operation settings by confirming, increasing,decreasing, or
discarding values as needed. You can also control the light function.
Parameter Setting:
To customize parameters, access the SETUP menu from the INFO menu using
password 123.
Parameters Profiles:
Parameters such as readout scale, minimum and maximum temperature setpoints,
thermostat settings, and defrost configurations can be adjusted to match your
requirements.
Alarm Threshold Management:
Set alarm thresholds for low and high temperatures,differentials, probe usage,
and alarm delay to manage temperature alarms effectively.
Stand-by and Digital Input Operations:
Configure stand-by button enabling, door switch input mode, door alarm delay,
compressor stop delay, digital input operations, and light control mode for
enhanced functionality.
Frequently Asked Questions (FAQ):
Q: How can I access the parameter setting menu?
A: To access the parameter setting menu, go to the INFO menu and enter
the password 123 to enter the SETUP menu for parameter customization.
Q: What should I do in case of a high-temperature alarm?
A: If a high-temperature alarm occurs, take necessary actions to address
the issue promptly to prevent any potential damage or product malfunction.
Thank you for having chosen an LAE Electronic product. Before installing the instrument, please read this instruction booklet carefully in order to ensure safe installation and optimum performance.
INSTALLATION
-
Insert the controller through a hole measuring 71×29 mm.
-
Make sure that electrical connections comply with the paragraph “wiring diagrams”.
To reduce the effects of electromagnetic disturbance, keep the sensor and signal cables wellseparate from the power wires. -
Place the probe T1 inside the room in a point that truly represents the temperature of the stored product.
-
Place the probe T2 on the evaporator where there is the maximum formation of frost.
-
The function of probe T3 is determined by the parameter T3.
DISPLAY INFO
In case of alarm, press any key to mute the buzzer sound.
OPERATION
SETTING
DEFROST START
DEFROST TERMINATION
Resuming thermostatic cycle. When defrost is over, if DRN is greater than 0,
all outputs will remain off for DRN minutes, in order for the ice to melt
completely and the resulting water to drain. Then, after the FTO time has
elapsed, the evaporator fans will restart. Differently, if T2=YES and this
probe measures the FDD temperature before FTO elapses, then the fans re-start
immediately.
Caution: if DFM=NON all defrost functions are inhibited; if DFT=0, automatic
defrost functions are excluded. During defrost, high temperature alarm is
bypassed.
CONFIGURATION PARAMETERS
FIRST CONFIGURATION
At the first power-up, “SEt” is displayed, to indicate that the controller
needs a first configuration.
Tap , PS will be displayed. Once again tap , then select the profile desired
among the options available via or . After selecting the option of choice, tap
again. The display will now show SCL (readout scale). If need be, by tapping ,
you return to the selection of the profile.
Tap , then select the readout scale desired via or . In closing tap again.
The controller is now ready to be used.
First configuration
PARAMETER SETTING
To obtain a customised configuration of the parameters, get access to the SETUP menu from the INFO menu with password 123.
PARAMETERS PROFILES
WIRING DIAGRAM
TECHNICAL DATA
Power supply
- CD5 100-240Vac +10%, 50/60Hz, 3W
Relay outout max loads
Input
- NTC 10K0@25°C LAE Part No. SN4…
Measurement Range
- 50….. 110°C; -50 / -9.9…19.9 °C / 110°C
- 58… 180°F
Measurement accuracy
- <0.5°C on the whole measurement range
Operating conditions
-
10… +50°C; 15%..80% r.H.
-
Purpose: Operating Control
-
Construction: Incorporated Control
Indoor type 1 enclosure
Type 1B Action -
Impulse voltage: 2500V
Pollution degree 2
Reference Norms
- IEC/EN 60079-15
- EN61000-6-1
- EN61000-6-3
- EN/UL60730-1
- EN/UL60730-2-9